SOLICITATION NOTICE
36 -- Upgade of Governor Systems at Amistad Dam
- Notice Date
- 2/5/2002
- Notice Type
- Solicitation Notice
- Contracting Office
- International Boundary and Water Commission, Information Management Division, Acquisition Division, 4171 North Mesa, Suite C-310, El Paso, TX, 79902
- ZIP Code
- 79902
- Solicitation Number
- IFB-02-04
- Response Due
- 4/18/2002
- Archive Date
- 5/3/2002
- Point of Contact
- Theresa Hyman, Contract Specialist, Phone (915) 832-4718, Fax (915) 832-4192, - Irma Gurrola, Office Automation Clerk, Phone (915) 832-4716, Fax (915) 832-4192,
- E-Mail Address
-
theresahyman@ibwc.state.gov, irmagurrola@ibwc.state.gov
- Small Business Set-Aside
- Total Small Business
- Description
- Furnish all materials, parts, equipment, engineering analysis, engineering design, and labor necessary to install digital upgrades to two existing Woodward Electric Hydraulic MOD II Governor systems that will integrate with the existing turbine and generator controls. Work is to be performed at the Amistad Dam Power Plant located at Amistad Dam on the Rio Grande approximately 12 miles northwest of the City of Del Rio, Texas. Existing controls include speed adjust, gate position, gate limit, brake, and damping. The systems to be installed by the contractor shall use Solid State Electronic Digital Speed Control, shall provide start/stop, speed control, and loading functions for Unit One and Unit Two without sacrificing any- of the existing capabilities of the Units. The systems shall include a PC based Human Machine Interface (HMI) to be used as the operator interface. The systems shall continuously sample and log all analog outputs from the units. The systems will integrate starting, speed control, synchronization, loading, and stopping of the existing hydroelectric generator. The systems shall provide information on the status of generator, speed, voltage, vars, breaker condition, load, current, frequency, wicket gate position, gate limit position, mode of operation, flow in cubic meters per second, and shall allow for the monitoring of twelve (12) alarm points. The systems shall be programmable by the Government's power plant personnel, have the capabilities and components to automatically synchronize Unit One and Unit Two to the electrical power grid that is connected to the Units and have the capabilities for self-diagnostics to determine proper operation conditions and parameters. The contractor shall provide four (4) complete sets of operating manuals, catalog cuts, and parts books of the systems. The contractor shall provide four (4) sets of As Built drawings, layout diagrams, and schematics of the electrical, electronic, mechanical, and hydraulic systems. A 100% warranty covering all labor, parts, and components for a period of twelve months, one year, beginning on the date of Government acceptance of the systems and installation will be provided. The systems shall be compatible with and wired to the existing Harris D20 SCADA Systems that currently provide for remote starting and stopping of the generators, raising and lowering Unit One and Unit Two speed, opening and closing of the wicket gates, and monitoring of operating conditions and alarms from or to the dispatch office in Nursery, Texas. Control of the above functions shall remain from the control room (panel) as it is at present and from the HMI. Tentative dates for issuing and closing IFB 02-04 are March 5, 2002 and April 18, 2002 respectively. The contractor shall provide a bar diagram schedule within 15 calendar days of the Government's issuance of Notice to Proceed. The contractor shall complete all work activities within 60 calendar days of the Government's approval of the contractor's schedule. This solicitation and any resulting contract are subject to the terms and conditions of the Walsh-Healy Public Contracts Act. Specifications will be available for inspection, without charge, at the International Boundary and Water Commission, U.S. Section, The Commons, Building C, Suite 224, 4171 North Mesa Street, El Paso, Texas 79902-1441. Copies of the bid package are available at no charge. All requests for bid documents must be in writing; no telephone or facsimile requests will be accepted. Requests for IFB 02-04 must be sent to the attention of Ms. Irma Gurrola at the preceding address. Requests must include business name, point of contact, address, telephone number (include area code), and IFB number. This requirement is a 100% set-aside for small business concerns. The North American Industry Classification Systems (NAICS) code for this acquisition is 335314 for Relay and Industrial Control Manufacturing. The associated small business size standard is 500 employees.
- Place of Performance
- Address: Amistad Dam, 12 NW of Del Rio, Val Verde County, Texas
- Zip Code: 78840
- Country: USA