Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY ISSUE OF JANUARY 02, 2003 FBO #0396
MODIFICATION

J -- Repair/Rewind 7500 KVA Transformer

Notice Date
12/31/2002
 
Notice Type
Modification
 
Contracting Office
Department of the Air Force, Air Mobility Command, 375th Contracting Squadron, 201 East Winters Street Building 50, Scott AFB, IL, 62225-5015
 
ZIP Code
62225-5015
 
Solicitation Number
F11623-03-Q-0002
 
Response Due
1/6/2003
 
Archive Date
1/21/2003
 
Point of Contact
Joe Pasqualucci, Contract Specialist, Phone 618-256-3001, Fax 618-256-2652, - Cindy Showers, Contract Specialist, Phone 618-256-9250, Fax 618-256-5237,
 
E-Mail Address
joe.pasqualucci@scott.af.mil, cindy.showers@scott.af.mil
 
Description
THE PURPOSE OF THIS MODIFICATION IS TO POST THE ANSWERS TO THE FOLLOWING FIVE QUESTIONS THAT HAVE BEEN ASKED BY VARIOUS VENDORS. 1. How accessible is the transformer, are there any obstacles a crane needs to be concerned with when trying to move the unit? ANSWER. No overhead obstacles. A 6-foot high fence surrounds transformer. It is 20 feet from fence to center of transformer. 2. Can you supply overall dimensions and dimensions with the bushings removed so handling and shipping can be decided? ANSWER. Overall Height is 134 inches xWidth 140 inches Length 165inches. HV bushing is 21 inches tall. Arresters are 24 inches, LV bushing is 14 inches. 3. Is previous test result available on the transformer? ANSWER. No, transformer is only about 5 years old. 4. Is information available about what going on before and during the failure? ANSWER. HV bushing was discolored, so it was decided to change it, we pumped down the oil and went and changed the bushing, then pumped the oil back in. When we reenergized the transformer, it failed. Upon inspection it appeared that the no-load tap changer may have been accidentally bumped because that is where it looks like it started arching and copper from that may have shorted the HV windings to LV windings. 5. What is the weight of the transformer? ANSWER. The approximate weight of the transformer is as follows: Core and Coils 22,500 lbs, Tanks and fittings 18,400 lbs, Type II Mineral Oil; Main Tank (2,190 gallons) 16,000 lbs, LTC Tank (150 gallons) 1,100 lbs. Total weight with oil is 58,000 lbs.
 
Place of Performance
Address: Patriot's Landing Military Family Housing, Scott AFB IL
Zip Code: 62225-5015
Country: USA
 
Record
SN00232817-W 20030102/021231213417 (fbodaily.com)
 
Source
FedBizOpps.gov Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |