- Description
- The contractor shall provide all supervision personnel, equipment, transportation, material and all other items and service necessary to perform the following: 1. Replace broken insulator on High Voltage Regulator (1 each). McGraw Edison, Catalog #WA341A200RAA, KVA 416.3, Load Amps 548. Replace insulator is on hand. Replace insulating oil and test on completion of repair. Remove used oil. 2. Inspect Nitrogen levels on High Voltage step down transformer (2 each). Westing house, 68800/7560-13090Y, 10,000 KVA, serial #PGP-11442. Add Nitrogen to required levels if needed. Contractor shall provide Nitrogen.\ 3. Inspect, test and calibrate High Voltage Vacuum Breakers (9 each). ABB, Type R, 15KV, 600 Amp Provide Test result documentation.