SOLICITATION NOTICE
Y -- Replace stator iron and rewind the generators of Unit 4 and Unit 6 at Wolf Creek Power plant, Russell County, Kentucky. Work at Unit 6 is currently offered as an option.
- Notice Date
- 4/27/2004
- Notice Type
- Solicitation Notice
- NAICS
- 335312
— Motor and Generator Manufacturing
- Contracting Office
- USA Engineer District, Nashville, P.O. Box 1070, 801 Broad Street, Nashville, TN 37202-1070
- ZIP Code
- 37202-1070
- Solicitation Number
- W912P5-04-R-0013
- Response Due
- 6/16/2004
- Archive Date
- 8/15/2004
- Point of Contact
- John Anders, 615-736-7912
- E-Mail Address
-
USA Engineer District, Nashville
(john.anders@usace.army.mil)
- Small Business Set-Aside
- N/A
- Description
- The Nashville District Corps of Engineers intends to issue a firm fixed price construction contract for civil works construction to replace stator iron and rewind the generators of Unit 4 and Unit 6 at Wolf Creek Power plant, Russell County, Kentucky . Work at Unit 6 is currently offered as an option. Generators are designed for star connection of the stator winding with each phase consisting of four parallel paths of 38 three-turn coils, for a total of 456 coils and slots. There are sixteen strand s per turn. Coil insulation is of the asphalt-mica type. Generator ratings, as defined by the nameplate stamping information are as follows: 50,000 kVA, 0.9 Power Factor, 13,800 V, 3-phase, 60 Hz, 105.9 RPM, 115 percent overload capability. The solicitation will be issued on or about May 17, 2004. This solicitation will be located electronically at http://www.lrn.usace.army.mil on or about May 17, 2004. The North American Industry Classification System (NAIC) Code for this procurement action is 335312. The magnitude of construction for this project will be between $5,000,000.00 and $10,000,000.00. The requirements specified in the solicitati on are considered to be minimum requirements. The relative importance of the evaluation factors are identified. Sub factors and items within sub factors are listed in descending order of importance. Note that the evaluation factors, and sub factors in V olume I Technical Proposal when combined, are slightly more important than Volume II Price Proposal. Volume II Price Proposal will be comparatively evaluated for reasonableness after Volume I Technical Proposal is evaluated. The awardee must be registered in the Central Contractors Registration database. Information regarding the Central Contractors Registration can be located electronically at http://www.ccr.gov. The Government intends to award this contract without discussions. The complete bid packag e shall be submitted to the U.S. Army Corps of Engineers, 110 9th Avenue South, Nashville, Tennessee 37203, Room A604, Attention: John W. Anders. Point of contact regarding this action is John W. Anders, (615) 736-7912, email john.w.anders@usace.army.mil, or Lannie Summers at (615) 736-7939. Anticipated issuance of the Solicitation is scheduled on about May 17, 2004. NOTE: THIS NOTICE WAS NOT POSTED TO WWW.FEDBIZOPPS.GOV ON THE DATE INDICATED IN THE NOTICE ITSELF (27-APR-2004); HOWEVER, IT DID APPEAR IN THE FEDBIZOPPS FTP FEED ON THIS DATE. PLEASE CONTACT fbo.support@gsa.gov REGARDING THIS ISSUE.
- Web Link
-
Link to FedBizOpps document.
(http://www.eps.gov/spg/USA/COE/DACA62/W912P5-04-R-0013/listing.html)
- Place of Performance
- Address: USA Engineer District, Nashville P.O. Box 1070, 801 Broad Street Nashville TN
- Zip Code: 37202-1070
- Country: US
- Zip Code: 37202-1070
- Record
- SN00573758-F 20040429/040427212830 (fbodaily.com)
- Source
-
FedBizOpps.gov Link to This Notice
(may not be valid after Archive Date)