- This modification provides answers to questions posted on Modification 07 on April 18, 2006. 1) Engine Generators - Is a permanent load bank really required with the generator or is this just for startup testing? Response: A permanent load bank is required. 2) Is electrical piping for interior work EMT? Response: Rated galvanized conduit with watertight fittings shall be used inside the building. Refer to wiring methods in notes on each drawing. 3) Is buried conduit PVC (from Pole P11 to ransformer/generator)? Response: Buried conduit shall be rigid galvanized conduit.