Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY ISSUE OF SEPTEMBER 18, 2008 FBO #2488
SPECIAL NOTICE

99 -- Contractor to provide all labor, material and equipment to move Liebert Units in server room closer to server, build a wall and close off service room from Admin/ Tech section at building 1607, Fort Detrick, Md.

Notice Date
9/16/2008
 
Notice Type
Special Notice
 
NAICS
238990 — All Other Specialty Trade Contractors
 
Contracting Office
Department of the Army, U.S. Army Medical Research Acquisition Activity, U.S. Army Medical Research Acquisition Activity, US Army Medical Research Acquisition Activity, ATTN: MCMR-AAA, 820 Chandler Street, Frederick, MD 21702-5014
 
ZIP Code
21702-5014
 
Solicitation Number
W81XWH-08-B-0037
 
Response Due
8/25/2008
 
Archive Date
12/15/2008
 
Point of Contact
Thomas Hood, 301-619-8585<br />
 
Small Business Set-Aside
N/A
 
Description
This amendement is to answer technical questions. The bid opening date is 9/22/08 at 1:30 pm. 1.Is type L copper, as specified by Liebert, an option for the pumped refrigerant piping for the XD system? Yes, type L piping is allowable. 2.Can I get a list of material ordered by the Government from Liebert so I can confirm all parts needed for a complete installation? The Governement will be providing the XDH units, the XDC unit and the outside condensing unit. The contractor is to provide all interconnection refrigerant piping (primary and secondary) and quick connects for the XDH units. A complete equipment list will be provided to the successful bidder. 3.Is the side of the building adjacent to the existing condenser location acceptable for the new condensers? The location outside of the building adjacent to the existing condensor is acceptable. Maintain manufacturer's recommended spacing to prevent reintrainment of condensor air. 4.Can primary refrigerant piping for the Liebert XD system be routed above the ceiling? Primary refrigerant can be routed above the ceiling if the contractor so desires. 5.Is the government furnishing the quick connect ports with the XD system? See reply to comment 2.
 
Web Link
FedBizOpps Complete View
(https://www.fbo.gov/?s=opportunity&mode=form&id=89d9a410ac947e3a2546a918e9199d39&tab=core&_cview=1)
 
Record
SN01671572-W 20080918/080916220529-89d9a410ac947e3a2546a918e9199d39 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers