MODIFICATION

99 -- Gym Water Infiltration

Notice Date
5/27/2009
 
Notice Type
Modification/Amendment
 
NAICS
238330 — Flooring Contractors
 
Contracting Office
Department of Labor, Employment Training Administration, Homestead Job Corps Center, 12350 SW 285 Street, Homestead, Florida, 33033
 
ZIP Code
33033
 
Solicitation Number
Gym-45402
 
Response Due
5/9/2008
 
Archive Date
7/4/2009
 
Point of Contact
Zooaycka Mercado, Phone: 305-257-4820
 
E-Mail Address
mercado.zooaycka@jobcorps.org
(mercado.zooaycka@jobcorps.org)
 
Small Business Set-Aside
N/A
 
Description
Findings: rain water is infiltrating the perimeter of the building,causing damage to the interior flooring and finishes and contributing to the humid atmosphere of the building. Additionally, the fluted block wall has numerous cracks and voids creating more area of water infiltration. Recommendations: A. Provide all necessary labor and materials to perform regrading and perimeter drainage: 1. Excavate along the exterior southeast, southwest and northeast walls down to the base of the foundation. Apply fibrous asphalt waterproofing conforming to ASTM D4479, Type II, to the entire perimeter of the foundation wall/grade beam. Application shall be in two coats. 2. Provide and place corrugated perforated polyethylene 6" diameter drainage pipe in a gravel bed at the foundation of the building. Tie in all drainage pipes and connect to one discharge pipe leading to the nearest drainage swale. 3. Backfill and compact the area with soil as excavated, up to the top of the grade beam and sloping away from the building for a minimum distance of eight feet or to the sidewalk. 4. Reseed all disturbed areas with an appropriate grass seed common to the area. B. Masonry Cleaning, restoration and sealing. 1. The work under this section includes the cleaning and sealing of all exterior wall surfaces along the southeast, southwest and northeast elevations of the building. Cleaning and sealing of the Northwest elevation shall begin at 8 foot elevation from the floor and continue to the full elevation of the wall. Added: <input type="hidden" name="dnf_class_values[procurement_notice][description][1][added_on]" value="2009-03-18 11:27:15">Mar 18, 2009 11:27 am Modified: <input type="hidden" name="dnf_class_values[procurement_notice][description][1][modified_on]" value="2009-05-27 16:21:44">May 27, 2009 4:21 pm Track Changes Walk-Thru is schedule for Wednesday, March 25th, 2009 at 2:00 pm If needed, site visits will be done by appointment only and NO VISITS after March 27th, 2009, Friday.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/DOL/ETA/HomesteadJCC/Gym-45402/listing.html)
 
Place of Performance
Address: Homestead Job Corps Center, 12350 SW 285th Street, Homestead, Florida, 33033, United States
Zip Code: 33033
 
Record
SN01828038-W 20090529/090527235148-9bca5aa37eb1b32f6a07974f86c3f08a (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.