Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY ISSUE OF SEPTEMBER 17, 2009 FBO #2854
SOLICITATION NOTICE

Z -- Cooling Towers - Fan Motors & VFD Upgrade - Attachment 3 - Chillers Points Lists - Attachment 1 - Building Automation Control System Schematic - Attachment 4 - Sequence of Operations - Formatted RFQ RRB09Q050 - SF1449 - page 1 for RRB09Q050

Notice Date
9/15/2009
 
Notice Type
Combined Synopsis/Solicitation
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
Railroad Retirement Board, Acquisition Management Division, OA, Procurement Section, 844 North Rush Street, 9th Floor NE, Chicago, Illinois, 60611-2092
 
ZIP Code
60611-2092
 
Solicitation Number
RRB09Q050
 
Archive Date
10/10/2009
 
Point of Contact
Paul T. Ahern, Phone: (312) 751-7130, Karen J. Haskins-Brewer, Phone: (312) 751-4615
 
E-Mail Address
ahernpat@rrb.gov, karen.haskins-brewer@rrb.gov
(ahernpat@rrb.gov, karen.haskins-brewer@rrb.gov)
 
Small Business Set-Aside
N/A
 
Description
SF1449 Page 1 of SAP RFQ RRB09Q050 Formatted word version of RFQ RRB09Q050 Attachment 4 - Sequence of Operations Attachment 1 - Building Automation Control System Schematic Attachment 3 Chillers 1 and 2 - points Lists I. A.General This is a combined/solicitation Synopsis for a Sim[plified Acquisition procurement for Upgrades to the Colling Systems for the RRB as follows: 1. The RRB headquarters facility is a 14 story federal building located at 844 N. Rush Street, Chicago, IL 60611. It was erected in 1939. The facility's HVAC system, and more specifically its cooling systems, includes the water cooled chillers and cooling towers. 2. The purpose and scope of this Simplified Acquisition Procurement project is to procure materials and services from a responsible contractor to (replace and) upgrade the cooling towers fan motors, including integrating variable frequency drives, in order to improve the efficiency of cooling operations and thereby save budget resources. B. Project Objectives 1. Furnish and install the (4) fan motors of the (2) cooling towers on the roof with new fan motors and variable frequency drives (VFDs). Locate the VFDs in the designated room on the facility's 13 th floor. Provide all electrical power circuits and cabling needed to support /supply the furnished and installed VFDs and the fan motors. 2. The installed VFDs shall have bypass and LON communication capability. 3. Connect and ensure proper communications and integration of the VFDs with the Building Automation Control System (BACS). The nearest JACE node of the BACS is located on the ninth floor. (See attachment 1 ) 4. Program the BACS to operate the VFDs in accordance with the government approved Sequence of Operation. 5. Provide complete test and acceptance of the installed system component retrofit and a final validation that the Cooling Tower Fan Motor/VFD upgrade is integrated into the BACS and that all control loops are fully operational according to design. 6. Modify existing system graphics to include new equipment (Fan Motors and VFDs) and control loops. II. SCHEDULE OF SUPPLIES AND SERVICES A. Price schedule Offeror shall provide firm fixed prices for the products and services listed below: CLIN 001 Variable Frequency Drives and any accessories or accompanying components 4 EA; 002 Fan motors for cooling towers and any accessories or accompanying components 4 EA; 003 Installation Services, including all labor, supervision, subcontracts as applicable, wiring and incidental materials to complete the requirements 1 JOB; 004 Programming of TRIDIUM graphics and workflow for the BACS 1 JOB; II B. Contractor Information for Ordering and Contract Administration including 1. Order address: 2. Business Size; 3. Federal Tax Id # 4. DUNS No; 5. Remit Address: 6. GSA MAS Offer Contract Number if applicable with copy; 7. Authorized representatives contact information Business and Technical 8. Central Contractor Registration (CCR) completed - O fferor must be registered on CCR to be eligible for award if a Contract or order. 9. As referenced in C3 above, (Extract from:) Offeror Representations and Certifications-Commercial Items (Aug 2009) FAR 52.212-3 III. STATEMENT OF WORK A. Existing Conditions (typical for each cooling tower) 1. There are (2) cooling towers on the roof of this facility. Each cooling tower has (2) fan motors housed on the exterior frame of each cooling tower. Each fan is powered with a two-speed 20 H, 480/3/60 fan motors. 2. The motors are fed from the motor control center in the basement. Each cooling tower has a dedicated two-speed motor starter. The remaining verbiage in this section pertains to a single cooling tower, and is typical for both: a. A single three-phase feed enters the motor starter and terminates at a 100-amp circuit breaker. b. From the line side of the breaker, the feed splits into two separate three-phase feeds, each going to a NEMA 3 size contactor, one designated as "low speed", and the other designated as "high speed". c. From the line side of each contactor, the three-phase feeds (two sets of three wires) run up to the roof. 3. Up at the roof, each three-phase feed to the fan motors hits a local disconnect, and the splits into two separate three-phase feeds. a. The "low speed" feeds terminate at the low speed legs of each motor. b. The "high speed" feeds terminate at the high speed legs of each motor. 4. Operation is such that, when the starter is commanded to operate on low speed (either manually or automatically via the control system), the "low speed" contactor is engaged, and both fan motors are energized to operate at low speed. Conversely, when the starter is commanded to operate on high speed, the "high speed" contactor is engaged, and both fan motors are energized to operate at high speed. B. Required Modifications (typical for each cooling tower) 1. Furnish and install two (2) new fan motors for each cooling tower (4 total) and a 20 HP VFD for each cooling tower fan motor (4 total) a. Furnish new motors for all cooling tower fans. Furnish a new 20HP 460/3/60 single speed motor rated for outdoor use (TE enclosure type), for each of the four cooling tower fans. b. Modify the motor starter control panels to eliminate starter functionality, such that the control panel serves only as a circuit breaker and disconnect switch. c. Disconnect the "low speed" feeds from the line side of the low speed contactor. These will not be re-used. Cap the conductors in a suitable manner. d. Up at the roof, intercept the three-phase "high speed" power wiring out to the motors. e. Furnish and install a VFD with three-contactor bypass for each motor (two fan motors per tower, thus two VFDs per tower). VFD manufacturer shall be ABB (to match the installed base of VFDs in the facility. f.S plit the "high speed" power wiring into two separate appropriately sized three-phase feeds, and terminate each three-phase feed to the line side of each VFD. g. Extend new three-phase feeds from the load side of ach VFD out to each motor, terminating at the "high speed" legs of the motors. h. Provide local disconnect service conforming to the National Electrical Code (NEC), either by re-using the existing disconnect or by providing new weather-tight disconnect switches. i. Provide installation wiring and rewiring of all the new cooling tower fan motors. 2. Required Control Wiring and Programming a. Run communication wiring, daisy-chaining the VFDs, and terminating at the JACE on the ninth floor. b. Program the control system to acknowledge the newly added equipment, and to operate the new equipment in accordance with the Sequence of Operation (fan speed control to maintain high-bound temperature setpoint of condenser water supply to chillers). c. Create graphics to reflect new equipment and control loops. Engage the end-user in the creation process. C. Test and Acceptance / Upgrade Installation Validation 1. Conduct start-up and operations of the VFDs, either by authorized factory personnel or by a qualified on-staff technician certified by the manufacturer to provide such service. 2. Confirm two-way communication between the BACS (connected JACE node) and the VFDs. 3. Send a manual command (through the control system) to run the VFDs through their entire speed/frequency range. Confirm proper operation and interoperability of the VFDs and the fan motors per the accepted sequence of operations (see current sequence at Attachment 4 ). 4. Implement the necessary control loops as required by the Sequence of Operation. Confirm the temperature control schemes as operable. 5. Upon the Contractor's completion of system installation, start-up and checkout, the government shall be informed in writing. The government shall select a representative to walk through the system. The Contractor will explain all of the system functions in detail and demonstrate system operation. Notation shall be made and the government and Contractor will address each issue until all are resolved to the satisfaction of the Government. At that point the training for the government on the operation of the system will be scheduled (see III.D.4 below). 6. Provide engineer control drawings (as-builts) of the upgraded system. 7 Document and date the validation process, for inclusion in the closeout documentation (see III.D.3 below). D. Work Quality Requirements, Assumptions and Constraints 1. The system will be installed by licensed electricians and trained mechanics in the direct employment of the electrical and temperature controls contractors. The controls contractor must be Tridium and Circon certified. 2. All conduit and piping will be installed in a neat and workman-like manner parallel or perpendicular to the building structure by a qualified electrician. 3. Fastening shall be secured to walls or ceilings by means of the appropriate screws, expansion screw anchors, toggle bolts, hollow wall screws, nylon expansion anchors or expansion shields. Plastic anchors referred to as "rawls" will not be accepted. 4. All wiring line and low voltage shall be protected in a metal raceway. 5. All VFD's and equipment shall be mounted on vibration free surfaces or a uni-strut frame. Multiple systems may be incorporated in a common enclosure. 6. No patching or painting is required. 7. Asbestos removal is not included in the scope of work. 8. All work must be conducted during normal working hours of the facility from 7:00 a.m. to 4:30 p.m. Monday through Friday except federal holidays. E. Project Completion & Closeout 1. Upon completion of installation, clean all work areas of debris, installation materials, etc. 2. Put the system into automatic operation, and verify proper operation. Verify control loops with an on-site visit one-two weeks after final validation. 3. Provide closeout documentation packages, to include the allowing as a minimum: a. VFD and fan motor operating and maintenance manuals; b. E ngineer control drawings (as-builts); c. Final Sequence of Operation & BACS Points List (current is at Attachment 3) ; d. Validation documentation (see III.C. above). 4. Provide 4 hours of end-user training. Training shall be a minimum of one 4-hour session. Upon training completion and acceptance/turnover document shall be generated, signed and distributed by both parties. F. Warranty - Include a one (1) year parts and labor warranty which will begin upon completion of the project and acceptance by the government. G. Pre-performance Submittals Prior to starting the project the contractor will provide the following submittals for pre-approval by the COTR before installation and programming begins: 1. A detailed description regarding new graphic displays. 2. Variable frequency drive assemblies and mounting locations. 3. Complete description of sequence of operations for cooling towers. Along with drawings indicating VFD and cooling tower fan system layout and panel layout along with any planned wiring details. 4. Project installation schedule. IV SUBMISSION OF PROPOSALS • A. Site Condition Verification and Site Visits 1. Offerors are responsible for verifying all existing conditions, including wire and breaker sizes, code issues, and feasible re-use of existing equipment (including but limited to existing wire and conduit, breakers, disconnects, and motors). Offerors shall include in their proposal all required equipment and labor to meet this scope and deliver a functional system free from defects and in conformance to all applicable local and national building codes. 2. Interested offerors can make a site visit by contacting the RRB facility manager at 312-751-4566 or by email at scott.rush@rrb.gov. C. RRB Supplement to Instructions to Offerors. Offerors may provide, in addition to their response to the Statement of Work listed in section III above, an alternate approach. However the offeror must explain their reasons for recommending the alternative approach in terms of the materials to be provided, system performance, dependability, price, or other factors benefiting the RRB. The Offeror must also submit a separate accompanying price proposal for any submitted alternate (approach) proposal. 1. Offerors shall submit their proposal in two Volumes: a. Technical proposal in four copies consisting of: 1. Contractor project plan. This should include a statement of work detailing required activities, estimated time needs and corresponding staff qualifications, the work steps involved in satisfying the requirement for each assigned task. A project plan/milestone chart listing and schedule of each task should also be included. Contractors shall specify the level of RRB Facility Management or other staff involvement by functionality, which they require in order to accomplish the tasks required by this Statement of Work and as outlined in their proposal. 2. At least three references for similar engagements, involving facility cooling tower fan motors and variable frequency drive installations and integration, performed within the last 18 months. Each reference must contain, at minimum, two knowledgeable contacts, along with their phone numbers. Federal government references are desired, but not required. Offerors shall provide at least one reference for each subcontractor’s work on like engagements. b.Business proposal in two original copies consisting of: 1. Standard Form (SF) 1449 in two originals with blocks 12, 17a and 17b, 30a, b, and c completed. 2. Contractor’s firm-fixed prices in Section II.A 3. Contractor’s business information outlined in Section II B. above. D.Government Provided Resources - The Contractor shall identify with their proposal any resources, which they require the RRB to provide for the Contractor to complete the services required by this solicitation. The RRB currently anticipates providing the following resources in support of this project and procurement: 1. Administrative access to existing building automated control system. 2. Physical access to the facility roof area and the cooling towers The RRB’s Technical Project Manager for this procurement is Mr. Scott Rush, Facility Manager, Office of Administration, 312/751-4566, Scott.rush@rrb.gov. E. Electronic offers are due by 11:00 am local time on Friday, September 25, 2009. Offers may be submitted by email to proposals@rrb.gov sooner than the above date and time. The contractor must deliver the original hard copies of the technical and business volumes at the RRB's Chicago headquarters facility no later than 11:00 a.m. local on September 25, 2006. Questions pertaining to technical aspects of this procurement must be submitted by email to Paul.ahern@rrb.gov or by facsimile to 312-751-4923 in writing and received by this office in sufficient time to allow the timely transmission by the RRB of written answers by a solicitation amendment. To ensure this, the RRB will only answer written questions received in this office no later than 11:00 a.m. local time on September 17, 2009. RRB will not furnish technical information over the phone. VI Evaluation. The Government will make an award from this solicitation based on price, past performance and other factors. NOTE: A copy of the formatted Solicitation (RFQ) and attachments are attached to this posting on FBO to aid in submission of offerors/quotations..
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/RRB/BSS/PD/RRB09Q050/listing.html)
 
Place of Performance
Address: 844 North Rush St., Chicago, Illinois, 60611, United States
Zip Code: 60611
 
Record
SN01955469-W 20090917/090916001646-d6f09a5f0ef3d42a0f4346213e537185 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.