Description
Solicitation Quarterly inspections - Four (4) inspections per system Work should include but not limited to the following: •§ Visual inspection of all devices, verify no changes have been made to the system •§ Inspect all system zones and verify that there are no trouble or alarm conditions •§ Perform a visual inspection of the batteries and verify voltage is between 24 - 28 vdc utilizing voltage meter •§ After completion, update the inspection card to reflect the date of inspection, person performing inspection and company name Annual inspection Work should include but not limited to the following: •§ Inspection of all system components for damage •§ Verification of proper system activation •§ Verification of indications and alarms •§ Activate a sample equal to or greater than 20% of total fire alarm input devices to accommodate a 100% device test within a five (5) year period. This 20% should represent devices in each area of the building. •§ Inspection and cleaning of any smoke detector devices in the system. •§ Verify all water flow switches operate correctly. •§ Verify all tamper switches operate. •§ Verify alarm and trouble indication signals are sent to and received by ANAD Fire Department. •§ Reset system. Verify all lamps operate during reset or lamp test. •§ Test batteries utilizing manufacturers' test procedure. •§ Test ground fault detection circuitry and verify proper operation. •§ Vendor shall update the inspection tag to reflect the date and system condition.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/notices/4afa0b6d0ae9eb494efb0a8577f2ce59)
 
Place of Performance
Address: 3580 Morrisville Road, Anniston, Alabama, 36201, United States
Zip Code: 36201
 
Record
SN02000690-W 20091111/091109234809-4afa0b6d0ae9eb494efb0a8577f2ce59 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.