SOLICITATION NOTICE
56 -- Clear Obstructions from PFS Coolers - Solicitation
- Notice Date
- 12/1/2009
- Notice Type
- Combined Synopsis/Solicitation
- NAICS
- 562998
— All Other Miscellaneous Waste Management Services
- Contracting Office
- Department of the Army, U. S. Army Materiel Command, Anniston Chemical Agent Disposal Facility (ANCDF), 3580 MORRISVILLE ROAD, Anniston, Alabama, 36201, United States
- ZIP Code
- 36201
- Solicitation Number
- ANCDF-RFQ-W10-0213
- Archive Date
- 1/5/2010
- Point of Contact
- Ashley Rollins, Phone: 256-238-0721 x 131
- E-Mail Address
-
ashley.rollins@wancdf.com
(ashley.rollins@wancdf.com)
- Small Business Set-Aside
- N/A
- Description
- Solicitation •I. Work Order # 355985 - The LIC clean liquor loop through PFS-COOL-213A/B is unable to maintain set point with the flow valve open 100%. The clean liquor pressure differential across the cooler tubes is running high which is indicative of a plug in the tubes. •§ Locate and remove obstruction from the discharge 4"-SL-635-AB-ET-SR on PFS-COOL-213A from the end header box to the 4"-V-580. •§ Locate and remove obstruction from the discharge 4"-SL-635-AB-ET-SR on PFS-COOL-213B from the end header box to the 4"-V-582. •§ Locate and remove obstruction from the charge 4"-SL-634-AB-ET-SR on PFS-COOL-213A from the inlet header box to the 4"-V-573. •§ Locate and remove obstruction from the charge 4"-SL-634-AB-ET-SR on PFS-COOL-213B from the inlet header box to the 4"-V-576. •§ Remove valves 4"-V-580, 582, 573 and 576 and insulate as needed for this effort. •§ Re-install valves 4"-V-580, 582, 573 and 576 and insulate as needed for this effort. Use new gaskets and torque to between 48 to 60 ft/lbs dry. Reference attached drawings 03-6-P-635-1 sheet 1, 03-6-P-635-2 sheet 2, 03-6-P-635-3 sheet 3, 03-6-P-635-4 sheet 4, 03-6-P-635-7 sheet 7, 03-6-P-635-8 sheet 8, 03-6-P-634-1 sheet 1, 03-6-P-634-2 sheet 2, 03-6-P-634-3 sheet 3, 03-6-P-634-6 sheet 6, 03-6-P-634-7 sheet 7 and AN-6-D-529. •§ PMT: Verify that the normal flow has been established through MPF PFS-COOL-114A/B. Record the post maintenance testing (PMT) results in the technician's report of the work report. The craft lead will sign the work order verifying that the (PMT) was completed. II. Work Order # 355984 - The MPF clean liquor loop through PFS-COOL-114A/B is unable to maintain set point with the flow valve open 100%. The clean liquor pressure differential across the cooler tubes is running high which is indicative of a plug in the tubes. •§ Locate and remove obstruction from the discharge 4"-SL-615-AB-ET-SR on PFS-COOL-114A from the end header box to the 4"-V-562. •§ Locate and remove obstruction from the discharge 4"-SL-615-AB-ET-SR on PFS-COOL-114B from the end header box to the 4"-V-564. •§ Locate and remove obstruction from the discharge 4"-SL-614-AB-ET-SR on PFS-COOL-114A from the inlet header box to the 4"-V-497. •§ Locate and remove obstruction from the discharge 4"-SL-614-AB-ET-SR on PFS-COOL-114B from the inlet header box to the 4"-V-494. •§ Remove valves 4"-V-494, 497, 562 and 564 and insulate as needed for this effort.. •§ Re-install valves 4"-V-494, 497, 562 and 564 and insulate as needed for this effort. Use new gaskets and torque to between 48 to 60 ft/lbs dry. Reference attached drawings 03-6-P-615-1 sheet 1, 03-6-P-615-2 sheet 2, 03-6-P-615-3 sheet 3, 03-6-P-615-4 sheet 4, 03-6-P-615-7 sheet 7, 03-6-P-615-8 sheet 8, 03-6-P-614-1 sheet 1, 03-6-P-614-2 sheet 2, 03-6-P-614-3 sheet 3, 03-6-P-614-6 sheet 6, 03-6-P-614-7 sheet 7 and AN-6-D-528. •§ PMT: Verify that the normal flow has been established through MPF PFS-COOL-114A/B. Record the post maintenance testing (PMT) results in the technician's report of the work report. The craft lead will sign the work order verifying that the (PMT) was completed.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/notices/8f76bcf7931faf3e9282e520799d5ded)
- Place of Performance
- Address: 358 Morrisville Road, Anniston, Alabama, 36201, United States
- Zip Code: 36201
- Zip Code: 36201
- Record
- SN02013635-W 20091203/091201235308-8f76bcf7931faf3e9282e520799d5ded (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)