FBO DAILY ISSUE OF JUNE 20, 2010 FBO #3130
MODIFICATION

Y -- East Grand Forks Pump Station Modifications, Polk County, Minnesota.

Notice Date
6/18/2010
 
Notice Type
Modification/Amendment
 
NAICS
237110 — Water and Sewer Line and Related Structures Construction
 
Contracting Office
USACE District, St. Paul, Contracting Division CEMVP-CT, 190 East Fifth Street, St. Paul, MN 55101-1638
 
ZIP Code
55101-1638
 
Solicitation Number
W912ES-10-T-0057
 
Response Due
9/1/2010
 
Archive Date
10/31/2010
 
Point of Contact
Patricia M. Simon, Phone: 6512905418
 
E-Mail Address
patricia.m.simon@usace.army.mil
(patricia.m.simon@usace.army.mil)
 
Small Business Set-Aside
HUBZone
 
Description
The following question has been received: We are in question of the electrical scope - page 11 of 165 of the specifications 3.0 Electrical - Contractor shall install new control panels in L8 & K1 for the new pumps in each station. 3.1.1 - provides information about these controllers - 3.1.2 provides wiring information and float information. The questions is - whom is providing the pump controller and the floats - plan sheet 64/1638 indicates the Storm Water Pump Motor Starter is Government furnished (L8) and the same on 64/1969 for K1. The descriptions in the electrical scope provide enough information (other than manufactures) that our normal vendors may assume they would provide pricing -We were involved in almost all of the original projects for East Grand Forks Levee's - and this equipment was provided by the government on those projects. Is it correct to assume that we are to just "install" the government provided equipment and "provide and install" the conduits and wiring to these controllers and electrical panels - and the government also "provides" final testing and systems check out with SIPAR. The scope for the pumps (2.0) indicates "new government furnished equipment" - that statement is not evident in regards to the pump starters. Other than in the plan sheets. Please advise. Government Response: The plan sheets provided for K1 and L8 including drawings 64/1638 and 64/1969 are provided for reference only. These drawings show the as-built condition of the stations at the completion of construction. These drawings do not indicate the requirements for this new contract. The contractor shall provide the control panel, motor starters, wiring, floats, and all conduit required for the new third pump installations at K1 and L8. The requirements for these features are stated in the scope of work. These are not Government furnished items.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/USA/COE/DACA37/W912ES-10-T-0057/listing.html)
 
Record
SN02181909-W 20100620/100618234644-eb7c1f3fa021d1f130e7a4b6adc1e164 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.