SOLICITATION NOTICE
61 -- 48VDC/1200Ah GNB Absolyte Battery Blocks
- Notice Date
- 7/12/2010
- Notice Type
- Combined Synopsis/Solicitation
- NAICS
- 335311
— Power, Distribution, and Specialty Transformer Manufacturing
- Contracting Office
- Department of the Air Force, United States Air Force Europe, 700 CONS, Ramstein AB, UNIT 3115, APO, 09021
- ZIP Code
- 09021
- Solicitation Number
- F3N0430182AC08
- Archive Date
- 8/3/2010
- Point of Contact
- Brian R. Maser, Phone: 011496315366210
- E-Mail Address
-
brian.maser@ramstein.af.mil
(brian.maser@ramstein.af.mil)
- Small Business Set-Aside
- N/A
- Description
- This is a combined synopsis/solicitation to purchase and install the following items: 1) Qty: 1, 2 Strings 48VDC/1200Ah GNB Absolyte Battery Blocks a) Delivery of 16x6V/1200Ah GNB Absolyte battery blocks, Cost of 22 hours x 2 installation engineers, travel costs, hotel accomodation costs, dismounting and transport costs of old batteries to supplier. 2) Qty: 1, 48VDC/1125A Rectifier System Cabinet a) Cabinet Rittal Typ TS, RAL 7035, Front and back doors steel vented w/ handle and locker hinge right(front door) hinge left(back door), Top cablng Entry,Interior cable fixing,vented socket, Magazine with place for up to 18x NPR 48 48V/3000W Rectifier Modules, supervisory module SM65, LCD, 3 LED's for "operation" "alarm" "warning", Key-pad 5 keys, battery and system management, remote motitoring features for NMS and SNMP-management-software, RS 232 Ethernet 10baseT RJ-45 Interfaces, Protocols TCP/IP SNMP S3P http https, 6 potential free programmable relay output alarms contacts, 6 digital inputs for external alarms, memory 10000 events and 10000 values, RTC, Load Distribution: 14x Fuse Switch TP00/1600A electronically supervised with fuses DC100...600A, Battery Distribution: 2x Fuse Switch TPS2/1600A supervised (MCB, aux. contact) with fuses DC1000A, AC Distribution: 18x 1-C20A for rectifier mains, LVD: Low volt Batt. Disconnect 1x 1500A, Terminals for mains signals temperature sensor, common plus rail system, load connection directly at fuse switches, temperature sensor for temperature compensation acc to battery spec., without rectifiers. b) Standards and Safety specs: Safety EN 60950-1, EMC EN300 386, RoHS WEEE CE, Input voltage: 3x 230/400 VAC 3W+N+PE 50/60 Hz Output Voltage: 48 VDC Nominal Output current:1125 ADC max, Dimensions [WxHxD]: 600x2100x600mm Weight: ca. 200 Kg w/o Modules, Env Temperature: -10C - +50C, Protection Class: 1 Protection: IP20 3) Qty: 18, Rectifier 48V 3000W / IES-NPR48 a) 208/220/240 VAC input, allows N-1 redundancy, hot swap, temperature controlled fan cooling, power and status indicators 4) Qty: 1, Power System Installation a) Installation of New power system, System commissioning and Start-up, Voltage-free swap of all critical load and batteried cabling from old to new power system, dismounting transport and disposal of old power system, system operation explanation and hand over to customer, Include 36 hours of 2 installation engineers 16 hours technician travel costs and hotel accomidations. Additional: Warranty: 12 months Delivery Time: 4 weeks after Ordering Payment: Net 30 days
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/USAF/USAFE/ROB/F3N0430182AC08/listing.html)
- Place of Performance
- Address: Building 500 Ramstein AFB, Ramstein AFB, Non-U.S., Germany