SOLICITATION NOTICE
41 -- Replace Compressor #2 on MDB-CHIL-930 - Solicitation
- Notice Date
- 8/11/2010
- Notice Type
- Combined Synopsis/Solicitation
- NAICS
- 238220
— Plumbing, Heating, and Air-Conditioning Contractors
- Contracting Office
- Department of the Army, U. S. Army Materiel Command, Anniston Chemical Agent Disposal Facility (ANCDF), 3580 MORRISVILLE ROAD, Anniston, Alabama, 36201, United States
- ZIP Code
- 36201
- Solicitation Number
- ANCDF-RFQ-W10-2155
- Archive Date
- 8/27/2010
- Point of Contact
- Ashley Rollins, Phone: 256-238-0721 x 131
- E-Mail Address
-
ashley.rollins@wancdf.com
(ashley.rollins@wancdf.com)
- Small Business Set-Aside
- N/A
- Description
- Solicitation •§ Contractor is to replace compressor and crankcase heater on refrigerant system #2 on 03-HVC-CHIL-930-SC with York part #364-49094-215. WA will provide replacement compressor and crankcase heater using WA part #16232. •§ Contractor is to replace motor contactor York part #024-31638-000. Replacement contactor is to be provided by the contractor. •§ Contractor is to replace the three compressor motor fuses using Ferraz Shawmut part 64001j. WA will provide replacement contactors from warehouse stock using WA part #17294. •§ Remove and dispose of the refrigerant and refrigerant oil as required by the EPA. Record the number of pounds of refrigerant removed on the Technicians Report. •§ Contractor to remove the failed compressor and return to manufacturer for core charge. Core charge to be listed as line item deduct on the final invoice. •§ Contractor is to install new refrigerant oil filter and "O" ring York part #026-35601-000 (filter) and York part #028-13849-000 ("O" ring). WA will provide replacement oil filter and o-ring from warehouse stock using WA part #14487 and #14488. •§ Contractor is to install new refrigerant oil York type "L" York part #011-00592-000 per manufacturers' specifications. WA will provide new refrigerant oil from warehouse stock using WA #14486. •§ Contractor is to install a new "Catch-All, core, refrigerant filter driers" York part # 026-18328-000. WA will provide the new drier from warehouse stock using WA part #WA17062. •§ Contractor is to install new refrigerant R-22 of type and quantity required 203 lbs per manufacturers' equipment tag. WA will provide new refrigerant from warehouse stock using WA part #WA19223. •§ Contractor will provide labor and materials to replace the refrigerant oil and oil filter with new and perform an acid test after the completion of a one wee run-in of the new compressor. •§ All work to be completed using good engineering practices for the replacement of a burnt refrigeration compressor. •§ There shall be no deviation from the original scope except as allowed through ANCDF Subcontracts and in conjunction with the Process Coordinator as required depending on the change(s) being recommended. •§ Contractor(s) will participate in the pre-job briefings to ensure that good communication are established with ANCDF Subcontracts, Engineering and Maintenance departments before any work begins. Extreme caution shall be taken to ensure that unplanned outages will not occur. Post Maintenance Testing (PMT) Function test chiller 03-HVC-CHIL-930-SC for like new operation once repairs are complete and chiller is ready for operation.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/notices/89cce0df644acf01338facf5d0d14780)
- Place of Performance
- Address: 3580 Morrisville Road, Anniston, Alabama, 36201, United States
- Zip Code: 36201
- Zip Code: 36201
- Record
- SN02236679-W 20100813/100811235236-89cce0df644acf01338facf5d0d14780 (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |