MODIFICATION

S -- Installation of Fire Alarm System at Santa Rosa Ranch School

Notice Date
9/16/2010
 
Notice Type
Modification/Amendment
 
Contracting Office
BIA - OCFO-Western Division of Acquisition2600 N. Central Avenue, Suite 450 Phoenix AZ 85004
 
ZIP Code
85004
 
Solicitation Number
RMH00100113
 
Response Due
9/16/2010
 
Archive Date
9/16/2011
 
Point of Contact
Paul Robinson Contract Specialist 6023794482 paul.robinson@bia.gov;
 
E-Mail Address
Point of Contact above, or if none listed, contact the IDEAS EC HELP DESK for assistance
(EC_helpdesk@NBC.GOV)
 
Small Business Set-Aside
N/A
 
Description
RESPONSE TO QUESTIONS. QUESTION 1: Part 3-Execution sub section 3.2 Wiring calls for initiation, indicating and return conductors to be "routed separately and independently". Is it the intent of the specification to require that all initiation, notification and returning conductors to be routed in separate conduits? This requirement will add greatly to the cost of this project and is typically not required in this type of structure. RESPONSE: NFPA 72 Edition 2010 does allow for routing in one conduit for addressable fire alarm. RFI is justified. QUESTION 2: Part 3-Execution sub section 3.2 Wiring calls for initiation, indicating and return conductors to be "routed separately and independently". Is it the intent of the specification to require that all initiation, notification and returning conductors to be routed in separate conduits? This requirement will add greatly to the cost of this project and is typically not required in this type of structure. RESPONSE: NFPA 72 National Fire Alarm and Signaling code Handbook 2010 Edition does allow all for returning conductors in one Conduit. QUESTION 3: Section 2.3 Initiating Devices section #2 calls for smoke detectors to be ionization type for both ceiling and duct detectors. Ionization detectors are no longer manufactured due to the radioactive isotope required for operation. Will you as the controlling authority permit the use of Photo Electric type smoke detectors for both ceiling and duct smoke detectors? RESPONSE: NFPA 72 National Fire Alarm and Signaling code Handbook will allow Photo Electirc type smoke detectors for both ceiling and duct smoke detectors. RFI is verified.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/DOI/BIA/RestonVA/RMH00100113/listing.html)
 
Place of Performance
Address: Santa Rosa Ranch School, Tohono O'odham Indian Reservaiton, Sells, Pima County, Arizona 85634
Zip Code: 85634
 
Record
SN02285613-W 20100918/100917000526-538850f17a4b2a1e61211533d8e5770d (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.