Description
RESPONSE TO QUESTION RECEIVED. QUESTION 1: Part 3-Execution section 3.2 "Wiring" #4 calls for minimum conductor size. 12 AWG is required for indicating circuits, 14 AWG is required for initiation circuits. Addressable fire alarm systems typically require 18AWG twisted sheilded wire for initiation circuits. 14AWG wire is typical with non-addressable "zoned" initiation devices. Will you approve the use of 18AWG twisted sheilded pair cable for addressable device initiation circuits? RESPONSE: NFPA 72 does allow the use of 18AWG Twisted Sheilded pair cable for alarm system. RFI is approved.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/DOI/BIA/RestonVA/RMH00100110/listing.html)
 
Place of Performance
Address: Santa Rosa Boarding School,Tohono O'odham Indian Reservation, Sells, Pima County, Arizona 85634
Zip Code: 85634
 
Record
SN02285635-W 20100918/100917000537-cb3c81c08ed2b8ff15a8b62191518c89 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.