MODIFICATION
S -- Installation of a Fire Alarm System at Santa Rosa Boarding School
- Notice Date
- 9/16/2010
- Notice Type
- Modification/Amendment
- Contracting Office
- BIA - OCFO-Western Division of Acquisition2600 N. Central Avenue, Suite 450 Phoenix AZ 85004
- ZIP Code
- 85004
- Solicitation Number
- RMH00100110
- Response Due
- 9/16/2010
- Archive Date
- 9/16/2011
- Point of Contact
- Paul Robinson Contract Specialist 6023794482 paul.robinson@bia.gov;
- E-Mail Address
-
Point of Contact above, or if none listed, contact the IDEAS EC HELP DESK for assistance
(EC_helpdesk@NBC.GOV)
- Small Business Set-Aside
- N/A
- Description
- RESPONSE TO QUESTION RECEIVED. QUESTION 1: Part 3-Execution section 3.2 "Wiring" #4 calls for minimum conductor size. 12 AWG is required for indicating circuits, 14 AWG is required for initiation circuits. Addressable fire alarm systems typically require 18AWG twisted sheilded wire for initiation circuits. 14AWG wire is typical with non-addressable "zoned" initiation devices. Will you approve the use of 18AWG twisted sheilded pair cable for addressable device initiation circuits? RESPONSE: NFPA 72 does allow the use of 18AWG Twisted Sheilded pair cable for alarm system. RFI is approved.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/DOI/BIA/RestonVA/RMH00100110/listing.html)
- Place of Performance
- Address: Santa Rosa Boarding School,Tohono O'odham Indian Reservation, Sells, Pima County, Arizona 85634
- Zip Code: 85634
- Zip Code: 85634
- Record
- SN02285635-W 20100918/100917000537-cb3c81c08ed2b8ff15a8b62191518c89 (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |