DOCUMENT
C -- repair dampers and economizers - Attachment
- Notice Date
- 3/30/2011
- Notice Type
- Attachment
- NAICS
- 541330
— Engineering Services
- Contracting Office
- Department of Veterans Affairs;VISN17 Network Contracting Activity;7400 Merton Minter Blvd. (10N17/90C);San Antonio TX 78229
- ZIP Code
- 78229
- Solicitation Number
- VA25711RP0191
- Response Due
- 5/2/2011
- Archive Date
- 8/9/2011
- Point of Contact
- Donna J. Pratt
- E-Mail Address
-
tonio,
- Small Business Set-Aside
- Service-Disabled Veteran-Owned Small Business
- Description
- This is a performance based scope of work (SOW). The contractor is encouraged to use Value Engineering in developing the necessary evaluation methods, inspection, corrective action and recommended approach to ensure the complete operation and functionality of all AHUs system components and DDC devices for the efficient use of economizers. 2 DESCRIPTION OF SERVICES Refer to Section 3 of this scope of work for the minimum requirements for each line item below. Item Description 001 AHU System Baseline Assessment and Evaluation 002 Engineering Evaluation Report and Design Approach 003 Architect and Engineering (A&E) Services 3 SPECIFIC PROJECT REQUIREMENTS The specific requirements in this section are intended to be used as a guide to note the minimum requirements to be evaluated for the system correction and proper operation. It is the contractor ™s responsibility to conduct a throughout review and evaluation of each AHU system components to meet necessary code inspection requirements and ensure full automatic modulation and operation. The contractor is encouraged to use Value Engineering in developing the necessary evaluation methods, inspection, corrective action and recommended approach to ensure the complete operation and functionality of all AHUs system components and DDC devices for the efficient use of economizers. 3.1 Item 001 - AHU System Baseline Assessment and Evaluation The objective of this item is to identify and verify operation of current AHUs system components and to document and establish all deficiencies to be corrected. Refer to attached AHUs list provided as reference. This item shall include at a minimum: 3.1.1 Outside Air (OA) grills and return air dampers shall be inspected for obstructions and all recommendations for cleaning, repair or replacement shall be noted in the scope line item 002. 3.1.2 The existing AHU field electronic control devices shall be verified that they are receiving a signal from the EMCS system. The components shall be checked to verify the unit is sending an output signal (electric or pneumatic) when commanded. 3.1.2.1 Main control valves, alarms and signals shall be remotely connected to the EMCS system. Existing DDC system is Andover and controls shall be able to directly communicate with this system without the use of any intermediary software interface. 3.1.3 The damper actuator (DDC or pneumatic) shall be checked for air leaks or hunting. The stoke of the device shall be verified for the full range of motion. 3.1.4 Linkages shall be inspected for wear, broken and loose connections. 3.1.5 The dampers shall be inspected for smooth operation and full closure. Conditions of binding or bent louvers shall be noted and recommendations for repairs also noted as part of scope line item 002. 3.1.6 The amount of outside air (CFM) and return air shall be measured and logged to determine the % outside air to ensure the minimum amount is being supplied. 3.1.7 Verify and validate AHU schematic configuration to be provided. Note and correct discrepancies with provided information. 3.1.8 Verify presence of actuators, current condition and identify if they are pneumatically operated, electronically operated, mechanically operated, and/or fixed. 3.1.9 Evaluate modulation capacity of dampers and condition. 3.2 Item 002 - Engineering Evaluation Report and Design Approach The objective of this item is to document the AHUs system components deficiencies found as part of scope line item 001 as well as the methodology used. In addition, this item shall include all recommendations and necessary approach to correct, repair and restore operation of these for energy efficiency devices. This report shall establish a baseline of current system condition and components (to be included, but not limited to AHUs, dampers, DDC, actuators, wiring, signals, etc). The report shall include a comprehensive narrative description of current system operation, report findings and recommendations. It shall also provide the necessary supporting documentation, associated site plan, checklists and pictures. This item shall include at a minimum: 3.2.1 Assessment approach and methodology used to evaluate all AHUs components 3.2.2 Outcome of scope of work paragraphs 3.1.1 thru 3.1.9 with proposed corresponding corrections and recommendations 3.2.2.1 Explain deficiencies found 3.2.2.2 Detail corrections and/or repair/replacement 3.2.2.3 Note and indicate the absence of system components, electrical and pneumatic connections necessary for the operation of economizers in the surveyed units. 3.2.3 Include schematic verification of existing AHUs ™ system configuration and components. 3.2.4 Include schematic verification of proposed AHUs ™ system configuration and components, if merited for some units, for the efficient use of economizers. 3.2.5 Establish clear design approach and any phasing requirements as per VA Medical Center master plan 3.3 Item 003 - Architect and Engineering (A&E) Services 3.3.1 This item shall comply with Section 4, Selected A/E Requirements. This item shall include at a minimum: 3.3.1.1 Detailed SOW and requirements for system correction, repair or replacement 3.3.1.2 Project Specifications 3.3.1.3 Certification requirements 3.3.1.4 Warranty requirements 3.3.1.5 Contract Drawings 3.3.1.6 Phasing requirements 3.3.1.7 Deductive alternates 3.3.1.8 Cost Estimate 3.3.1.9 Deduct Alternates (in both scope and cost estimate) 3.3.2 The final document submission shall bear the seal of the Registered Architect and Professional Engineer responsible for the final report. 3.3.3 Mechanical and electrical tie-ins shall be clearly shown on the construction documents if full damper replacement is recommended. The A/E shall perform careful mechanical, electrical, structural, environmental, etc. analysis to avoid any possible change order during construction. 4 SELECTED A/E REQUIREMENTS 4.1 Selected A/E firm shall visit the site before submitting his final proposal. Visits to the site shall be made by appointment with the Contracting Officer. A/E firm shall have a comprehensive knowledge, experience, facilities, instruments, expertise, equipment and personnel to develop all required documents for this study. 4.2 The A/E is required to perform all necessary inspection, survey and evaluation of the existing project site and related utilities, systems and associated distribution systems to produce a correct, complete and fully coordinated report, including data obtained, results, evaluations, design approach and Cost Estimate. 4.3 Site survey work shall consists of existing drawing verification, comprehensive research, investigation, evaluation and study of the existing systems, equipment, structure and utilities that will be tied to the AHUs and EMCS. 4.3.1 VA may provide an architectural as-built in DWG, FCD or DXF format as per A/E request, but does not warrant the 100% accuracy of the same. The VA 4 may provide any other drawing from their files required by the A/E, but does not warrant the accuracy of the same. All of these, if provided, shall be verified by A&E. 4.4 All construction barriers are to be shown on the plans. 4.5 A/E contract is to develop the recommendations with several deductive alternatives in such manner that the construction project does not exceed $199,920. 4.6 The A/E will certify compliance with all national codes used by the VA, and Federal Requirements and Regulations. VA design standard, VA master specifications, design manuals, and/or other publications should be obtained by the A/E at the following Internet addresses: 4.6.1 http://www.cfm.va.gov/contract/aeDesSubReq.asp (A/E Design Submissions Requirements (PG-18-15) 4.6.2 http://www.cfm.va.gov/TIL/ 4.6.3 http://www.cfm.va.gov/til/criteria.asp#multi 4.6.4 http://www.cfm.va.gov/til/alert.asp 4.7 A/E design work shall be in accordance with the following: 4.7.1 Requirements summarized in this scope of work. 4.7.2 VA-HVAC Design Criteria Handbook, Latest VA Standards, ASHRAE, OSHA, NFPA, NEC, ASME, Federal and Industrial Requirements and Regulation. 4.8 A/E shall keep the Project Manager and Contracting Officer informed at all times of the status and project progress. 4.9 The A/E shall prepare written minutes of each meeting with the Government concerning contractual and design approach matters. Copies of the minutes shall be furnished to the Contracting Officer within two calendar days of meeting. The A/E shall prepare written records of phone conversations addressing mayor design issues, and furnish a copy to the Contracting Officer within five calendar days of contact. 4.10 Detailed specifications and/or notes, regarding the removal or removal or relocation of existing equipment and/or system shall be provided on drawings. Related equipment and or units to remain shall be evaluated by the A/E, such equipment schedules shall be provided on drawings. Also A/E shall note any existing items to re-used, cut, patched or adapted. Demolition drawings and details shall be clearly shown. 4.11 Demolition drawings and details shall be clearly shown. 4.12 All calculations, criteria, design references, assumptions, and design values should be presented. All key design decisions shall be discussed. 4.13 The design analysis should be complete and well organized. To achieve this, A/E shall conduct its own coordinated and internal review before each submission (25%, 75%, 100%, final). 5 4.14 Delivery Schedule/ Period of Performance: ITEM NUMBER DATE OF DELIVERY 0001 Due 60 days after issuance of contract notice to proceed 0002 Due 90 days after issuance of contract notice to proceed 0003 Due 210 days after issuance of contract notice to proceed 4.15 Cost Estimate 4.15.1 The A/E shall develop a program Cost Estimate in accordance with Manual for Preparation of Cost Estimates for Hospital Projects: http://www.cfm.va.gov/til/dManual/dmCost.pdf. It should include the various categories of work involved, the quantities and unit cost. Cost can also use typical market values with adequate supporting documentation. 4.15.2 A well-developed estimate by the A/E is a critical element and shall be thoroughly reviewed. The construction estimate shall be based on the anticipated start date of construction. It should include an inflation allowance, which is appropriate for the geographical area from the time that is prepared to the anticipated time of bidding. It should take into account actual local market conditions to the extent possible for materials, and allow for undefined cost anticipated during work drawings design.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/VA/VASTHCS/VASTHCS/VA25711RP0191/listing.html)
- Document(s)
- Attachment
- File Name: VA257-11-RP-0191 VA257-11-RP-0191.doc (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=187232&FileName=VA257-11-RP-0191-000.doc)
- Link: https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=187232&FileName=VA257-11-RP-0191-000.doc
- Note: If links are broken, refer to Point of Contact above or contact the FBO Help Desk at 877-472-3779.
- File Name: VA257-11-RP-0191 VA257-11-RP-0191.doc (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=187232&FileName=VA257-11-RP-0191-000.doc)
- Place of Performance
- Address: Audie L. Murphy Veterans Memorial Hospital;7400 Merton Minter Blvd;San Antonio, Texas 78229
- Zip Code: 78229
- Zip Code: 78229
- Record
- SN02412660-W 20110401/110330234257-e22f8aaf3949a2a51dd882d3b109debf (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |