The work includes furnishing all labor, transportation, supervision, material, equipment, and performing all operations in connection with installing new 55 ft. and 65 ft., class 2 and 1, power poles in place of the existing power poles #325 and #435. The work shall be performed in Forrestal Village and Camp John Paul Jones, Great Lakes, IL, 60088. The work shall be completed and ready for use not later than 45 days after the date the contract is awarded. Power Pole #325 Replace in place, a 55 foot, class 2, electrical power pole with a new 55 foot, class 2, power pole. Provide three new 34kV, clamp type, porcelain standoff insulators, armor rod and associated hardware. Provide one new guy wire with a 10 ™ fiberglass insulator. Provide a new #2 stranded copper ground wire from the static wire to a new 10 ™ ground rod. Transfer and reuse all remaining hardware and wire as feasible related to a 34.5kV and a 12.47kV circuit to the new pole. The work will be performed on de-energized circuits. Buildings fed on the 12.47kV circuit will need to have a scheduled outage outside of normal working hours long enough to temporarily isolate the 12kV circuit from the construction site. After work is complete at the new pole, another outage will be necessary after hours to reconnect the 12kV circuit. The contractor will be responsible for the work related to isolating and reconnecting the 12kV circuit. No building outages are required for the 34.5kV circuit. Reattach existing fiber optic cabling to the new pole. Provide temporary fencing to secure the construction area from the adjacent daycare facility, Bldg 3110. Remove and dispose of the existing power pole and any remaining unused equipment and hardware. All disturbed pavement, concrete, and landscaping shall be restored to original condition. Power Pole #435 Replace in place, a 65 foot, class 2, electrical power pole with a new 65 foot, class 1, power pole. Provide six sets of new 34kV, porcelain dead end bell insulators and associated hardware. Provide six new guy wires with 10 ™ fiberglass insulators. Provide a new #2 stranded copper ground wire from the static to a new 10 ™ ground rod. Transfer the existing 34.5kV circuit and static wire to the new pole. The work will be performed on de-energized circuits. No building outages are required so the work can be done during normal working hours. Disassemble and reinstall the existing fence surrounding Camp John Paul Jones to gain access to the pole location. Provide temporary fencing to secure the construction area. Remove and dispose of the existing power pole and any remaining unused equipment and hardware. All disturbed pavement, concrete, and landscaping shall be restored to original condition. New Poles Poles shall be wood poles machine trimmed by turning, Southern Yellow Pine conforming to ATIS O5.1 and RUS Bull 345-67. Gain, bore and roof poles before treatment. Should additional gains be required subsequent to treatment, metal gain plates shall be provided. Pressure treat poles with pentachlorophenol. The quality of each pole shall be ensured with "WQC" (wood quality control) brand on each piece, or by an approved inspection agency report.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/DON/NAVFAC/N40083B/N4008311Q3022/listing.html)
 
Document(s)
Attachment
 
File Name: N4008311Q3022_Existing_Utility_Dwgs.pdf (https://www.neco.navy.mil/synopsis_file/N4008311Q3022_Existing_Utility_Dwgs.pdf)
Link: https://www.neco.navy.mil/synopsis_file/N4008311Q3022_Existing_Utility_Dwgs.pdf

 
Note: If links are broken, refer to Point of Contact above or contact the FBO Help Desk at 877-472-3779.
 
Place of Performance
Address: 201 Decatur Avenue Bldg 2016, Great Lakes, IL
Zip Code: 60088
 
Record
SN02432798-W 20110427/110425234708-19571423ed61681c68d60fdf2d65b2dd (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.