Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY - FEDBIZOPPS ISSUE OF OCTOBER 17, 2013 FBO #4345
SOLICITATION NOTICE

J -- Backwash Recovery Pumping Station Emergency VFD Replacement, Washington Aqueduct, Washington, D.C. less than br greater than less than br greater than - Justification and Approval (J&A)

Notice Date
10/15/2013
 
Notice Type
Justification and Approval (J&A)
 
NAICS
811310 — Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
 
Contracting Office
USACE District, Baltimore, 10 South Howard Street, Baltimore, MD 21203
 
ZIP Code
21203
 
Solicitation Number
W912DR-14-P-0001
 
Archive Date
11/14/2013
 
Point of Contact
Brandy Nicole Thomas, 4109624888
 
E-Mail Address
USACE District, Baltimore
(brandy.n.thomas2@usace.army.mil)
 
Small Business Set-Aside
N/A
 
Award Number
W912DR-14-P-0001
 
Award Date
10/10/2013
 
Description
J&A 1.Replace two existing VFDs (Make: ALSTOM, Model No. ALSPA MV 3000) for Backwash Recovery Pump Motors rated at 400 HP, 885 RPM, 460 V, 3 phase, 60 Hz, 460 Amp. with compatible motor Soft Starters. Integrate new Soft Starters with existing Pump Control Panel. Use existing motor cables and provide lugs to terminate the motor cables with new Soft Starters. less than br greater than less than br greater than 2.Procure and install one 400 HP, 885 RPM, 460 V, 3 phase, 60 Hz pump motor. The new Pump Motor shall be similar in performance, enclosure and frame as the existing motors so that the new motor can be swapped with either one without modifications. Nameplate data for existing Pump Motors is provided below: less than br greater than less than br greater than Make : U.S. Electrical Motors (Emerson Electric Company) less than br greater than FR: 5810P; Type: HVF1; Encl.: WP1 less than br greater than Phase: 3; Max. Ambient Temp.: 40 degree C; ID # E09 00054046-100R-01/02 less than br greater than Insulation Class: F; Duty: Cont. less than br greater than HP: 400; RPM : 885; SF: 1.15; Hz : 60 less than br greater than Volts: 460; Nominal Efficiency: 95; Amps: 460; PF: 85.8; Code: G less than br greater than Customer P/N: 063135 less than br greater than
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/USA/COE/DACA31/W912DR-14-P-0001/listing.html)
 
Record
SN03216235-W 20131017/131015233954-89a49cf912eb05a909c6ee77bef407cf (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers