MODIFICATION
61 -- TRANSFORMER REPLACEMENT FOR USCG AIR STATION CLEARWATER
- Notice Date
- 12/16/2013
- Notice Type
- Modification/Amendment
- NAICS
- 335311
— Power, Distribution, and Specialty Transformer Manufacturing
- Contracting Office
- Department of Homeland Security, United States Coast Guard (USCG), USCG Base Support Unit Miami, 909 SE First Avenue, Room 512, Miami, Florida, 33131-3050, United States
- ZIP Code
- 33131-3050
- Solicitation Number
- HSCG28-14-Q-PMW010
- Archive Date
- 1/2/2014
- Point of Contact
- Rea L. Hughes, Phone: 305-415-7083
- E-Mail Address
-
rea.l.hughes@uscg.mil
(rea.l.hughes@uscg.mil)
- Small Business Set-Aside
- Total Small Business
- Description
- Subject Solicitation is amended as stated below. "This is the applicable section of the referenced specs 26 12 19.10 and will answer questions regarding the material type: Corrosion Protection Bases and cabinets of transformers shall be corrosion resistant and shall be fabricated of stainless steel conforming to ASTM A240/A240M, Type 304 or 304L. Base shall include any part of pad-mounted transformer that is within 75 mm (3 inches) of concrete pad. Paint entire transformer assembly Munsell 7GY3.29/1.5 green. Paint coating system shall comply with IEEE C57.12.28 regardless of base, cabinet, and tank material. The Munsell color notation is specified in ASTM D1535." All other information remains the same.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/DHS/USCG/COUSCGISCMi/HSCG28-14-Q-PMW010/listing.html)
- Place of Performance
- Address: U.S. COAST GUARD AIR STATION CLEARWATER, 15100 RESCUE WAY, CLEARWATER, Florida, 33762, United States
- Zip Code: 33762
- Zip Code: 33762
- Record
- SN03252771-W 20131218/131216235337-c312fb057fc433d7182d675ccacd1dfa (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)