DOCUMENT
Z -- Wall Repairs - Attachment
- Notice Date
- 10/22/2014
- Notice Type
- Attachment
- NAICS
- 236220
— Commercial and Institutional Building Construction
- Contracting Office
- Department of Veterans Affairs;Louis A Johnson, VAMC;Contracting Office (90C);1 Med Center DR;Clarksburg WV 26301-4199
- ZIP Code
- 26301-4199
- Solicitation Number
- VA24415R0002
- Response Due
- 10/28/2014
- Archive Date
- 1/26/2015
- Point of Contact
- Rebecca Besten
- Small Business Set-Aside
- Service-Disabled Veteran-Owned Small Business
- Description
- CONTINUATION PAGE 1.The specifications include some pretty encompassing requirements relating to photo documentation. Will a "Multi Vista" type photo record be required for this project? (A) All that is required is a photographic record of completed work that clearly identifies where each image was taken. 2.Spec section 1.27 references relocated equipment as well as the removal of abandoned lines. Please verify that the scope of this project does not entail anything relating to the removal or reinstallation of anything relating to MEP. (A) It is the VA's position that with the proper equipment and materials all the work identified in the construction drawings can be accomplished without the relocation or removal any existing equipment or utility lines. 3.Drawing LS 1.2 Note 3 reads "Mechanical Shaft near Stairway E - Extend approximately 8' of 1 hour rated wall 2' to the deck above and seal penetrations with approved rated material." Where the note is located on the drawings appears to have a 2 hour fire rated wall. Which type of wall is required in this area? (A)This is correct. The wall indicated at LS1.2 Note 3 is a 2 hour rated shaft wall. 4.Drawing LS 1.4 Note 1 reads "Soiled utility room 517 - Extend 24 LF of smoke wall 3 feet to the deck above and seal with approved rated material." The drawing note is located in an area which shows it to be either a 1 hour or 2 hour fire rated wall. Which type of wall is required in this area? (A)This is correct. The wall indicated at LS1.4 Note 1 is the 1 hour rated fire wall. 5.Drawing LS 1.5 Note 1 reads "Remove non-compliant material and install 1 hour spray on fireproofing on approximately 900 sf patio roof enclosure." What sort of non-compliant material is specifically required to be removed? Also, would the VA accept a 1 hour fireproof paint in lieu of spray on fireproofing? (A) Revise LS1.5 Note 1 to delete all work associated with the fire proofing of the patio roof. A revised drawing is included in this amendment.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/VA/ClVAMC540/ClVAMC540/VA24415R0002/listing.html)
- Document(s)
- Attachment
- File Name: VA244-15-R-0002 A00003 VA244-15-R-0002 A00003_1.docx (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1692145&FileName=VA244-15-R-0002-A00003006.docx)
- Link: https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1692145&FileName=VA244-15-R-0002-A00003006.docx
- File Name: VA244-15-R-0002 A00003 SOC PFI REPAIR RATED WALLS DRAWINGS.pdf (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1692146&FileName=VA244-15-R-0002-A00003007.pdf)
- Link: https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1692146&FileName=VA244-15-R-0002-A00003007.pdf
- Note: If links are broken, refer to Point of Contact above or contact the FBO Help Desk at 877-472-3779.
- File Name: VA244-15-R-0002 A00003 VA244-15-R-0002 A00003_1.docx (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1692145&FileName=VA244-15-R-0002-A00003006.docx)
- Place of Performance
- Address: Louis A, Johnson VA Medical Center;1 Medical Center Drive;Clarksburg, WV
- Zip Code: 26301
- Zip Code: 26301
- Record
- SN03555979-W 20141024/141022234335-9db72acc65e5801afb2fffb88983982e (fbodaily.com)