DOCUMENT
J -- COMPREHENSIVE ELECTRICAL SYSTEM TESTING AND MAINTENANCE FOR WHITE RIVER JUNCTION VAMC CAMPUS - Attachment
- Notice Date
- 6/8/2016
- Notice Type
- Attachment
- NAICS
- 541380
— Testing Laboratories
- Contracting Office
- Department of Veterans Affairs;VAMC Manchester;718 Smyth Road;Manchester NH 03104
- ZIP Code
- 03104
- Solicitation Number
- VA24116Q0495
- Response Due
- 7/8/2016
- Archive Date
- 7/9/2016
- Point of Contact
- Stephen Clements, Contract Specialist
- E-Mail Address
-
anchester<br
- Small Business Set-Aside
- Service-Disabled Veteran-Owned Small Business
- Description
- Performance Work Statement Electrical Testing and Maintenance 1.Introduction: A.This Statement of Work (SOW) describes the requirements for the phase one, phase two, and phase three maintenance, inspection, testing, and/or calibration of the White River Junction VA Medical Center Electrical Power Distribution System and all of its components at the White River Junction VA Medical Center. These work items are referenced as "Maintenance and Testing" in this document, hereafter. B.This SOW describes the requirements for the Qualified Electrical Contract Professionals - known as "Contractors" in this document, hereafter. Contractors who are contracted by VA Medical Center to perform maintenance and testing of the Electrical Power Distribution System, and all of its components shall meet all requirements stated in Section 2 of this SOW. C.The White River Junction VAMC consists of approximately 23 significant buildings and 502,000 square feet. We receive service from the local electrical utility (Green Mountain Power) at 12,470 volts. We have a medium voltage underground distribution loop around the campus with radial feed and radial taps supplying mostly pad mounted transformers. Utilization voltage is three phase 480/277 and 208/120. We expect to divide the electrical testing and maintenance work into three phases. In general the work consists of clean, tighten, lubricate, inspect, test and calibrate, and Infra-Red (IR) test. Including low voltage power circuit breakers, primary switches, automatic transfer switches; transformers, panelboards including MCCB's and LVB's, medium voltage circuit breakers, protective relays, pad mounted medium voltage switches, and fault current indicators. Also inspection and IR of 16 medium voltage manholes. Work shall not include oil samples, testing of emergency generators engines and components. D.This SOW describes the requirements to complete phase one, phase two, and phase three of maintenance and testing and preparation of reports. 2.Qualifications of Contractors: A.Contractors shall be experienced Electrical Contractors, having properly trained and licensed permanent staff required to perform the proposed work. Electrical Contracting (i.e. the construction, repair, testing and maintenance of industrial and commercial electrical distribution systems) shall be the primary interest/specialty of the Contractor's business. B.Contractors shall be certified by the International Electrical Testing Association (NETA) or equivalent certifying organization acceptable to the VA as Certified Technicians with each employee having completed the Occupational Safety & Health Administration (OSHA) approved 10-hour construction safety training. C.Contractors shall have technical training and demonstrable track records of working experience in maintenance, inspection, and testing of the Electrical Power Distribution Systems and related components in healthcare, industrial, educational, and commercial facilities for a minimum of five (5) continuous years. Electrical components on which the Contractors have experience shall include, but not be limited to, switchboards & switchgear (low and medium voltage); low voltage controls; emergency and standby generators; automatic transfer switches, wiring, transformers, meters, breakers and other electrical appurtenances. D.Contractors shall have safety trainings - either on-the-job or class-room type - in electrical safety outlined in the OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S - Electrical, and the NFPA 70E - Standard for Electrical Safety in the Workplace. Training certification shall be provided indicating each technician is a Qualified Person as defined by NFPA 70E. Training certifications shall be submitted to the VA Contracting Officer prior to work. If no training certifications are available, the contractor' Employer shall certify that he/she has met this requirement in writing, and submit it to the VA Contracting Officer for review and approval prior to work. E.Contractors shall have ready access to the latest versions of the following references and work shall be completed in accord with the latest version of these documents: 1)NFPA 70, National Electrical Code. 2)NFPA 70B, Recommended Practice for Electrical Equipment Maintenance. 3)NFPA 70E, Standard for Electrical Safety for the Workplace. 4)NFPA 110, Standard for Emergency and Standby Power System. 5)OSHA Standard 29 CFR 1910, Subparts I & S. 6)International Electrical Testing Association, Inc. (NETA) - Maintenance and Testing Specifications. 7)Operating/Maintenance manuals, and specifications of the electrical equipment to be maintained and tested. These documents may be obtained from the VHA Medical Center, or the equipment manufacturers. 8)VHA Directive 1028, Electrical Power Distribution System F.Contractors shall have and provide all necessary tools, equipment, and Personal Protective Equipment (PPE) to perform the work safely, effectively, and timely. Tools, equipment, and PPE shall comply with the requirements of OSHA Standard 29 CFR 1910, Subpart I, and NFPA 70E. Prior to initiating work, Contractor shall provide documentation that all instruments, test equipment, tools and PPE have current calibration. Dated calibration labels shall be visible on all instruments, test equipment, tools and PPE as appropriate. 3. Duration of work The project shall be completed no later than 180 days following the Notice to Proceed. 4.Summary of Work: A.The Contractor shall provide a proposed schedule with their bid proposal. The schedule shall be in the form of a progress chart of suitable scale to indicate the work scheduled for completion by any given date during the work period. The proposed schedule shall be reviewed by the VAMC Facilities Management Service; any requirements for adjusting the schedule (e.g. to minimize disruption to the VAMC) shall be incorporated by the Contractor. Contractor shall understand that the majority of work will be done de-energized in accord with VA regulations. Any "hot" work shall be approved in advance by the VA including written approval by the medical center Director. Such request shall be put forth to the Medical Center Director, as appropriate, to complete the intended scope of work. Work shall be scheduled to minimize the impact on the daily operations of a full service medical center. This means a substantial amount of work shall be scheduled during other than normal working hours, including scheduling during nights and weekends. Costs for all such work shall not result in extra charges to the VAMC. B.Work in Base Year consists of Phase One, Two, and Three (each Phase detailed below) over the course of the Base Year. C.Contractors shall report deficiencies that are deemed critical or catastrophic immediately to the Contracting Officer and the Contracting Officers Representative (COR) and the WRJ Chief of Facilities Management Service for immediate actions. D.Work items, definitions, references and procedures shall comply with the latest edition of the NETA - Maintenance Testing Specifications (MTS) and with the VHA Directive 1028, Electrical Power Distribution System. Below is a list of electrical equipment that shall be maintained and tested, as applicable for the phase of work proposed: 1.Switchgear and Switchboard Assemblies 2.Transformers, Dry Type, Air-Cooled, Low-voltage, Small 3.Transformers, Dry Type, Air-Cooled, Low-voltage, Large 4.Transformers, Liquid-Filled 5.Metal-Enclosed Busways 6.Switches, Air, Low-Voltage 7.Switches, Air, Medium-Voltage, Metal-Enclosed 8.Switches, Oil, Medium-Voltage 9.Switches, Vacuum, Medium-Voltage 10.Switches, SF6, Medium-Voltage 11.Circuit Breakers, Air, Insulated-Case/ Molded-Case 12.Circuit Breakers, Air, Low-Voltage Power 13.Circuit Breakers, Air, Medium-Voltage 14.Circuit Breakers, Oil, Medium and High-Voltage 15.Circuit Breakers, Vacuum, Medium-Voltage 16.Circuit Breakers, SF6 17.Protective Relays, Mechanical, and Solid State 18.Protective Relays, Microprocessor Based 19.Grounding Systems 20.Ground-fault Protection Systems 21.Motor Control, Motor Starters, Low-Voltage 22.Motor Control, Motor Starter, Medium-Voltage 23.Emergency Systems, Engine Generator switchgear 24.Emergency Systems, Automatic Transfer Switches 25.Medium voltage electrical manholes 26.Underground fault indicating devices Proposed Phasing E.Description of work for Phase One Phase One shall consist of testing all medium voltage (12.5kv and 4.16kv) equipment, including all switchgear and all pad mounted transformers to include the secondary terminals. Contractor will be expected to adjust transformer taps, if so requested by the VA representative. Include the 2000 kW standby generator associated switchgear and controls in Bldg 32. Includes testing 4.16kv system serving B 4, 6, 7, T58, T59, T60. Include testing of each of the existing Schweitzer Engineering Laboratories, Inc (SEL) Underground Fault Indicators (approximately 42), located in the switchgear of our 12.5kv system. Includes approximately 13 manholes (assume three will require water removal), 14 transformers, 7 pad mount switches, one double ended substation in Bldg 31, and Shallbetter switchgear Bldg 55. Includes isolation of Bldg 55 by Green Mountain Power Corporation. Includes a complete report on Phase One testing. F. Description of work for Phase Two Phase Two shall consist of the work described above, for equipment in the following buildings: 31, 32, 32A, 32B, 1, 1A, 40, 2, 44, 45. Includes all electrical equipment and EES components (including generator switchgear) associated with the named buildings. Includes a complete report on Phase Two testing. G. Description of work for Phase Three Phase Three shall consist of the remaining campus equipment not covered by phase one or phase two, to include equipment in the following buildings: 28, 65, 66, 67, 8, 8A, 88, T44, T58, T59, T60, T61, T62, T63, T18, 39, 4, 6, 7, 10, 5. Includes all electrical equipment and EES components (including generator switchgear) associated with the named buildings. Includes a complete report on Phase Three testing. H.Information Available. 1.Available upon request: One-line and other informational drawings of the Electrical Power Distribution System. These drawings are not certified as-built drawings. Drawings PSE-3870 through PSE-3882 document the entire electrical system as of 2/2/2004 as documented by Cutler Hammer. Drawings from project 405-11-105 Electrical Deficiencies Phase 2 consist of as built drawings from a comprehensive project completed in 2013. Other project drawings specific to individual buildings are also available upon request. These drawings may be available electronically or in hard copy 2.Available upon request: We have several Electrical Power System studies with information relevant to the scope of this effort, such as coordination study data, short-circuit analysis, arc-flash hazard analysis and available protective device setting information. 3.Available upon request: Previous campus electrical testing and maintenance report completed by Alset Power Grid, dated September 10, 2010. 4.Available upon request: Specification on the SEL Underground Fault Indicators installed. Also e-mail (5/11/15) from SEL regarding test equipment and procedure recommended for testing the indicators. I.Infra-Red Scanning/Thermographic Survey shall be performed on electrical equipment. 1.Use an infra-red scanning camera to detect hot spots in the Electrical Power Distribution System. Objective of this work is to detect any loose, broken, or corroded connections in the system. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet the equipment manufacturers' specifications. 2.Note that since this work item must be done while the Electrical Power Distribution System is energized, appropriate safety precautions must be taken before, during and after scanning the system. Prior written authorization will be required from the Medical Center Director. J.System Function Tests. Provide function tests for all equipment listed in this Scope of Work. K.Other The contract shall include all components of the Essential Electrical System (EES) for the areas covered in the current phase. Work shall include racking in and out of all breakers as well as all switching, grounding and lifting and re-connecting all Medium Voltage switches or connections. The Contractor shall include in their bid proposal all costs associated with the services of the local utility company, if any. The Contractor shall assist the VAMC staff with troubleshooting and correcting malfunctioning electrical equipment discovered during the testing. Contractor shall make any required adjustments and/or re-calibrations to all equipment which has been otherwise maintained, inspected, and tested under this Scope of Work. Contractor shall test ground resistance for the facility grounding system for the areas covered in the current phase. Contractor shall be responsible for pumping out water from manholes as required to complete the maintenance and testing. 4.Summary Report of Work: A.A complete written report of the work performed shall be provided to the VA within 30 days of completion of onsite work. Information shown in the report shall be as following: 1)Company's name, addresses, telephone, & FAX numbers. 2)Name and signature of contractors who perform the maintenance and testing. 3)VA Work Contract Number, name and number of VA Contracting Officer. 4)Date and Time of work. 5)Copies of contractors' valid licenses, professional and training certificates. 6)Descriptions and model number of specialized tools and equipment used, such as torque wrench or infra-red scanning camera. 7)Location, Type, Name, and nameplate information of electrical equipment maintained and tested. 8)Descriptions of work items. 9)Test data. 10)Reference materials such as equipment manufacturer's specifications, coordination study, etc. 11)Remarks on conditions of electrical equipment. List all deficiencies, if any. 12)Summary report with recommended corrective actions, if any. B.Submit one electronic copy of the complete written report to VA Contracting Officer within 30 calendar days of completion. C.Submit two (2) hard copies of the complete written report, and one (1) CD-ROM or DVD of the electronic version of the report in Microsoft Word format to the Chief of Facilities Management Service within 30 calendar days of completion. All reference materials shall be included in the electronic version of the report, either through scanning or other means of electronic text import methods. 5.Requirements A.Prior to the start of any work, contractor shall provide their written work plan for the project phase including: 1)Concept and scheduling work including plan for limiting disruption to the medical center. 2)Description of their approach to complete the project and meet all requirements. B.All the work shall be performed to industry standard, or better, by qualified personnel and in conformance with VA standards and Vermont requirements. C.Personnel shall be fully licensed or certified for the trades being performed where these trades are licensed by Vermont or by the governing association for that trade or specialty. Submit documentation on licenses or certifications on request. D.Safety and Health: a.All project personnel working on site are required to have safety training appropriate to their work. A minimum of the ten hour (10 hour) OSHA class is required for all construction personnel working on site. b.The Contractor is required to have a Competent Person, as defined by OSHA, on site at all times while any work is in progress. c.Contractor and all Subcontractors shall comply with all VA safety and health Policies, including but not limited to: i.Personal Protective Equipment ii.Fire Safety and Hot Work permits iii.Lock Out/Tag Out iv.Confined Space Entry v.Fall Protection vi.Electrical Safety vii.Trenching and excavation safety, OSHA 1926 viii.Hazardous Materials/Workers Right to Know Act ix.Penetration Permits, assuming FRR separation may be in place prior to this work x.Security - including badges, keys, and parking. d.Documentation of compliance, including Daily Reports, will be required. e.Submit training and other advance documentation before start of work and prepare other reports daily for each day that on site work is underway. E.Personal Identity Verification of Contractor Personnel (October 2006) a.The Contractor shall comply with agency personal identity verification (PIV) b.This PIV process typically requires all workers to complete forms in advance of entering the VA Medical Center, to present two official forms of identification, to submit finger prints and background checks, etc depending on the nature of the project and the length of construction. The approval process typically requires four weeks following fingerprinting before access can be approved. F.Waste Disposal/Recycling: a.All metal suitable for recycling shall be placed in the metal trailer by the loading dock of Building 31. b.Hazardous waste resulting from the demolition, if any, shall be delivered to VA Building 46 under the supervision of the GEMS coordinator. c.Other Hazardous waste, if any, shall be correctly disposed of by the Contractor at no additional cost to the VA (provide a copy of the manifest, and other documentation to COTR). d.Other waste including rubbish and C&D - The Contractor, at no cost to the VA, shall properly dispose of (construction and demolition) debris off site. e.Store, label waste and containers and dispose of waste in full compliance with EPA, NFPA and VT AEC requirements. G.An SDS shall be maintained at the work site for all chemicals and hazardous materials brought onto the VA property. Employees using such materials shall use required PPE and shall be familiar with the hazards, disposal, storage and emergency response including spill and fire procedures, etc. Contractor is responsible for compliance with EPA and VT requirements related to use, storage, disposal and emergency response including spill and fire procedures, etc. for all hazardous materials utilized in this project. H.Work is to be done during working hours, including nights and weekends in accord with the approved schedule. Unscheduled variances to the schedule may be allowed with advance written request, subject to availability of VA staff to support operations. I.Contractor is responsible for providing and installing all required system components, fastening, miscellaneous hardware and construction materials, including any building materials required for patching/painting/touch up/restoration. J.Where applicable, in advance of construction, submit shop drawings, catalog cuts, manufacturer's literature, installation instructions, wiring and piping diagrams, control prints, recommended spare parts lists and O&M manuals for new equipment and materials to be incorporated into the work for approval. At the completion of the work and before acceptance, Contractor is to submit copies of the above plus any as-built changes, as applicable, in a three ring binder. K.Cleanup & protection: a.Work sites to be protected during construction to minimize damage to VA property, furnishings, etc. b.Work sites to be regularly cleaned and kept free of waste and hazards c.At completion of work, and prior to acceptance, the interior and exterior of equipment, panels, etc. and the work site shall be thoroughly cleaned of all construction scraps, dirt, dust, etc. L.Restoration - Cleanup & protection: a.Any damage to finished surfaces shall be replaced or repaired to a condition equal, or better than current conditions. 6.Warranty: a.Work is to be guaranteed for 100% of all labor and materials for a period of one (1) year from the date of completion or acceptance, whichever is later. Contractor shall promptly repair or replace any portion of the work or equipment which fails within this time period, except in the case of VA abuse, VA failure to follow minimum operations and maintenance requirements that have been specifically outlined by the contractor and conveyed in the documentation at acceptance, or by acts of God. b.If manufacturer's warranty exceeds one year then contractor shall extend guarantee for the same period for only that equipment or materials. 7.Additional information: A.Summary of Project Terms 1)Clean All the contaminants that are not compatible with electricity must be eliminated. These contaminants include dust, dirt, moisture, water, rust or anything else that could reduce the efficiency of the electrical system. 2)Tighten Loose electrical connections are heat sources that reduce the efficiency of the electric system and ultimately result in the destruction of a portion or portions of the system. An energized alternating-current system is subject to constant vibration, and therefore, connections frequently become loose. 3)Lubricate Direct-Acting, circuit breakers, relay-actuated power circuit breakers and switches contain many pivoting or sliding mechanical parts. These parts require lubrication and exercising so that they do not become inoperable because of nonuse. 4)Inspected The ratings and settings of electrical devices are checked to assure that they are in accordance with good design and load changes. 5)Test & Calibrated The system or protective devices are subjected to abnormal electrical conditions; the operation of the system or devices is compared to the manufacturer's specifications and plant design requirements. B. Summary Description Of Equipment Tested And Inspected A partial list of the equipment to be tested, inspected and serviced is listed below: 1).Low Voltage Power Air Circuit Breakers a.Visual and mechanical inspection. b.Check case for cracks and other defects c.Lubricate and clean the breaker. d.Perform ductor and insulation tests. e.Perform trip time tests on breaker time current devices. f.Exercise and operate the breaker to ensure proper operation. g.Infrared bus connections 2).Primary Switches a.Inspect for physical, electrical and mechanical condition b.Clean switches and check for tightness c.Perform insulation resistance testing d.Lubricate and clean the switch e.Perform contact resistance f.Infrared bus connections 3).Automatic Transfer Switches (ATS) h.Visual and mechanical inspection of connections i.Check case for cracks and other defects j.Lubricate and clean, where accessible k.Inspect and test contacts where accessible l.Perform transfer time tests to Emergency m.Perform transfer time tests to Normal n.Perform engine cool down o.Exercise and operate the ATS to ensure proper operation p.Infrared bus and cable connections 4).Liquid Filled Transformers a.Visual and mechanical inspection/ inspect for leaks. b.Check tightness of accessible electrical connections. c.Draw an oil sample and perform Oil ASTM Tests and Dissolved Gas Analysis. d.Perform Moisture in Oil analysis. e.Perform Power Factor in Oil Analysis. f.Inspect all grounds g.Clean the transformer where accessible. h.Check for proper voltage and measure loads. i.Infrared bus connections where accessible 5).Switchboards/Panelboards a.Inspect for physical, mechanical, and electrical condition c.Clean switchgear and check for tightness where applicable d.Perform insulation resistance testing on primary entrance switchgear e.Ground fault systems tested f.Infrared bus connections where accessible 6). Medium Voltage Circuit Breakers a.Clean and lubricate b.Verify primary and secondary contact wipe c.Check cell fit and element alignment d.Check proper operation of cubicle shutters e.Measure contact resistance f.Perform insulation resistance g.Operate the breaker electrically and mechanically h.Visual and mechanical inspection 7). Protective Relays a.Inspect relays for mechanical or moisture damage b.Perform all settings in accordance with set points c.Check alignment, connections, and tap plugs d.Perform pickup on each operating element e.Perform timing test at 2 points on the time dial curve f.Compare settings to coordination study when available 8.Scope of work for Option Year 1 A.Same as section 4.D above "Description of Work for Phase One". All other general provisions will apply. B.Duration of work The Option Year One, Phase One work shall be completed no later than 120 days following the Notice to Proceed. It is anticipated the Option Year One, Phase One work will be awarded approximately 12 months after the completion of Phase Three above. 9.Scope of work for Option Year 2 A.Same as section 4.E above "Description of Work for Phase Two". All other general provisions will apply. B.Duration of work The Option Year Two, Phase Two work shall be completed no later than 120 days following the Notice to Proceed. It is anticipated the Option Year Two, Phase Two work will be awarded approximately 12 months after the completion of Option Year One, Phase One, above. 10.Scope of work for Option Year 3 A.Same as section 4.F above "Description of Work for Phase Three". All other general provisions will apply. B.Duration of work The Option Year Three, Phase Three work shall be completed no later than 120 days following the Notice to Proceed. It is anticipated the Option Year Three, Phase Three work will be awarded approximately 12 months after the completion of Option Year Two, Phase Two, above. 11.Scope of work for Option Year 4 C.Same as section 4.D above "Description of Work for Phase One". All other general provisions will apply. D.Duration of work The Option Year Four, Phase One work shall be completed no later than 120 days following the Notice to Proceed. It is anticipated the Option Year Four, Phase One work will be awarded approximately 12 months after the completion of Phase Three above. Evaluation Criteria EVALUATION FACTOR A: Proposed Team The Government will evaluate the total team: prime contractor and if applicable, all subcontractors being proposed under the offer submitted. The offeror shall identify the total team proposed to perform work under any contract awarded from this solicitation and provide the information required below. Proposals that do not offer a complete team or which propose subcontractor team contingencies such as "to be determined" or "potential" among others, will be determined technically unacceptable. After award, no changes to the team offered may be made without the written approval of the Contracting Officer in advance of any such change. In its technical proposal, the Offeror shall identify itself as the Prime Contractor and describe its organization. Directly identify the proposed Project Manager, the On-The-Job Superintendent, and the individual(s) assigned as Safety Officer, Quality Assurance/Control Officer. Provide detailed information describing the solicitation project-relevant experience and solicitation project-relevant personal qualifications of each of the above identified personnel. In addition to the above, provide biographical data on each individual to include the name of the individual, company position, years with the company, prior work, educational background, tasks to be assigned to that individual on the solicitation project, percentage of work-week to be committed to the solicitation project, and level of authority assigned to that individual to act on behalf of the Offeror. Note: FAR 52.236-6 requires on-site superintendence at all times during performance of the contract. The Offeror shall identify all subcontractors, if any, to be used in performance of work under any contract awarded from this solicitation. For each subcontractor to be utilized the Offeror shall detail the subcontractor's work experience and qualifications applicable to performing work under any contract awarded from this solicitation. In addition, the Offeror shall identify key subcontractor personnel who will be involved in the project tasks. Provide biographical data on each key individual to include the name of individual, company position, years with the company, prior work, educational background, experience applicable to the solicitation project, and tasks to be assigned to that individual on the solicitation project. EVALUATION FACTOR B: Construction Management The numeric elements listed under each sub-factor are in no particular priority order and responses to each element will be treated as part of the whole. Sub-factor B.1. Organization In this section, the Offeror shall: - demonstrate relevant experience of their organization that demonstrates knowledge of the requirement and the ability to meet and/or exceed the contract specifications and schedules. - identify any other business name or relationship used in the last three to five years to perform similar work. - describe the functions to be performed by the prime contractor's employees to satisfy any self-performance requirements. A summary cost breakout by performance line item, validating the above if applicable, is required. - demonstrate financial stability in terms of resources, assets, and cash flow with regard to the ability to make timely payments to employees, Subcontractors and material suppliers. - describe in detail the types of communication methods that will be used to ensure that there is no lost time contacting and communicating between VA, the Superintendent and the Offeror as well as its ability to be contacted by VA 24/7. - provide examples of recent past experiences in construction where unforeseen conditions/events occurred and provide details of the Offeror's response to the situation. Sub-factor B.2 Quality Control & Risk Assessment In this section the Offeror shall: - provide a written performance plan demonstrating the ability to complete the project and all requirements within the contract terms and conditions. - demonstrate techniques for maintaining quality control for workmanship, material, and workprogress. - describe management procedures that ensure all contractual requirements will be completed on time and all written documents and records (e.g., payrolls, daily logs, submittals, insurance certificates, payments, change orders, supplemental agreements, correspondence, etc.) are easily accessible. - demonstrate techniques for work coordination with subcontractors, if applicable: what is in place to monitor performance of subcontractors and guarantee performance; how contract requirements flow down to the lowest level of Subcontractor. - provide a written risk assessment of this project to include an affirmation of understanding of the site conditions and a general description of plans to deal with varying elements and factors affecting the work (e.g., weather, local obstacles, public access and other conditions, and length of contract performance). The risk assessment shall include summary of contingencies anticipated and plans designed to address them. EVALUATION FACTOR C: Past Experience The Offeror shall demonstrate prior prime contractor experience listing only projects awarded within the last three years similar in size, scope and complexity to the solicitation project. Include the following information for each project listed: - Name, Address, Telephone Number, and Fax Number of a customer point of contact (POC) who would have the most detailed information about the Offeror's performance. - Project location, award date, original completion date, actual completion date, original contract award amount, final contract amount. Include names, addresses and phone numbers of subcontractors used. The Offeror shall demonstrate prior corporate experience listing all projects awarded within the last two years for hospital work. Include the following information for each project listed: - Name, Address, Telephone Number, and Fax Number of a customer point of contact (POC) who would have the most detailed information about the Offeror's performance. - Project location, award date, original completion date, actual completion date, original contract award amount, final contract amount. Include names, addresses and phone numbers of subcontractors used. EVALUATION FACTOR D: Past Performance Past performance is one indicator of an offeror's ability to perform the contract successfully. Each Offeror shall provide the attached Past Performance Evaluation Form to at least three of the principals listed in the above referenced projects and request that the form be completed and returned to the Contracting Officer (scan and email) no later than the date and time established for receipt of proposals. The Government reserves the right to solicit completion of this form to any other source identified as having a relationship with the Offeror. Offerors with no relevant history of past performance will not be evaluated favorably or unfavorably on Past Performance. Offeror's may provide information on problems encountered on contracts identified under the Past Experience evaluation factor, describing corrective actions taken. The Government will consider this information as well as information obtained from any other sources, when evaluating the Offeror's past performance. EVALUATION FACTOR E: Construction Schedule The Offeror shall submit a draft Progress Schedule (see VAAR 852.236-84(a)) detailing its schedule plan showing the schedule and sequencing of all major components required to be accomplished to meet the solicitation performance and performance period requirements. The draft shall be prepared as if award of all items is made thirty days after the closing date for submission of proposals under this solicitation. WEIGHTING The contract will be awarded based on BEST VALUE to the Government. All factors plus Price will be considered with each factor receiving equal weight.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/VA/MaVAMC608/MaVAMC608/VA24116Q0495/listing.html)
- Document(s)
- Attachment
- File Name: VA241-16-Q-0495 VA241-16-Q-0495_1.docx (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=2786164&FileName=VA241-16-Q-0495-000.docx)
- Link: https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=2786164&FileName=VA241-16-Q-0495-000.docx
- Note: If links are broken, refer to Point of Contact above or contact the FBO Help Desk at 877-472-3779.
- File Name: VA241-16-Q-0495 VA241-16-Q-0495_1.docx (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=2786164&FileName=VA241-16-Q-0495-000.docx)
- Place of Performance
- Address: Department of Veterans Affairs;White River Junction VAMC;215 North Main Street;White River Junction, VT 05009-0001
- Zip Code: 05009
- Zip Code: 05009
- Record
- SN04143198-W 20160610/160608234817-27ae0dc488b15b779c1ba1deb23ac882 (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |