Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY - FEDBIZOPPS ISSUE OF FEBRUARY 19, 2017 FBO #5567
AWARD

Z -- Replace Emergency Generator @ USCG Station Barnegat Light

Notice Date
2/17/2017
 
Notice Type
Award Notice
 
NAICS
238210 — Electrical Contractors and Other Wiring Installation Contractors
 
Contracting Office
Department of Homeland Security, United States Coast Guard (USCG), Commanding Officer, USCG Civil Engineering Unit Cleveland, 1240 East 9th Street, Cleveland, Ohio, 44199-2060, United States
 
ZIP Code
44199-2060
 
Solicitation Number
HSCG83-17-C-PCR004
 
Archive Date
3/4/2017
 
Point of Contact
Thomas E. Walllace, Phone: 2169026110
 
E-Mail Address
thomas.e.wallace@uscg.mil
(thomas.e.wallace@uscg.mil)
 
Small Business Set-Aside
N/A
 
Award Number
HSCG83-17-C-PCR004
 
Award Date
2/17/2017
 
Awardee
Summit Construction & Environmental Services, 6290 Old Warwick Road, Richmond, Virginia 23324, United States
 
Award Amount
$245,158.00
 
Description
DEPARTMENT OF HOMELAND SECURITY UNITED STATES COAST GUARD ENGINEERING SERVICES DIVISION SPECIFICATIONS FOR REPLACE EMERGENCY GENERATOR U.S. COAST GUARD STATION BARNEGAT LIGHT BARNEGAT LIGHT, NJ Provide 600A, 240/120V, single phase service entrance rated automatic transfer switch and 150KW, 600A, 240/120V, single phase stand by diesel generator and connect as shown on sheets E-01 & E-02 on new concrete pad. The generator shall come complete with an integral 350 gallon minimum, sub-base, double wall diesel fuel tank. The generator and fuel tank housing shall be suited for outdoor use. Use existing breaker #15 for hot start and existing breaker #7 for battery charger (in existing emergency panel "E") and connect to generator terminal block. Prior to connect new 150 kW generator on line, disconnect and remove existing generator, existing automatic transfer switch and their associated wire and conduit. Remove natural gas line up to the door and cap it as shown on sheets E-02. Dispose of 20 KW generator in its entirety according to all federal, state and local regulations as shown on sheet E-02. Full normal electrical power shall remain available to the station at all times during construction. Provide (1) 150 KW, 240/120V, single phase temporary generator to provide power to the station during times of commercial power interruption. Provide all required temporary cables, connections, etc.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/DHS/USCG/USCGCEUC/Awards/HSCG83-17-C-PCR004.html)
 
Record
SN04407042-W 20170219/170217234414-dbf9199f0891bd0d065a4297f12f49df (fbodaily.com)
 