MODIFICATION
N -- UMESC CAT6A CABLING UPGRADES
- Notice Date
- 5/31/2018
- Notice Type
- Modification/Amendment
- NAICS
- 238210
— Electrical Contractors and Other Wiring Installation Contractors
- Contracting Office
- USGS OAG DENVER ACQUISITION BRANCH PO BOX 25046 204 DENVER FEDERAL CENTER DENVER CO 80225-0046 US
- ZIP Code
- 00000
- Solicitation Number
- 140G0218R0032
- Response Due
- 6/5/2018
- Archive Date
- 6/20/2018
- Point of Contact
- Wilson, Mary
- Small Business Set-Aside
- Total Small Business
- Description
- Amendment 0004 is issued to provide answers to additional questions received. 1) Non-plenum cable shall be allowed in Segment A and Segment B areas. Segment C specifically has a plenum return ventilation system, so this area would require the use of plenum-rated cable. 2) The drawings provided by the Government have a legend that that indicates that a star on the drawing indicates 2 data ports. Of these two ports, is one for data and one for phone or are both ports data ports? Both are data ports 3) If they are both data ports then is there a third port at each location for the phone? Yes, the third port is for phone 4) If there are three ports at each location with two being for data and one being for phone, are all three in the same face plate or is the phone port in a separate face plate? For the most yes, but there are a few locations where there is a separate box for phone. These cases would be in the cubicle areas and the labs in A and B segments. 5) In building A, which room is the data closet? Room A204 6) Are just patch panels needed for the upgrade or are Data racks needed also? Just patch panels racks are provided 7) For the fiber running from building C to building A, I want to confirm that the LC connections are at both ends. Yes, LC on both ends 8) What are the dimensions of Building A, B,and C? Ex (L×W) Vendors had the opportunity to take measurements during the walk through 9) On the Floorplans each star represented 2 ports. Section 2.b.iv states that data ports and voice ports must be differently colored. Does each star represent 1 Data port and 1 voice port? As indicated a star represents 2 data ports the voice port where applicable would be a third port. This Solicitation Notice is to announce the U.S. Department of Interior (DOI), U.S. Geological Survey (USGS) has a requirement for the removal of all CAT5 infrastructure cabling not being retained and replace with CAT6 cabling in Lacrosse, WI and in accordance with the attached solicitation. The solicitation number is 140G0218R0032 and is being issued as a Request for Proposal (RFP). The policies contained in FAR Part 12, in conjunction with the policies and procedures for solicitation, evaluation and award prescribed in FAR Part 13, as appropriate, shall be used for this acquisition. This is a 100% Small Business Set-aside. The associated NAICS code is 238210 - Electrical Contractors and Other Wiring Installation Contractors. A copy of this solicitation may be accessed by clicking on the FedConnect Link below, under "Additional Info." All requirements for preparation, submission, and receipt of quotes contained in this solicitation shall be adhered to. There will be an organized site visit on May 25, 2018 All questions and quotes are to be submitted via email to Beth Wilson at bwilson@usgs.gov.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/DOI/USGS/USGS/140G0218R0032/listing.html)
- Record
- SN04939703-W 20180602/180531231428-301c83959805ebed771cd4e21f2f2918 (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |