Z -- Project 603-16-701 Replace TIPP Units

Notice Date
1/15/2019
 
Notice Type
Modification
 
NAICS
236220 — Commercial and Institutional Building Construction
 
Contracting Office
Department of Veterans Affairs;Network Contracting Office 9;1639 Medical Center Parkway;Suite 400;Murfreesboro TN 37129
 
ZIP Code
37129
 
Solicitation Number
36C24919B0001
 
Response Due
1/30/2019
 
Archive Date
4/30/2019
 
Point of Contact
Contract Specialist
 
Small Business Set-Aside
N/A
 
Description
Answers to the questions that were submitted: Do we need to connect VRF to an Energy Management System? If so, what is the Energy Management System and who maintains the Energy Management System? Yes, per the specs, the VRF and its individual units are to be connected to the energy management system which is Johnson Controls Metasys Controls system.   See specs 23 09 23 (Direct-Digital Control System for HVAC) and 23 81 43 ( Air Source Unitary Heat Pumps).  This work shall include all work, materials, etc. such that all points available from the BacNet cards can be pulled to the Metasys server and then creating graphics to display this data.    Metasys administrator contact info: Jon Bloom, jon.bloom@va.gov. Phone: 502-287-5509. Is there a minimum efficiency requirement for the VRF? Yes, per the specs, the VRF is to have a minimum EER of 11.1 for cooling and 12.1 for heating; a minimum IEER of 16.1 for cooling and 16.6 for heating; and a minimum SCHE of 21.4 for simultaneous cooling and heating.   See page 3 in spec 23 81 43. Will the contractor have access to multiple escorts simultaneously? One escort will be provided and an additional escort on a limited basis for a total of no more than 2 escorts at any time.   Also take note of Specification Section 01 00 00, 1.5 Construction Security Requirements The General Contractors employees working on this project shall hold a National Background Investigation Bureau (NBIB) https://nbib.opm.gov Tier 1 VA badge. This is also known as a NACI investigation. What type of air handler is required for the VRF in each IT closet? Ceiling Cassette, Wall Mount or Floor Mount? Air handler shall be Wall mounted type for all locations. NOTE: THIS NOTICE WAS NOT POSTED TO FEDBIZOPPS ON THE DATE INDICATED IN THE NOTICE ITSELF (15-JAN-2019); HOWEVER, IT DID APPEAR IN THE FEDBIZOPPS FTP FEED ON THIS DATE. PLEASE CONTACT 877-472-3779 or fbo.support@gsa.gov REGARDING THIS ISSUE.
 
Web Link
Link To Document
(https://www.fbo.gov/spg/VA/NaVAMC/VAMCCO80220/36C24919B0001/listing.html)
 
Place of Performance
Zip Code: 40206
 
Record
SN05195466-F 20190117/190115230045 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.