Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
SAMDAILY.US - ISSUE OF DECEMBER 24, 2021 SAM #7328
SOLICITATION NOTICE

N -- UPS System Replacement

Notice Date
12/22/2021 8:35:43 AM
 
Notice Type
Presolicitation
 
NAICS
238290 — Other Building Equipment Contractors
 
Contracting Office
REGION 4: EMERGENCY PREPAREDNESS AN ATLANTA GA 30341 USA
 
ZIP Code
30341
 
Solicitation Number
70FBR422Q00000020
 
Response Due
1/22/2022 8:00:00 AM
 
Point of Contact
Nicole L. Joseph, Phone: 4704169313
 
E-Mail Address
nicole.joseph@fema.dhs.gov
(nicole.joseph@fema.dhs.gov)
 
Description
FOR INFORMATION ONLY; SCOPE TO BE CONFIRMED Replace existing 80KVA 480V UPS system with a new 80KVA UPS System with a capacity of a minimum 15 minutes of backup power. � SCOPE: Replacement of the current failed GE Model SG 80KVA 208Y/120V UPS System with a new 80KVA UPS System Installation of (1) wrap around maintenance bypass panel to include (1) Tie Maintenance bypass breaker (MIS Breaker) Reuse existing UPS battery cabinet and batteries that were installed new on 10/29/2021 if compatible with new UPS system that is being proposed. Batteries must provide a minimum of 15 minutes of battery run time at current load plus 15%. Vendor shall complete all electrical connections between existing electrical distribution panels and the new UPS and Maintenance Bypass cabinet in accordance with all National Electrical Codes. Vendor shall commission all functions of the UPS System upon completion of the installation and provide a full commissioning report of the new UPS and maintenance bypass. �� Removal and disposal of existing UPS to include disposal of UPS batteries and cabinet if not compatible with UPS system that is being proposed for consideration. Provide detailed procedures for switching from �Normal� operation to a �Maintenance Bypass� mode of operation. Provide (1) year warranty to include labor and parts for the first year that shall begin upon the date of acceptance of the completed project.� Provide a line item option for all manufacturer recommended maintenance of the UPS System to include any battery maintenance and testing of the existing batteries. BACKGROUND: Existing UPS System has failed, and the critical frame room is on currently running on Utility power until the UPS can be replaced. The existing system has a new battery cabinet and batteries installed on 10/29/2021 that could possibly be reused to mitigate additional cost if they are compatible with a new UPS system. Current UPS configuration does not currently have a maintenance bypass cabinet to allow for the system to switch to normal utility power for maintenance/repairs.
 
Web Link
SAM.gov Permalink
(https://sam.gov/opp/c44876d2806f4ba09c5ccddb7a1a7f5b/view)
 
Place of Performance
Address: Thomasville, GA 31792, USA
Zip Code: 31792
Country: USA
 
Record
SN06203596-F 20211224/211222230110 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.