SOURCES SOUGHT
C -- 632-23-116 - Arc Flash Study
- Notice Date
- 6/14/2022 9:57:06 AM
- Notice Type
- Sources Sought
- NAICS
- 541330
— Engineering Services
- Contracting Office
- 242-NETWORK CONTRACT OFFICE 02 (36C242) ALBANY NY 12208 USA
- ZIP Code
- 12208
- Solicitation Number
- 36C24222Q0758
- Response Due
- 7/11/2022 10:00:00 AM
- Archive Date
- 08/23/2022
- Point of Contact
- Delfo Saco-mizhquiri, Contract Specialist, Phone: (718) 526-1000 ext 7524
- E-Mail Address
-
Delfo.Saco-mizhquiri@va.gov
(Delfo.Saco-mizhquiri@va.gov)
- Small Business Set-Aside
- SDVOSBC Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
- Awardee
- null
- Description
- THIS ANNOUNCEMENT IS NOT A REQUEST FOR PROPOSAL. THE GOVERNMENT WILL NOT PAY NOR REIMBURSE ANY COSTS ASSOCIATED WITH RESPONDING TO THIS REQUEST. THE GOVERNMENT IS UNDER NO OBLIGATION TO AWARD A CONTRACT AS A RESULT OF THIS ANNOUNCEMENT. The Department of Veterans Affairs is seeking a qualified Architect-Engineering (AE) firm to Conduct Arc Flash Study as described in the statement of work. The project number is 632-23-116 and the location is Northport VA Medical Center, 79 Middleville Road, Northport, NY 11768. This requirement is being procured in accordance with the Brooks Act as implemented in FAR Subpart 36.6. Applicable NAICS code is 541330 and small business size standard of $16.5 Million. This is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) Set Aside. The anticipated award date of the proposed Architectural and Engineering Contract is on or before September 30, 2022. Potential contractors must be registered in SAM (www.sam.gov ) and visible/certified in Vet Biz (https://www.vip.vetbiz.va.gov ) at time of submission of their qualifications in order to be considered for an award. As a prospective offeror or bidder for this Service-Disabled Veteran-Owned Small Business (SDVOSB) set aside, you are verifying your company meets the status requirements of a SDVOSB concern as established by VAAR 852.219-10. NOTE - Offerors are referred to 852.219-11 (d)(1) Services. In the case of a contract for services (except construction), it will not pay more than 50% of the amount paid by the government to it to firms that are not VIP-listed SDVOSBs. In order to assure compliance with this clause, all firms submitting a SF330 for this Sources Sought Notice are required to indicate what percentage of the cost of contract performance will be expended by the concerns employees and in which discipline(s) and percentage of cost of contract performance to be expended (and in what disciplines) by any other subcontracted or otherwise used small or large business entity(s). Any subcontracted or otherwise business entity(s) used must be identified by name, office location and size/type of business (i.e. SDVOSB, VOSB, 8(a), large, etc). SCOPE OF SERVICE REQUIRED GENERAL PROJECT NO. 632-23-116 - Arc Flash Study. The Contractor shall perform electrical system studies for the Department of Veterans Affairs Medical Centers (VAMCs) Northport VA Medical Center, 79 Middleville Road, Northport, NY 11768. All work shall be accomplished in strict compliance with NFPA-70E, 2021 Edition (Standard for Electrical Safety in the Workplace); and IEEE 242-2001, Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. All survey work will be accomplished on energized equipment unless an outage is required due to specific equipment safety conditions. All requests for outages must be submitted in writing to and approved by the Facility Manager/Chief Engineer. Appropriate personal protective equipment (PPE) shall be used where it is necessary to remove covers/open equipment thereby exposing live buses or other energized components. VA staff are not available to assist the Contractor in accessing/opening electrical equipment; therefore, the Contractor must not assume such support will be available and, accordingly, shall hire a local electrician, have proper staffing, PPE, and equipment to perform such tasks without VA assistance. Most VAMC will not provide more than two electricians to escort the survey, so the Contractor shall plan accordingly and not have more than two teams on-site per trip. The Contractor shall conduct an entrance briefing with the Facility Manager/Chief Engineer upon arrival at Northport Medical Center. The Contractor shall use the meeting to introduce him/herself and to discuss the procedures for obtaining the necessary drawings and field information. The Contractor shall have the Chief Engineer/Facility Manager complete or review a survey of compliance with VHA Directive 1028, Electrical Power Distribution System. At the completion of each site survey, the Contractor shall conduct a short briefing with the Medical Center Director or designee to discuss any major problems or life-threatening issues if any are discovered during the survey. All information obtained during site visits, or any conditions discovered during subsequent calculations shall be kept in strict confidence. The electrical system study will include an initial site visit to the Northport VAMC by a team from the Contractor. The contractor s team members will consist of experienced, professional staff having extensive knowledge in the field of electrical power and shall include at least one registered professional electrical engineer. The Contractor will be responsible for obtaining all necessary data for these reports from as-built drawings, field investigations and from available VAMC staff (utilizing the staff s knowledge and familiarity of the facility electrical systems). Information for site electrical utilities will also be gained from as-built drawings and contractor s personal inspection of these utilities. The VA will provide the contractor with the most recent SKM study performed in 2015 as well as recent known changes to the electrical system as shown on recent project drawings. It is the expectation that the contractor should be able to utilize the existing study and the initial site visit to gather all information needed to complete the study without follow-up visits. The electrical system study shall be conducted using SKM Power Tools software. A copy of the software model and data files used to develop the study shall be turned over to the VAMC for the facility s use and modification for future facility work. For the 60%, 90%, and Final submissions, incorporate the peer review comments and the responses to the reports. Baseline Review (BR). Approximately 15 days after submitting the 90% documents but before completing the Final Submission documents, the Contractor will coordinate and conduct a Baseline Review meeting with the respective VAMC COR. This meeting may be held via MS Teams unless the Consulting Engineer determines that an on-site meeting is warranted. At this meeting, the lead Engineer of the Consultant s team shall provide the COR a prioritized overview of the deficiencies found and the potential consequences if such deficiencies are not corrected. In short, the Consulting Engineer should review the findings of the study with the medical center staff and explains inherent risks and respond to any questions regarding the study. At conclusion of the BR, the Consulting Engineer shall document the meeting in minutes indicating the VAMC has received the study and have been apprised by the AE for associated risks. Copies of these minutes shall be included in the Final Submission documents. Qualification: The short-circuit, protective device coordination and arc flash hazard analysis studies shall be conducted under the supervision and approval of a Registered Professional Electrical Engineer skilled in performing and interpreting the power system studies. Engineer shall be registered by the State of New York and shall stamp the final report. The Registered Professional Electrical Engineer shall have a minimum of five (5) years of experience in performing power system studies. Key Personnel: The Technical Lead (TL) shall monitor the technical aspects of the order and report, any deficiencies, or abnormalities to the contracting officer. In no event shall the TL change any of the terms and conditions of the contract. Any changes or modifications to the contracts shall be made only by the contracting officer and/or, Administrator pursuant to a properly executed contract action. VA FURNISHED ITEMS As-Built Drawings: As-built drawings may not be 100% accurate and will need verification by the Contractor. Substantial deviations from actual as-built condition which affects the SOW shall be brought to the attention of the COR. List of buildings to be assessed: The list shall identify each building (by common name and building number), the current function and total gross square footage. Plans and One-line Diagrams: Site plan, incoming electrical service, and primary distribution system one-line diagram and basic one-line diagrams for the buildings at each VAMC. SKM Study and Files from 2015 VAMC personnel knowledgeable of the existing electrical systems that shall accompany the Contractor s team members during the site investigation. The contractor shall coordinate and verify schedule and personnel, with the Chief Engineer, in advance of site visit(s). Chief Engineer shall ensure that medical center personnel are available to accompany the survey team. In the event of an operation emergency, assistance from a VAMC staff will be intermittent. Contractor must have skilled staffing and equipment to perform task without VA assistance. Most recent electrical maintenance and testing reports performed at the VAMC. Facility Ground Resistance Test Reports: VAMC is to provide the A-E the most recent of these ground resistance test report. A small conference workroom with telephone, and access to internet, large format, and small format copiers. DELIVERABLES For 60% and 90% submission, provide hard copies and an electronic PDF only. Copies of each submittal shall be provided to the COR. Drawings (Full-size for site, primary one-line diagram and secondary one-line diagrams) Use the latest version of AutoCAD (compatible with the local VAMCs version). For the Final Study Submittal, the VAMC shall receive live CADD drawing files which can be manipulated and updated. Reports shall be loose leaf, three-hole punched, in an appropriately sized binder to include all data and drawings. Each binder shall include a cover sheet including, but not limited to, the VAMC name, VISN, location (City and State) and date. In addition, an insert including this information shall be inserted into the spine of the binder. Submit, with the bid proposal, a proposed schedule for completion of the study. The content requirements for each submission: 60% submission SHALL include: Letter from local electric utility provider indicating the available fault current at the point of service. Executive Summary. Minutes of the Entrance Briefing with the Chief of Engineering/Facility Management. Analysis and calculations for the Primary Distribution System and partial Secondary Distribution System for each building including switchgear, switchboard, and distribution panel etc. Analysis shall include Short Circuit Study and Protective Device Coordination Curves. The analysis shall be based on the actual device data (including but not limit to fuses, breakers and relays. 90% submission SHALL include: All Content from 60% submittal (except as updated below) Deficiencies report. All comments from 60% submission with annotations and responses. All items identified in Para. 5, Specific Scope, as a separate Tab or Section to include: One- Line Diagram Grounding Analysis Short Circuit Study Hazard-Risk Table Coordination Curves Voltage Drop Calculations Emergency Power Analysis Recommendations Protective Device Settings Cost Estimates FCA Excel spreadsheet Completed analysis and calculations for the entire Primary and Secondary Distribution. Completed one-line diagrams. Each building on the Building List shall be identified on the diagrams. For Final Submission, provide three hard copies and three electronic copies (compact disc) of the electrical system study (including data files). One original document of Final Submission shall be sent to Chief Engineer at VAMC and shall include: A completed Report, including all corrected data from the 60% and 90% submittals and the coordination curves shall be printed in color. Responses to the 60% and 90% submission comments including annotations and response. Electronic copy (CD) of the entire report including all SKM data, AutoCAD, Word, Excel files and PDF. Color photos that show devices listed on the deficiency report. Arc Flash Hazard Warning labels compliant with requirements of latest NFPA 70E edition. NOTE: Arc Flash Hazard Warning labels need only to be provided to the VAMC. Provide final report with stamp and signature by a Licensed Professional Electrical Engineer SPECIFIC SCOPE The Contractor shall prepare a complete Short Circuit and Coordination Study including voltage drop calculations on the entire electrical system/s (both normal and emergency) at each VAMC. It shall begin at the incoming utility electrical service (for the normal system) and at the emergency generators (for the emergency system) and continue through to each branch circuit panelboard, motor control center or motor control panel in each building. The study shall include a system one-line diagram; Short Circuit and ground fault analysis, protective coordination plots, voltage drop calculations and the following for each building: One Line Diagrams: The one-line diagrams shall show the schematic wiring of the electrical distribution system for each building. Include all electrical equipment and wiring protected by the over current devices. Also show on the one-line diagrams the following specific information: Calculated Short Circuit values at each bus. Breaker and fuse ratings. Transformer kVA, voltage ratings and wiring connections. Voltage at each bus. Identification of each bus. Conduit material, feeder sizes and lengths. Generator kW and voltage ratings. Room Number for each electrical equipment including, but not limited to, the panelboard, disconnect, and transformer, etc. Ground Resistance Analysis: A concise qualitative description (not to exceed one (1) page of narrative) describing the overall condition of the facility ground resistance shall be provided. Any violations of NEC or other abnormalities (high ground resistance, damaged conductors or electrodes, harmonics, etc.) warranting further detailed study shall be highlighted. Analysis of the facility ground resistance shall be based upon: Facility Ground Resistance Test reported (provided by VAMC). Visual inspection of visible ground system components (made during site investigation). Include photographs in Appendices. Interviews with VAMC engineering staff; and Other data on ground system made available by the VAMC. Short Circuit Study: Systematically calculate the fault impedance to determine the available Short Circuit and ground fault currents at each bus. Incorporate the motor contribution in determining the momentary and interrupting ratings of the protective devices. Motors less than 25 HP may be grouped together. The study shall be calculated by using SKM software. Pertinent data and the rationale employed in developing the calculations shall be incorporated in the introductory remarks of the study. Use actual conductor impedances if known. If unknown, use typical conductor impedances based on IEEE Standard 141-1993. Transformer design impedances shall be used when test impedances are not available. Provide the following: Calculation methods and assumptions Selected base per unit quantities One-line diagram of the system being evaluated Source impedance data, including electric utility system and motor fault contribution characteristics Tabulations of calculated quantities Results, conclusions, and recommendations Calculate short-circuit momentary and interrupting duties for a three-phase bolted fault at each: Electric utility s supply termination point Incoming switchgear Unit substation primary and secondary terminals Low voltage switchgear Motor control centers Standby generators and automatic transfer switches Branch circuit panelboards Machine control panels Bus Ducts Other significant locations throughout the system For grounded systems, provide a bolted line-to-ground fault current study for areas as defined for the three-phase bolted fault short-circuit study. Protective Device Evaluation: Evaluate equipment and protective devices and compare to Short Circuit Ratings. Adequacy of switchgear, motor control centers, and panelboard bus bars to withstand short-circuit stresses. Notify Owner in writing, of existing, circuit protective devices improperly rated for the calculated available fault current. Present the data determined by the Short Circuit study in a table format, include the following: Transformer kVA and voltage ratings, percent impedance, X/R ratios and wiring connections. Generator kW and voltage ratings. Conduit material, feeder sizes, length, and X/R ratios. Device identification (Manufacturer, Catalog No. and Device Curve No. and ID) Operating voltage. Protective device. Device rating. Calculated Short Circuit current. Hazard-Risk category at each piece of equipment for the worst-case fault condition Arc Flash Hazard Analysis: The arc flash hazard analysis shall be performed according to the IEEE Std. 1584-2018. The IEEE Std 1584-2018 provides a new mathematical model and calculation procedure, which is more comprehensive, accurate, and complex than the IEEE Std 1584-2002. The SKM modeling must consider the equipment configuration, whether the buss/conductor is horizontal or vertical. Also, the equipment s actual dimensions need to be accounted for to increase the calculation accuracy. The flash protection boundary and the Incident Energy shall be calculated at all equipment locations referenced in IV. The Arc-Flash Hazard Analysis shall include all significant locations in 240 volt and 208-volt systems fed from transformers equal to or greater than 125 kVA where work could be performed on energized parts. Safe working distances shall be based upon the calculated arc flash boundary considering Incident Energy of 1.2 cal/cm2. When appropriate, the Short Circuit calculations and the clearing times of the phase overcurrent devices will be retrieved from the Short-Circuit and Coordination Study model. Ground overcurrent relays should not be taken into consideration when determining the clearing time when performing Incident Energy calculations The short-circuit calculations and the corresponding Incident Energy calculations for multiple system scenarios shall be compared and the greatest Incident Energy must be uniquely reported for each equipment location. Calculations must be performed to represent the maximum and minimum contributions of fault current magnitude for all normal and emergency operating conditions. The minimum calculation will assume that the utility contribution is at a minimum and will assume a minimum motor contribution (all motors off). Conversely, the maximum calculation will assume a maximum contribution from the utility and will assume the maximum number of motors to be operating. Calculations shall take into consideration the parallel operation of synchronous generators with the electric utility, where applicable. The Incident Energy calculations must consider the accumulation of energy over time when performing arc flash calculations on buses with multiple sources. Iterative calculations must take into account the changing current contributions, as the sources are interrupted or decremented with time. Fault contribution from motors and generators should be decremented as follows: Fault contribution from induction motors should not be considered beyond 3-5 cycles. Fault contribution from synchronous motors and generators should be decayed to match the actual decrement of each as closely as possible (e.g., contributions from permanent magnet generators will typically decay from 10 per unit to 3 per unit after 10 cycles). Each equipment location with a separately enclosed main device (where there is adequate separation between the line side terminals of the main protective device and the work location), calculations for Incident Energy and flash protection boundary shall include both the line and load side of the main breaker. When performing Incident Energy calculations on the line side of a main breaker (as required per above), the line side and load side contributions must be included in the fault calculation. Mis-coordination should be checked amongst all devices within the branch containing the immediate protective device upstream of the calculation location and the calculation should utilize the fastest device to compute the Incident Energy for the corresponding location. Arc Flash calculations shall be based on actual overcurrent protective device clearing time. Where it is not physically possible to move outside of the flash protection boundary in less than 2 seconds during an arc flash event, a maximum clearing time based on the specific location shall be utilized Arc Flash Labeling: Contractor shall produce and deliver, the Arc Flash Labeling, to the VAMC according to the number of distribution devices that are shown on the one-line diagram in accordance with NFPA 70 (NEC) and NFPA 70E. Labels shall be 4 x 6 (nominal) printed on industrial quality, adhesive backed vinyl. Danger labels shall have pre-printed headers in red; ""Danger"" labels shall be provided for equipment/devices having incident energy greater than or equal to 40 cal/Cm2; Warning labels shall have pre-printed headers in orange. ""Warning"" labels shall be provided for equipment/devices having incident energy less than 40 cal/cm2. Electrical equipment shall be labeled IAW NFPA 70, Articles 110.16 & 100.21(B) and NFPA70E, Article 130.5. The arc flash hazard analysis to determine the Arc Flash Protection Boundary for each label shall be calculated IAW NFPA 70E Article 130.5. Nominal system voltage Arc flash boundary At least one of the following: Available incident energy and the corresponding working distance, or the arc flash PPE category in Table 130.7(C)(15)(A)(b) or Table 130.7(C)(15)(B) for the equipment, but not both. Minimum arc rating of clothing Site-specific level PPE In addition to the requirements of NFPA 70 and 70E, each customized label shall identify the corresponding piece of electrical equipment, by Panelboard or device identifier and Building number. The identification shall be in a manner (nomenclature) understood by VAMC personnel who will be applying the labels to the respective devices. Generic labels do not require equipment and building identifiers. Arc flash labels shall be provided in the following manner and all labels shall be based on recommended overcurrent device settings. For each 600, 480 and applicable 208-volt panelboard, one arc flash label shall be provided. For each motor control center, one arc flash label shall be provided. For each low voltage switchboard, one arc flash label shall be provided. For each Switchgear, one flash label shall be provided. For medium voltage switches one arc flash label shall be provided For each machine control panel, one arc flash label shall be provided. For each bus duct plug, one arc flash label shall be provided. For each compartment of the transformer, one arc flash label shall be provided. Protective Device Coordination Study: Prepare the coordination curves to determine the required settings of protective devices to assure selective coordination. Graphically illustrate (using log paper) that adequate time separation exists between series devices, including the utility company upstream device. Plot the specific Time Current Characteristics (TCC) of each device in the electrical system as follows: Provide TCC curve down to the last branch-circuit panelboard (regardless the protective device is an adjustable or fixed device) in the three-branches of the Essential Electrical System (EES). Provide TCC curve down to the last adjustable device (stop after the first fixed device) in the Normal System but at the minimum two-level curves from each of the building Service Entrance switchgear/switchboard shall be provided. The following specific information shall also be shown on the coordination curves at each level of power distribution system: Device identification (including Manufacturer, Catalog Number, and Device Curve Number and ID) Voltage and current ratio for curves. 3 phase and 1 phase ANSI damage points for each transformer. No damage, melting, and clearing curves for fuses. Cable damage curves. Transformer inrush points. Maximum Short Circuit cutoff point. Excerpts from one-line diagram reflecting the protective devices modeled on each curve. This excerpt may be inserted onto a corner (typically top right-hand) of the curve print out or may be on the proceeding facing page for ease of reference. Provide explanation, analysis, and recommendation to achieve better coordination. The analysis for recommended curve of a particular device shall be put right after the existing curve in the report for comparison. Develop a table to summarize the settings selected for the protective devices. Include all medium voltage devices in the table, as well as all low voltage devices which require modification, showing the following data: Device identification. Relay CT ratios, tap, time dial, and instantaneous pickup. Circuit breaker sensor rating, long time, short time, and instantaneous settings, and time bands. Fuse rating and type. Ground fault pickup and time delay. Voltage Drop Calculations: Provide voltage drop calculations for all three-phase branch and feeder circuits. Show calculated voltages at each bus and voltage drops on each feeder. Calculations shall be based on the maximum values of kVA, kW, kvar, power factor and amperes for each power circuit. For branch circuit level, use 80% of nameplate rating. For incoming service and distribution level, use 50% of the nameplate rating or actual maximum peak demand load collected in the field if it is available Provide tabular information showing the sizes of all cables, transformers, and other circuit data. Provide a system one-line diagram which clearly identifies individual equipment busses, bus numbers, cable and bus connections and other circuit information. Provide a separate section or tables which provide an evaluation of the calculated voltage drops with recommendations for improvements where voltage drops exceed the allowable NEC limits. Provide voltage drop calculations based on the following scenarios: Scenario 1: Steady State condition- both utility feeds up, CHP online and generators offline Scenario 2: Same as scenario 1 except CHP offline Scenario 3: Loss of Pulaski feed with all power flow from Ellwood, CHP and generators offline Scenario 4: Loss of Ellwood line with all power from Pulaski feed, CHP Online, generators offline Scenario 5: Both utility feeds down, CHP offline, Generators online Analysis and Recommendations: For all electrical equipment, determine if adequate code clearances exist. Note cases by site, building and specific equipment that do not include adequate code clearances. Provide information in table format. Determine if ground fault protection exists where required by NFPA 70 Articles 215 and 517. Note all cases where this condition exists. Provide information in table format. For all automatic transfer switches, determine if the correct 3-pole or 4-pole switches are used. Where ground fault protection is used on the normal feed to the switch, determine if the switch is correctly wired. Note all cases where this condition exists. Provide information in table format. Note any use of cable limiters and provide recommendations to avoid any single phasing conditions. Note all cases where this condition exists. Provide information in table format. On the medium voltage switchgear, where undervoltage relays (27) are used, determine whether all 3 phases are monitored or only 2 phases are monitored. For those locations where only 2 phases are monitored, provide a cost estimate for providing adequate protection for all 3 phases. Analyze the short circuit calculations and highlight any equipment that is determined to be underrated. Provide recommendations to protect the underrated equipment effectively. After developing the coordination curves, highlight areas lacking coordination. Present a technical evaluation with a discussion of the logical compromises for best coordination. Protective Device Settings: For all adjustable and fixed protective devices, provide tables to show existing settings and new settings where changes are recommended for proper protection. If adjustments will not provide adequate protection, provide recommendations to update or replace the existing underrated equipment and include cost estimates to accomplish the necessary corrections. Provide table in Excel format to show ONLY the devices that require that their settings need adjustment. SCHEDULE Site survey work shall begin immediately and be coordinated with VAMC after awarding of the contract. All final reports shall be completed, submitted, and approved within 180 calendar days after the Notice to Proceed. The Medical Centers shall be contacted at least three (3) weeks in advance of the site visit to allow ample time for the Medical Center to arrange the staffs and prepare the necessary documents. Draft final reports (90% submission) shall be submitted 45 days before the submission of the complete final report. The draft final report will be reviewed by the government with comments, edits and corrections provided to the contractor within three weeks after receipt of the draft final report. Contractor shall submit a tentative delivery schedule to contracting officer for approval prior to any work. --End of Scope of Work-- LOCATION Northport VA Medical Center, 79 Middleville Road, Northport, NY 11768 TYPE OF CONTRACT CONTEMPLATED The Department of Veterans Affairs is contemplating awarding a firm fixed price contract. ESTIMATED START AND COMPLETION DATES The Department of Veterans Affairs requires design and contract support services. The estimated start and end dates for the design are as follows: 1. NORTHPORT VAMC - PROJECT SCHEDULE NTP 60% Submission 90% Submission 100% Submission Total Notice to Proceed Request and obtain Incoming Fault Current from Local Utility Revised SKM Model Baseline Review Meeting Introduction Meeting Preliminary SKM Model QA/QC Finalize SKM Model Review As-built Documents QA/QC Submit 90% QA/QC Coordinate Site Visit with VAMC Submit 60% VAMC review (15 days) Submit 100% On-site survey VAMC review (15 days) Duration in Calendar Days 45 45 45 45 180 The A/E shall perform the work required within the limits of the schedule. Professional architects, engineers, and related design disciplines familiar with the work shall be provided, as directed by the Contracting Officer, to attend the VA reviews. SELECTION CRITERIA CRITERIA WEIGHT Professional qualifications and disciplines of staff proposed for the satisfactory performance of required services. 20% Specialized experience and technical competence in the type of work required, including, where appropriate, experience in energy conservation, pollution prevention, waste reduction, and the use of recovered materials. 20% Capacity to Accomplish the work in the required time. 20% Past performance on contracts with Government agencies and private industry in terms of cost control, quality of work, and compliance with performance schedules. 20% Proximity of firm or working office providing professional services to the facility. 10% The extent to which potential contractors identify and commit to the use of service-disabled Veteran-owned small businesses, Veteran-owned small businesses, and other types of small businesses as subcontractors. 10% Total 100% SELECTION CRITERIA DESCRIPTIONS The selection criteria descriptions are provided below. PROFESSIONAL QUALIFICATIONS NECESSARY FOR SATISFACTORY PERFORMANCE OF REQUIRED SERVICES. Provide brief resumes of proposed team members who will specifically serve as the Project Managers and Designers of Record. The Designers of Record shall perform and direct the design within their respective discipline and shall sign and seal the drawings. All Designers of Record must...
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/3a141c81d8da41af8237dba291fc0285/view)
- Place of Performance
- Address: Department of Veterans Affairs Northport VA Medical Center 79 Middleville Road, Northport, NY 11768, USA
- Zip Code: 11768
- Country: USA
- Zip Code: 11768
- Record
- SN06358212-F 20220616/220614230118 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |