SOLICITATION NOTICE
Y -- 632-22-137 Glycol Upgrade for Preheat Hot Water System
- Notice Date
- 8/30/2022 5:46:21 AM
- Notice Type
- Solicitation
- NAICS
- 238220
— Plumbing, Heating, and Air-Conditioning Contractors
- Contracting Office
- 242-NETWORK CONTRACT OFFICE 02 (36C242) ALBANY NY 12208 USA
- ZIP Code
- 12208
- Solicitation Number
- 36C24222Q1128
- Response Due
- 9/6/2022 10:00:00 AM
- Archive Date
- 10/06/2022
- Point of Contact
- Delfo R Saco-mizhquiri, Contract Specialist
- E-Mail Address
-
delfo.saco-mizhquiri@va.gov
(delfo.saco-mizhquiri@va.gov)
- Awardee
- null
- Description
- Who is replacing the damaged HW Coils in the AHUs and will this scope be done prior to the Glycol replacement scope? Answer: The HW coils have already been replaced by in-house personnel. As the system failed due to freezing temperatures, a pressure test will be needed to confirm system integrity prior to glycol installation. Please confirm all bidders will be required to do so. Answer: Repairs to damage from the freeze-up have already been made and pressure tested by inhouse personnel. All bidders are responsible for pressure testing their new work per contract specifications and drawings. If the system fails the pressure test, who is responsible for system repairs in order to provide a sealed system. Answer: All bidders are responsible to complete any required repairs to their new work, following pressure testing, per contract specification and drawings.
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/673a8375bb814326b5d5298a46ae3ae4/view)
- Record
- SN06446371-F 20220901/220830230126 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |