Z -- Install Continuous Monitoring for Legionella, 589A7-22-204

Notice Date
4/5/2023 11:50:06 AM
 
Notice Type
Solicitation
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
255-NETWORK CONTRACT OFFICE 15 (36C255) LEAVENWORTH KS 66048 USA
 
ZIP Code
66048
 
Solicitation Number
36C25523R0082
 
Response Due
5/5/2023 12:00:00 PM
 
Archive Date
08/12/2023
 
Point of Contact
Kevin D Knight, Contract Specialist
 
E-Mail Address
KEVIN.KNIGHT2@VA.GOV
(KEVIN.KNIGHT2@VA.GOV)
 
Awardee
null
 
Description
Scope of Work This project will install a continuous water monitoring system for Buildings 1 (Main Hospital), 59 (Substance Abuse Residential Treatment Facility � SARRTF), and 60 (Community Living Center � CLC) in accordance with VHA Directive 1061. The scope will include the following items: 1. The continuous monitoring system will meet the requirements located in VHA Directive 1061, chapter 3 paragraphs j., Appendix A 2.a., 2.b.(3), and 2.c.(2)(a). The system will integrate with and use the existing Building Automated System to display and record data. The system will be able to trend data and alert when values are outside of acceptable limits. The system and the data will be owned by the VA and will not require a subscription or service contract. 2. Incoming water will be monitored at two locations. Continuous monitoring of incoming water will include water pressure, temperature, pH, hardness, suspended or dissolved solids, and biocide levels (monochloramine). a. Building 1: Domestic cold water entering building 1 room 019-1. b. Building 60: Domestic cold water entering building 60 in room 102B-60. i. A new hub drain will be needed to channel the water out since there is no drain nearby. 3. Temperature and biocide residual (monochloramine) will be monitored at approximately 8 locations. a. Building 1: Hot water recirculation in the basement mechanical room and the domestic cold water and hot water loops on fourth floor east and west. b. Building 59: Domestic cold water and hot water in room 139-59. c. Building 60: Domestic cold water, hot water, and hot water recirculation loops in attic. 4. The basis of design for water monitoring will be an Emmerson Rosemount MCL water monitoring station. They will be in accessible locations at the areas indicated on the project drawings. The unit shall be connected to the BAS for monitoring via 4-20 cable. 5. Architectural scope is limited to patch and repair or walls, ceilings, and finishes as required to address the demolition of plumbing items.
 
Web Link
SAM.gov Permalink
(https://sam.gov/opp/ec370e898fcd4f948851074c6f64a8a5/view)
 
Place of Performance
Address: Wichita, KS 67218, USA
Zip Code: 67218
Country: USA
 
Record
SN06640864-F 20230407/230405230105 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.