Z -- Galley Chiller Repair

Notice Date
10/3/2023 12:34:14 PM
 
Notice Type
Award Notice
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
NAVFACENGSYSCOM SOUTHEAST NAS JACKSONVILLE FL 32212-0030 USA
 
ZIP Code
32212-0030
 
Solicitation Number
N69450-23-C-0079
 
Archive Date
10/17/2023
 
Point of Contact
Jason Clayton, Phone: 6016792510, Fax: 6016792147, Lisa Harris, Phone: 6016792179
 
E-Mail Address
jason.e.clayton.civ@us.navy.mil, lisa.a.harris50.civ@us.navy.mil
(jason.e.clayton.civ@us.navy.mil, lisa.a.harris50.civ@us.navy.mil)
 
Small Business Set-Aside
8AN 8(a) Sole Source (FAR 19.8)
 
Award Number
N69450-23-C-0076
 
Award Date
09/26/2023
 
Awardee
AEM SERVICES LLC Fort Valley GA 31030 USA
 
Award Amount
413683.51
 
Description
Work to be performed by the Contractor: Remove and dispose of the existing chiller. Contractor shall reclaim approximately 650 lbs of R-134A refrigerant using government provided cylinders, and turn over to the government.� Provide credit for salvage scrap weight of the old chiller. Provide a new chiller, scroll type with variable volume ratio.� EER rating minimum 15.8-16.5.� EER Full Load 9.7-10.4.� Performance meeting ASHRAE 90.1-2016 Standards.� Minimum 128 tons.� Chiller must have two independent circuits, each with its own compressor.� Chiller must meet the design conditions shown on Sheet M-003, Attachment 2. Refrigerant to be R-454B.� New chiller shall fit on existing slab. Provide factory authorized start-up and test and balance. Provide electrical service from the existing disconnect to the new chiller.� Re-use existing conduit to the extent possible.� Provide new rigid conduit as needed, mounted to the brick wall and concrete slab by uni-strut.� Flex conduit may be used to transition across the gravel yard, routed perpendicular to the brick wall and slab at ground level.� Provide new electrical wire.� Existing wire may be re-used if long enough.� No splicing permitted.� Connect existing ground wire to new chiller. Replace in kind 4-each wafer butterfly valves at the bypass tee on the chill water piping, shown in Figure 10, Attachment 1.� Provide new chill water piping from the bypass tee to the new chiller.� New chill water piping shall be welded connections.� Provide new insulation and jacketing for new work and existing materials damaged by new work. Connect new chiller to existing controls system.� Provide points for Chiller Enable and Chiller Alarm as shown on Sheet M-407, Attachment 2.� Include authorized start-up and testing.� Test shall include emergency shut down switch.
 
Web Link
SAM.gov Permalink
(https://sam.gov/opp/e4396b06daf043e491de4f57ddb0ef92/view)
 
Place of Performance
Address: Meridian, MS 39309, USA
Zip Code: 39309
Country: USA
 
Record
SN06851794-F 20231005/231003230046 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.