AWARD
Z -- Galley Chiller Repair
- Notice Date
- 10/3/2023 12:34:14 PM
- Notice Type
- Award Notice
- NAICS
- 238220
— Plumbing, Heating, and Air-Conditioning Contractors
- Contracting Office
- NAVFACENGSYSCOM SOUTHEAST NAS JACKSONVILLE FL 32212-0030 USA
- ZIP Code
- 32212-0030
- Solicitation Number
- N69450-23-C-0079
- Archive Date
- 10/17/2023
- Point of Contact
- Jason Clayton, Phone: 6016792510, Fax: 6016792147, Lisa Harris, Phone: 6016792179
- E-Mail Address
-
jason.e.clayton.civ@us.navy.mil, lisa.a.harris50.civ@us.navy.mil
(jason.e.clayton.civ@us.navy.mil, lisa.a.harris50.civ@us.navy.mil)
- Small Business Set-Aside
- 8AN 8(a) Sole Source (FAR 19.8)
- Award Number
- N69450-23-C-0076
- Award Date
- 09/26/2023
- Awardee
- AEM SERVICES LLC Fort Valley GA 31030 USA
- Award Amount
- 413683.51
- Description
- Work to be performed by the Contractor: Remove and dispose of the existing chiller. Contractor shall reclaim approximately 650 lbs of R-134A refrigerant using government provided cylinders, and turn over to the government.� Provide credit for salvage scrap weight of the old chiller. Provide a new chiller, scroll type with variable volume ratio.� EER rating minimum 15.8-16.5.� EER Full Load 9.7-10.4.� Performance meeting ASHRAE 90.1-2016 Standards.� Minimum 128 tons.� Chiller must have two independent circuits, each with its own compressor.� Chiller must meet the design conditions shown on Sheet M-003, Attachment 2. Refrigerant to be R-454B.� New chiller shall fit on existing slab. Provide factory authorized start-up and test and balance. Provide electrical service from the existing disconnect to the new chiller.� Re-use existing conduit to the extent possible.� Provide new rigid conduit as needed, mounted to the brick wall and concrete slab by uni-strut.� Flex conduit may be used to transition across the gravel yard, routed perpendicular to the brick wall and slab at ground level.� Provide new electrical wire.� Existing wire may be re-used if long enough.� No splicing permitted.� Connect existing ground wire to new chiller. Replace in kind 4-each wafer butterfly valves at the bypass tee on the chill water piping, shown in Figure 10, Attachment 1.� Provide new chill water piping from the bypass tee to the new chiller.� New chill water piping shall be welded connections.� Provide new insulation and jacketing for new work and existing materials damaged by new work. Connect new chiller to existing controls system.� Provide points for Chiller Enable and Chiller Alarm as shown on Sheet M-407, Attachment 2.� Include authorized start-up and testing.� Test shall include emergency shut down switch.
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/e4396b06daf043e491de4f57ddb0ef92/view)
- Place of Performance
- Address: Meridian, MS 39309, USA
- Zip Code: 39309
- Country: USA
- Zip Code: 39309
- Record
- SN06851794-F 20231005/231003230046 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)