41 -- 20-Ton Industrial Water Chiller
- Notice Date
- 5/30/2024 12:09:57 PM
- Notice Type
- Solicitation
- NAICS
- 333415
— Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
- Contracting Office
- FA9101 AEDC PKP PROCRMNT BR ARNOLD AFB TN 37389-1332 USA
- ZIP Code
- 37389-1332
- Solicitation Number
- FA910124IndustrialWaterChiller
- Response Due
- 6/17/2024 6:00:00 AM
- Archive Date
- 12/31/2024
- Point of Contact
- Brogan Fullmer, Brooke Vandeman
- E-Mail Address
-
brogan.fullmer@us.af.mil, brooke.vandeman@us.af.mil
(brogan.fullmer@us.af.mil, brooke.vandeman@us.af.mil)
- Small Business Set-Aside
- SBA Total Small Business Set-Aside (FAR 19.5)
- Description
- Technical Specifications 20 Ton Industrial Water Chiller 1.�� General & Operational Data/Specifications a.�� Must be rated for continuous usage b.�� Ambient working limits: Minimum requirements are +14 Fahrenheit (?F) or -10 Celsius (�C) through +113 ?F or 45 �C c.�� Cooling capacity (Capacity based on 45 ?F or 7.22 �C water outlet temperature): 10 ?F or -12.22 �C delta at 95 ?F or 35 �C ambient temperature i.��� Twenty (20) tons, minimum capacity ii.�� 239,756 British thermal units (BTUs) per hour (BTUs/hr.), minimum capacity d.�� Must be designed to use water as a medium e.�� Cooling Water flow rate: 50 gallons per minute (GPM) or 189.27 liters (L), minimum flow rate f.��� Head Pressure: Fifty (50) pounds per square inch (PSI) at a flow rate of 46 gallons or 174.12L per minute (GPM) g.�� Refrigerant Type: R-410A h.�� Noise rating: Not-to-exceed 69 decibels (dBs) at thirty-two feet (32�) or 10 meters (m) 2.�� Reservoir/Self-Contained Water Tank: a.�� Fifty-five (55) gallon or 208.19L minimum capacity b.�� Chiller is to only operate using water contained in a reservoir/self-contained tank; an external water supply IS NOT required, except to fill the reservoir/self-contained tank. c.�� Tank is to be stainless steel. 3.�� Interfaces: a.�� Power Supply: i.��� Volts (V): 460V ii.�� Phase: Three (3) phase alternating current (AC) iii.� Hertz (Hz): 60Hz iv.� Full Load Amps (FLA): Maximum of 60 FLA b.�� Fluid Connections i.��� System water supply: male pipe thread (MPT) two inches (2�) or 5.08 centimeters (cm) ii.�� System water return: male pipe thread (MPT) two inches (2�) 5.08cm c.�� Filling reservoir/self-contained tank with drain 4.�� Weight & Dimensions: System must fit within below dimensions (Note, Reservoir/Self-Contained water tank is included in these measurements a.�� Dry Weight in pounds (lbs): Not-to-exceed two-thousand six-hundred sixty pounds (2,660 lbs) or 1206.55 kilograms (kg) b.�� Width: Not-to-exceed forty-five inches (45�) or 114.3cm c.�� Length/Depth: Not-to-exceed one-hundred inches (100�) 254cm d.�� Height: Not-to-exceed ninety inches (90�) 228.6cm 5.�� Portability a.�� Portability must be maintained while meeting all requirements in these specifications b.�� System must be self-contained on a movable skid/frame c.�� Skid/frame is to have lifting hole to allow forklift to move system d.�� Only permitted items to be disconnected for portability are: i.��� Power Source identified in 3.a.iv ii.�� Fluid connections identified in 3.b.i and 3.b.ii e.�� Drain reservoir/self-contained tank of water 6.�� Clearance Spacing. The following states minimum space must be provided between the system and an obstacle-- a.�� Side Clearances: Required clearance for any side of unit is not-to-exceed six and one-half feet (6.5�) or 1.98m b.�� Top Clearance: Required clearance for top of unit is not-to-exceed ten feet (10�) or 3.04m
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/e75a96d942874b21ba9c5572b526007a/view)
- Place of Performance
- Address: Arnold AFB, TN 37389, USA
- Zip Code: 37389
- Country: USA
- Zip Code: 37389
- Record
- SN07080644-F 20240601/240530230053 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |