COMMERCE BUSINESS DAILY ISSUE OF JANUARY 10,1995 PSA#1259US Army Engineer District, CESWF, 819 Taylor St., P.O. Box 17300, Fort
Worth, Texas 76102-0300 61 -- PROVIDE VACUUM CIRCUIT BREAKER, SAM RAYBURN POWER HOUSE JASPER,
TX SOL DACW63-95-R-0025 DUE 032895 POC Denver Heath, Contract
Specialist, or Leslie L. Bearden, Contracting Officer, 817/334-2131.
The Contractor shall provide all engineering, supervision, labor,
equipment, parts and components necessary to accomplish the following
in the Sam Rayburn Power House, Jasper, Texas: 1. Remove and dispose
existing 2 generator and 2 station service breakers (Westinghouse
De-Ion Air Circuit Breakers, 150-DH-500E, rated at 2000 amperes), 2
neutral breakers (Westinghouse 150-DH-250E breakers, rated at 1200
amperes) and spare set of arc chutes (three in number). All arc chutes
contain asbestos. 2. Provide a total number of (5) five and install
(4) four new and unused roll-in exact replacement vacuum circuit
breakers rated for (2000) two thousand continuous amps with dual trip
coils and provide (3) three and install (2) two new and unused single
pole roll-in exact replacement vacuum circuit breakers rated for (1200)
one thousand two hundred continuous amps. No modifications to the
existing metal clad switchgear cabinets or control scheme will be made.
The new breakers shall have a maximum voltage rating of 15 kV, nominal
voltage class of 13.8 kV, BIL rating of 95 kV, maximum symmetrical
interrupting current of 18 kA at max rated kV and a 3-second short-time
current of 23 kA rms. The Contractor will remove existing ''X'' and
''Y'' control panels and provide (8) eight and install (6) six new
''X'' and ''Y'' control panels. The Contractor shall inspect, clean and
resurface or replace as necessary (28) twenty eight 13.8 KV bus to
breaker attachment terminals, (6) vacuum circuit breaker secondary
voltage receptacles, (6) six MOC switches and operating mechanisms, (6)
six TOC switches and operating mechanisms and cabinet shutter
mechanisms. The Contractor shall provide operation and maintenance
manuals and various spare parts. A maximum of (8) eight weeks delivery
time is required. The Government intends to solicit and negotiate with
only one source under the authority of FAR 6.302-1. Contractor is
Westinghouse Electric Corporation, Electric Generation Services
Division, 11881 Fairmont Parkway, LaPorte, Texas 77571. Interested
persons may identify their interest and capability to respond to this
requirement by submitting a capability statement. The capability
statement must provide information and qualifications to provide this
type of equipment. This notice of intent is not a request for
competitive proposals; however, all ''capability statements'' received
within 45 days after date of publication of this synopsis will be
considered by the Government. A determination by the Government not to
compete this proposed contract based upon responses to this notice is
solely within the discretion of the Government. Information received
will normally be considered solely for the purpose of determining
whether to conduct a competitive procurement. See numbered Note 22.
(0006) Loren Data Corp. http://www.ld.com (SYN# 0142 19950109\61-0001.SOL)