COMMERCE BUSINESS DAILY ISSUE OF JANUARY 10,1995 PSA#125981 CONS/LGCS, 200 Fifth Street, Suite 103, Keesler AFB MS 39534-2104
Attn:/Wanda F. Sledge 70 -- UNINTERRUPTABLE POWER SUPPLY SYSTEM SOL F22600-94-R0116 DUE
020195 POC Wanda F. Sledge tel: 601/377-1845/Joy K. Bissonnette,
Contracting Officer, 601/377-3130 81 CONS requires one uninterruptable
power supply system (UPS). The UPS is a power modulator and short term
power source for critical medical laboratory equipment. The minimum
requirements for the UPS is a 60 KW 3-phase uninterruptable power
supply (208Y/120) with internal electronic bypass, main DC breaker, a
42-panel load distribution and a battery pack sufficient to support
laboratory equipment for a minimum of 26 minutes at 45 KW load
cabinets. This is a single UPS unit which is sized to support existing
medical genetics laboratory instrumentation and which has extra
capacity to accommodate future needs. Customer is requesting Best Power
Technologies' Model DP3600L or equal. The solicitation will be issued
on or about 1 Feb 95. FOB destination to Keesler AFB MS. Only written
or faxed (601-377-3298) requests received directly from the requester
are acceptable. (0006) Loren Data Corp. http://www.ld.com (SYN# 0158 19950109\70-0009.SOL)