COMMERCE BUSINESS DAILY ISSUE OF MARCH 3,1995 PSA#1295Regional Contracting Department (Code 201A.PF) Fleet and Industrial
Supply Center, Box 300, Pearl Harbor, HI 96860-5300 41 -- AIR-COOLED LIQUID CHILLER SOL N00604-95-R-0046 DUE 041795 POC
Contact Point: Ms. Paula Fukuda, 808/474-2397, ext. 209, Contract
Specialist, Ms. J. Basile, Contracting Officer Provide one air-cooled
liquid chiller, 70 ton nominal, package. The unit shall be a
microprocessor controlled, air cooled, liquid chiller utilizing
reciprocating compressors and electronic expansion valves. Unit shall
be factory assembled in one cabinet. Unit shall be completely wired,
fully piped complete with controls and refrigerant charge. FRAME: shall
consist of heavy gage galvanized steel members (zinc phosphate) with an
electrostatically applied baked enamel finish. Condenser fans shall be
direct-drive, propeller type, discharging air vertically (upward).
COMPRESSORS: shall be reciprocating, semihermatic type, mounted on
spring vibration isolators, with an isolation efficiency of no less
than 95%. Cooler shall be tube type, with removable heads. Tubes shall
be internally enhanced, seamless copper type rolled into tube sheets,
insulated with 3/4'' PVC foam of maximum K factor 0.28. Cooler design
shall incorporate two (2) independent direct expansion refrigerant
circuits. Condenser shall be all copper fins and tubes. Condenser shall
be coated with vinyl corrosion protection. CONTROLS: Refrigerant
circuit components shall include a hot gas muffler, high side pressure
relief device, liquid line shut-off valves, suction and discharge
shutoff valves, replaceable core filter drier, moisture indicating
sight glass, stepper motor actuated electronic expansion valve, and
complete operating charge of refrigerant (R-22 and compressor oil).
Controls shall include: microprocessor, power and control circuit
terminal blocks, on/off control switch, replaceable solid state relay
panel, eight character diagnostic display/set point panel, thermistors,
and pressure transducers and potentimeters. Safeties shall be equipped
with thermistors and potentiometers and all necessary components, in
conjunction with the control system. These shall provide the unit with
the following protections: loss of refrigerant charge protection, low
water flow detection, low chilled water temperature protection, low
and high superheat protection, low control voltage protection, high
pressure switch and low oil protection for each compressor circuit.
Electrical overload protection shall be accomplished through the use of
two devices (1) definite purpose contactors and (2) calibrated, ambient
compensated, magnetic trip circuit breakers. Circuit breaker shall open
all three phases in the event of an overload in one phase. Diagnostic
display module shall be capable of indicating the safety lock out
condition by displaying a code (a scrolled display is preferred). Unit
shall be rated for 460 volts, three phase 60 HZ. Unit dimensions shall
not exceed 13 feet 8 inches length by 7 feet 7 inches width. Two
standard technical manuals shall be provided upon delivery. Brand name
Carrier 30GN-070-CG or equal, 01 EA. Delivery FOB Pearl Harbor, Hawaii
120 days after date of contract. All responsible sources may submit a
proposal which shall be considered by the agency. Prospective offerors
are requested to provide with their request for the solicitation,
their phone and facsimile numbers. Requests may be made by calling
808/474-2397, extension 207, via FAX 808/471-5750, or by writing the
contracting office above. (0060) Loren Data Corp. http://www.ld.com (SYN# 0317 19950302\41-0001.SOL)