Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF MARCH 8,1995 PSA#1298

Regional Contracting Directorate (Code 201A), Fleet and Industrial Supply Center, Box 300, Pearl Harbor, HI 96860-5300

41 -- FACTORY ASSEMBLED COOLING TOWER SOL N00604-95-R-0060 POC Contact Point: VELMA WONG, 808/474-2397, Ext. 232 Contract Specialist, J. BASILE, Contracting Officer Cooling Tower, Factory Assembled; Basin-constructed with galvanized steel not lighter than No. 12 W.S.S. Gage; Fill shall be PVC not less than 0.0625 inches thick, Fed. Spec. L-P-535, Type 1, Composition A. Design Condition: Tower Flow Rate-900 GPM; Entering H2O-95 D.F; Leaving H2O-85 D.F.; Wet Bulb Temp. 78 D.F.; 15 H.P. Motor, Rated for 460 Volts/3, PH/60 Cycles, Two Speed, 1800/1900 RPM. Tower to be Supplied with: Air Inlet Screens; Flow Control Valves; External Lube Lines; Motor Outside Air Stream (Motor Mounts); Handrails and Ladder; Side Outlet 1A1; Vibration Limit Switch; Basic Cooling Tower Controls, factory wired, factory installed, in a NEMA 3R enclosure mounted on casing near access door, complete with thermostat controller for two-speed motor to maintain chosen cold water temperature. All responsible sources may submit a proposal which shall be considered by the agency. Requests may be made by calling 808/474-2397 Ext 207, via FAX 808/ 471-5750 or by writing the contracting office above. (0065)

Loren Data Corp. http://www.ld.com (SYN# 0276 19950307\41-0001.SOL)


41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page