COMMERCE BUSINESS DAILY ISSUE OF MARCH 8,1995 PSA#1298Regional Contracting Directorate (Code 201A), Fleet and Industrial
Supply Center, Box 300, Pearl Harbor, HI 96860-5300 41 -- FACTORY ASSEMBLED COOLING TOWER SOL N00604-95-R-0060 POC Contact
Point: VELMA WONG, 808/474-2397, Ext. 232 Contract Specialist, J.
BASILE, Contracting Officer Cooling Tower, Factory Assembled;
Basin-constructed with galvanized steel not lighter than No. 12 W.S.S.
Gage; Fill shall be PVC not less than 0.0625 inches thick, Fed. Spec.
L-P-535, Type 1, Composition A. Design Condition: Tower Flow Rate-900
GPM; Entering H2O-95 D.F; Leaving H2O-85 D.F.; Wet Bulb Temp. 78 D.F.;
15 H.P. Motor, Rated for 460 Volts/3, PH/60 Cycles, Two Speed,
1800/1900 RPM. Tower to be Supplied with: Air Inlet Screens; Flow
Control Valves; External Lube Lines; Motor Outside Air Stream (Motor
Mounts); Handrails and Ladder; Side Outlet 1A1; Vibration Limit Switch;
Basic Cooling Tower Controls, factory wired, factory installed, in a
NEMA 3R enclosure mounted on casing near access door, complete with
thermostat controller for two-speed motor to maintain chosen cold water
temperature. All responsible sources may submit a proposal which shall
be considered by the agency. Requests may be made by calling
808/474-2397 Ext 207, via FAX 808/ 471-5750 or by writing the
contracting office above. (0065) Loren Data Corp. http://www.ld.com (SYN# 0276 19950307\41-0001.SOL)