COMMERCE BUSINESS DAILY ISSUE OF APRIL 5,1995 PSA#1318Department of Transportation, Federal Aviation Admin. (FAA), Contracts
and Acquisition Management Branch, AWP-55, P.O., BOX 92007, WWPC., Los
Angeles, CA. 90009-2007 Z -- REMOVAL AND DISPOSAL OF ENGINE GENERATOR AND ASBESTOS CONTAINING
FLOOR TILE FROM E/G ROOM AT PHOENIX, AZ. (ATCT) SOL DTFA08-95-B-03282
POC Michelle H. Turner Provide all necessary labor, equipment and
materials required to perform the work as described in FAA
specifications and drawings. The work includes but is not limited to
the following: (1) Provide a new diesel engine generator set. (2)
Provide an automatic closed transition and bypass-isolation switch. (3)
Provide accessories, including load bank, day tank batteries and
battery charger, exhaust system and dampers, control devices and other
equipment. In addition install a visible blade, heavy duty, 3-pole,
non-fused, 600 VAC, 400A, lockable switch. (4) Construct new concrete
pads for engine generator and remote radiator. (5) Provide proper
branch circuits, as necessary, to provide power for the EGS, battery
charger and other specified accessory equipment. (6) Remove and dispose
the existing EGS, batteries, automatic transfer switch, manual bypass
switch, two 480/277-208V transformers (T1 and T2), concrete slab in E/G
room, conduits, 100KW load bank, remote radiator, and the evaporative
cooler in E/G room. (7) Connect new EGS using existing underground
conduits and new above ground conduits. (8) Ground all conduits,
raceways and all other equipment according to FAA standard
FAA-STD-091b. (9) Provide a 200KW (minimum), 480V, 3-phase temporary
EGS and an automatic transfer switch. Automatic transfer switch shall
be a closed transition transfer switch. EGS shall be provided with
sufficient fuel for continuous 72 hour operation. (10) Obtain all
necessary certifications and permits. (11) Test the EGS upon completion
of the project. (12) Installation of cables between panel SB-1 and the
engine generator room shall require working in an underground tunnel
which can be classified as a confined space. (13) remove asbestos floor
tiles and other asbestos containing material-ACM from engine generator
room. The IFB DTFA08-95-B-03282 will be available approximately 30
days after the date of this publication with a public bid opening 30
calendar days from date of issuance. Estimated price range is between
$100K and $250K. Standard Industrial Classification (SIC) Code is 1542.
Requests for the IFB shall be made in writing to the aforementioned
address or FAX to: (310)297-0056, Attn: Michelle Turner. This notice
BELOW is for informational purposes for Minority, Women-Owned and
Disadvantaged Business Enterprises: The Department of Transportation
(DOT), Office of Small and Disadvantaged Business Utilization (OSDBU),
has programs to assist minority, women-owned and disadvantaged
business enterprises to acquire short-term working capital and bonding
assistance for transportation-related contracts. This is applicable to
any eligible prime or subcontract at any tier. The DOT Bonding
Assistance Program enables firms to apply for bid, payment, and
performance bonds up to 1.0 million per contract. The DOT provides an
80 percent guaranty on the bond amount to a surety against losses.
Loans are also available under the DOT Short Term Lending Programs
(STLP), at prime interest rates to provide accounts receivable
financing. The maximun line of credit is $500,000. For further
information regarding the bonding and lending programs, please call the
DOT Office of Small and Disadvantaged Business Utilization at (800)
532-1169. For information concerning the acquisition, contact the
contracting official listed above. (0093) Loren Data Corp. http://www.ld.com (SYN# 0215 19950404\Z-0001.SOL)
Z - Maintenance, Repair or Alteration of Real Property Index Page
|
|