Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF APRIL 12,1995 PSA#1323

Regional Contracting Department (Code 201B.RH), Fleet and Industrial Supply Center, Pearl Harbor, HI 96860-5300

61 -- DIESEL ENGINE GENERATOR/RECTIFIER SETS SOL N00604-95-R-0082 DUE 070395 POC Contact Point: Richard Harr, 808/474-2397, Ext. 210, Contract Specialist, Robert S. Kay, Contracting Officer Diesel Engine Generator/Rectifier Sets. Generator/Rectifier output must be capable of providing 325 KW Direct Current, and 15 KW auxiliary (hotel) 120-volt single phase A/C. System shall be capable of producing it's specified DC and AC auxiliary output continuously and simultaneously and each (AC/DC) shall be capable of sustaining intermittent overloads of 19% for 120 minutes, and 50% for one (1) minute. The generators shall be self exciting, brushless and shall conform to NEMA MG-1. Maximum voltage rating for the main generator shall be 480 VAC. Estimated quantity required is four (4), 2 sets in FY96 and 2 sets in FY97. Inspection, testing, and acceptance shall be performed at the contractor's facility, and witnessed by Government representative(s). Government will install the generators on the shipyard cranes. Delivery to be f.o.b. destination (Pearl Harbor Naval Shipyard, Hawaii) within 120 days after order or modification. All responsible sources may submit a proposal which shall be considered by the agency. Requests may be made by phoning 808/474-2397, ext. 207, via FAX 808/471-5750, or by writing the contracting office above. Requestor to provide name, address, telephone, and FAX number. (0100)

Loren Data Corp. http://www.ld.com (SYN# 0424 19950411\61-0005.SOL)