COMMERCE BUSINESS DAILY ISSUE OF AUGUST 9,1995 PSA#1406Arnold Engineering Development Center, ATTN: AEDC PKP, 100 Kindel
Drive, Suite A332, Arnold AFB, TN 37389-1332 48 -- GLOVE VALVES SOL F40650-95-Q-0006 DUE 090695 POC Sue Tate,
Contract Specialist, (615)454-7801, Tony Clayborne, Contracting
Officer. This procurement is for globe body temperature control valves.
Valves must meet the following specifications. End Connection: 1''-150#
RJ ANSI FLG; Material: 300 Series Stainless Steel; Trim, Seat, Guides,
and Gaskets Replacable with material suitable for service conditions.
NO ASBESTOS ALLOWED.; Leakage: Bubble Tight; Cv MIN at Full Open: 11;
Service Conditions: 1. Medium - Liquid Air 2. Design Pressure - 275
PSIG 3. Design Temp - -325 Degrees F; Actuator and Positioner: Provide
the valve complete with a pneumatic spring cyclinder actuator. The
actuator shall perform to rated specifications with an air supply
pressure in the range of 60 to 80 PSIG. The valve will perform with a
proportional air supply of 3 to 15 PSIG from full close to full open.
The valve and actuator shall come factory assembled in an ''air to
open'' or ''fail closed'' mode. This failure mode shall be field
reversible. The response of the valve shall exhibit the characteristics
of a first order linear system to a 10-90% (of full scale) step input.
Under the step input, the valve shall have a rise time of not more
than 1.5 seconds. The valve shall be furnished with a position PAC
including limit switches (open and closed, Form C, 5 AMP, 120 VAC
contacts) and a 1K OHM potentiometer (factory mounted) which will
indicate 75% minimum resistance when valve is full open. The open and
closed Form C limit switches and the position potentiometer (CW, W, CCW
wires) shall be factory wired to a terminal strip mounted in the
electrical housing which has a 1/2'' conduit entry. The valve actuator
shall cause the valve to have linear flow versus command
characteristics. Travel stops are to be provided to prevent overtravel
in the full open and full closed positions. The valve shall have a 0.5
second emergency closing time. All electrical shall meet NFPA Class I,
Division II, Group C/D hazardous area requirements. Globe Body
Temperature Control Valve with same specifications as above except End
Connection: 1 1/2'' - 150# RJ ANSI FLG and Cv MIN at Full Open: 3.2
Globe Body Temperature Control Valve with same specifications as above
except Cv MIN at Full Open: 6.4 Descriptive Literature must be
included on all Valves. Delivery shall be to Arnold AFB TN within 30
days after contract award. Any responsible source may submit a bid that
shall be considered. Firms responding to this synopsis should so in
writing and indicate whether they are a small or small minority
business. FAX request will be accepted (615)454-7330. (0219) Loren Data Corp. http://www.ld.com (SYN# 0295 19950808\48-0001.SOL)