COMMERCE BUSINESS DAILY ISSUE OF AUGUST 24,1995 PSA#1417AFFTC/PKAD Directorate of Contracting, 5 S. Wolfe Ave., Edwards AFB, CA
93524-1185 44 -- LOW PRESSURE STEAM BOILER SOL F04700-95TD056 POC Patsy Casares,
Contract Negotiator, (805) 277-3900 x2211 John Lemacks, Contracting
Officer, (805) 277-3900 x2253. The Government intends to procure the
following requirements: One (1) each 100 BHP Low Pressure (15 PSI Max.)
Steam Boiler, to be equipped with a Natural Gas Low NOx Modulating
Firing Rate Burner capable of meeting Kern County Air Pollution Control
Disrict (KCAPCD) Rule 425.2 for over 5 million BTU's boilers as
described in the following specifications: 115 VAC control circuit,
with boiler controller; low water cut-off, manual reset; combination
low water cut-off, pump control, water column, sight-glass and three
(3) try-cocks; pressure actuated safety valves; two (2) pressure
controllers, one to be manual reset; overall boiler length including
burner and any associated equipment not to exceed 13.5 feet; boiler
width (including gas train, and boiler safety controls) not to exceed
7.5 feet; boiler height (to include any requested safeties) not to
exceed 8 feet; boiler/burner will have a flue gas recirculation (FGR)
system; gas train must meet or exceed California/Kern County
requirements; all associated blower motors must be 460 VAC, 3 phase;
burner is required to modulate automatically throughout low fire (25%)
to high fire (100%) of rated input; burner will operate with a maximum
of 15% excess air throughout firing range; burner will emit no more
than 30 PPM of Nitrogen Oxides (NOx), on a volume basis, throughout the
firing range; burner will emit no more than 30 PPM of Carbon Monoxide
(C0) throughout the firing range; burner will be fully factory
firetested, including FGR systems prior to shipment. Services for the
steam boiler, to inlcude: adjust burner to meet KCAPCD Rule 525.2 to
take place on site 30 days after boiler delivery to the site and
provide combustion analysis data to show that the burner meets
requirements. This requirement is 100% set-aside for small business.
SIC Code is 3443. Size Standard is 500 employees. FOB is destination.
Delivery is 14 days after award. The procedure to be used in awarding
this contract is oral/written quotation; FAX quotations will also be