COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 28,1995 PSA#1441Alliant Techsystems Incorporated, Allegany Ballistics Laboratory, P.O.
Box 210, State Route 956, Rocket Center, WV 26726 59 -- 7500 KVA TRANSFORMER Sol PHC-182, Due 103195, contact point,
Patrick H. Cunningham, 304/726-5047. 7500 KVA Transformer that must
meet the requirements of ANSI C57.12.00, C57,12.80 and C57.12.90.
Minimum tested impedance shall be not less than 5.0 percent.
Transformer shall have four 2-1/2% rated KVA taps, two above and two
below rated primary voltage. Transformer shall be suited for pad
mounting, painted with a manufacturer's industrial paint to withstand
outside elements. Estimated range is between $25,000 and $100,000.
Written or faxed (304) 726-4730 requests only. (265) Loren Data Corp. http://www.ld.com (SYN# 0209 19950927\59-0010.SOL)