COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 1,1995 PSA#1481Regional Contracting Department (Code 201B.DA), Fleet and Industrial
Supply Center, Box 300, Pearl Harbor, HI 96860-5300 61 -- 500 KVA TRANSOFRMER SOL N00604-96-Q-A003 DUE 120795 POC Contact
Point: Debby Alberto, 808/474-2397, extension 202, Contract
Specialist, Robert S. Kay, Contracting Officer Seeking qualified
''small business manufacturers'' or ''small business dealers'', who can
provide the product of a ''small business manufacturer'', for 500 KVA
substation transformer, insulated type, primary 4160V, secondary;
208y/120VAC, 3-phase, 4-wire, (4) externally operated 2-1/2% full
capacity taps, (2) above and (2) below rated voltage, 11.5% impedance.
Stainless steel diagram name plate and NEMA standard maintenance
devices. The insulating liquid shall be mineral oil conforming to ASTM
D 3487, type II, and shall be tested in accordance with ASTM D 117.
Transformer shall be identified as non-pcb on name plate. New
transformer shall fit into existing available space and conform to
current electrical connection requirements. Existing transformer is
General Electric secondary substation transformer model numbers
F-957510A and F-957510B. Quantity: 2 each. FOB Pearl Harbor, Hawaii.
Delivery: On or about February 22, 1996. FSC Code 6120, SIC Code 3612,
Size standard 750 employees apply. All qualified sources are requested
to submit sufficient information which clearly shows they meet the
above criteria. Please fax required info to 808/471-5750 or
808/474-8885 and include your phone and fax number. As an alternative
you can mail the required info to the contracting office identified
above to reach us by the date specified in item 10. (0333) Loren Data Corp. http://www.ld.com (SYN# 0371 19951130\61-0010.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|