|
COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 8,1995 PSA#1486Regional Contracting Department (Code 201A), Fleet and Industrial
Supply Center, Box 300, Pearl Harbor, HI 96860-5300 61 -- SUBSTATION UNIT, 12KV SOL N00604-96-Q-0016 DUE 122695 POC
Contact Point: Ms. Paula Fukuda, 808/474-2397, ext. 209, Contract
Specialist, Ms. Juliana Basile, Contracting Officer Substation unit, 12
KV. Secondary shall consist of (a) incoming transition section, (1)
transformer section, (1) outgoing transition section, and (1) secondary
main switchgear section. The substation shall be designed for indoor
service. (A) Primary transition section: Provide transition section for
cable connection between the existing primary switchgear and the new
transformer, support cable connections between the high voltage air
circuit breaker and transformer primary by porcelain insulators, and
size brace cable to withstand the maximum available short circuit
capacity of 500 MVA. (B) Transformer section: The transformer section
shall be oil-insulated, rated 500 KVA, 55/65 degree C temperature rise,
60 HZ, 3-ph, 12 KV, 95 KV Bil primary connected delta to 240V secondary
connected delta. Minimum tested impedance shall not be less than 5%.
The transformer shall have (4) exter- nally operated 2-1/2%. Full
capacity taps, (2) above and (2) below rated voltage. Transformer shall
have stainless steel diagrammatic nameplate and nema standard
maintenance devices. Oil-insulated transformers shall have an
insulation system rated 55/65 degree C rise to allow the transformer to
have a continuous overload capacity of 12% at rated voltage without
exceeding 65 degree C winding temperature rise above 40 degree C
maximum ambient. The insulating liquid shall be mineral oil conforming
to ASTM D 3487, Type 11. It shall be tested in accordance with ASTM D
117, provide identification of transformer as 'non-PCB' on the
nameplate. (C) Secondary transition section: Provide transition section
for busbar connection to the transformer secondary. Support busbar
connections between the transformer secondary and the low-voltage power
circuit breaker by porcelain insulators, and size and brace bus to
withstand the maximum available short circuit capacity of 500 MVA. (D)
Secondary main switchgear section: ANSI/IEEE C37.20.1 for metal-
enclosed, low-voltage power circuit breaker type, insulated for 600V
for use on a 240V system, each steel unit forming part of the outgoing
secion structure shall be a self-contained housing having individual
breaker or instrument compartment, and a full height center and rear
compartment for the bare busses and outgoing cable connections. Equip
individual circuit breaker compartments with primary and secondary
contacts, rails, disconnecting mechanism parts, and a cell interlock to
prevent moving the removable element into or out of the ''connected''
position while the circuit breaker is closed. (1) Phase busses and
connections-mount bus structure on insulates supports of high-impact,
non-tracking, high quality insulating material and brace to withstand
the mechanical forces exerted during short-circuit conditions when
connected directly to an 11.5 KV system having maximum 500 MVA short
circuit capacity. Bus bars shall be high conductivity copper having
silver plated joints. Make bus bar connections from main buses to the
incoming circuit breaker studs. Equip outgoing circuit breaker studs
with mechanical clamp type cable connectors for the size of cable
shown. Provide cable supports for outgoing cables. Wire secondary
circuits including heater circuits, to terminal blocks. Terminal blocks
shall be readily accessible for making external connections as
required. (2) Ground bus. Provide a copper ground bus secured to each
vertical structure and extending the entire length of the switchgear.
Include provision for making the station ground connections. (3) Main
circuit breaker 48 VDC. Electrically stored energy draw out type with
an interrupting rating of not less than 50,000A at 240V. Breaker frame
size shall be 1600A. Equip breaker with solid state trip device with
long time, ground fault and adjustable short time, time tripping
characteristics so that branch breakers will normally trip first on
overload and at lower fault current levels. Key interlock main
secondary breaker with the existing primary air breaker to prevent
operation of the primary air breaker with the secondary main breaker
closed. Equip electrically operate breaker with motor charged, stored
energy closing mechanism to permit rapid and safe closing of the
breaker against fault currents within the short time rating of the
breaker, independent of the operators strength or effort in closing the
handle. (a) Contacts: silver plated, multifinger, positive pressure,
self- aligning type for auxiliary, control and main draw out contacts.
(b) Each draw out braker shall be provided with four-position
operation. Each position shall be clearly identified by an indicator on
the circuit breaker front panel. (c) Connected position: Primary and
secondary contacts are fully engaged. The breaker must be tripped
before it can be racked into or out of this position. (d) Test
position: Primary contacts are disconnected but secondary contacts
remain fully engaged. Position shall allow complete test and operation
of the breaker without energizing the primary circuit. (e)
Disconnected position: Primary and secondary contacts are disconnected.
(f) Withdrawn (removed) position: Places breaker completely out of
compartment, ready for removal. (E) Provide heaters in each primary and
secondary switchgear section. Heaters shall be rated 120V, shall have
sufficient capacity to control moisture condensation in the
compartments, and shall be sized 250W (minimum). Heaters shall be
controlled by a thermostat and humidistat. NOTE: Dimensions for new
switchgear sections are critical due to surrounding available space.
Vendor shall furnish shop drawings for approval with its quotation.
Dimensions of switchgear cannot exceed the following: width 78'' by
height 90-1/2'' (Westinghouse porceline type), length 10.00''. Deliver
one each to Pearl Harbor, Hawaii by 90 days after date of order. All
responsible sources may request a copy of the solicita- tion.
Prospective offerors are requested to provide with their request for
the solicitation, their phone and facsimile numbers. Requests may be
made via FAX 808/471-5750, or by writing the contracting office above.
This is a 100 percent small business set-aside and note 1
applies.(0340) Loren Data Corp. http://www.ld.com (SYN# 0262 19951207\61-0001.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|