COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 13,1995 PSA#1489Regional Contracting Department (Code 201B.PM), Fleet and Industrial
Supply Center, Pearl Harbor, HI 96860-5300 61 -- DIESEL ENGINE GENERATOR/RECTIFIER SETS SOL N00604-96-R-0018 DUE
022696 POC Contact Point: Paulette Mesiona, 808/474-2397 Ext. 219,
Contract Specialist, Robert S. Kay, Contracting Officer Diesel Engine
Generator/Rectifier Sets. Generator/Rectifier output must be capable of
providing 325 KW Direct Current, and 15 KW auxiliary (hotel) 120 Volt
single phase A/C. System shall be capable of producing it's specified
DC and AC auxiliary output continuously and simultaneously and each
(AC/DC) shall be capable of sustaining intermittent overloads of 19%
for 120 minutes, and 50% for one (1) minute. The generators shall be
self exciting, brushless and shall conform to NEMA MG-1. Maximum
voltage rating for the main generator shall be 480 VAC. Estimated
quantity required is six (6), 2 sets in FY96, 2 sets in FY97 and 2 sets
in FY98. Inspection, testing, and acceptance shall be performed at the
contractor's facility, and witnessed by Government Representative(s).
Government will install the generators on the shipyard cranes. Sets
shall be capable of fitting through crane openings of 5' width x 17''
length for two (2) sets, 5' width x 19'6'' length for 2 sets, and 7'
width x 20' length for 2 sets. Drawings will be provided with the
solicitation. Delivery to be F.O.B. destination Pearl Harbor Naval
Shipyard, Hawaii within 120 days after order or modificaiton. All
responsible sources may submit a proposal which shall be considered by
the agency. Please fax your request for the solicitation package to
(808) 471-5750 or (808) 474-8885 and include with your request for your
phone and Fax numbers. As an alternative you can submit a written
request to the Contracting Office idenified above. (0345) Loren Data Corp. http://www.ld.com (SYN# 0254 19951212\61-0001.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|