COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 7,1996 PSA#1526Western Area Power Administration, 114 Parkshore Drive, Folsom, CA
95630 Atn:1521 59 -- POLYMER INSULATORS-MARKET RESEARCH INFORMATION POC Sharon Bates,
Contract Specialist, (916) 353-4469. Western Area Power Administration,
Sierra-Nevada Region is soliciting vendor information for possible
contract arrangement for polymer insulators. The information provided
should address whether this requirement can be met with commercial type
items, or modified commercial type items as defined in Federal
Acquisition Regulation (FAR) 2.1. Vendors are requested to send product
information that meets the following criteria: Non-Ceramic insulators
to be used as replacement parts on a 230 kV high voltage transmission
line. The insulators shall have end fittings made of high-strength
ductile iron, galvanized to resist corrosion, and pressed onto a
fiberglass rod covered with continuous silicone rubber weather sheds.
Corona rings shall be provided. Insulators must be able to withstand
high pressure' washing with water. ITEM 001 - (450 Each) Insulator,
Suspension, 86'' Long, polymer w/corona ring, Tower End Fitting - Eye,
Line End Fitting - Ball (ANSI 52-5), Corona Ring (tower end) - None,
Corona Ring (line end) - 8 inches, Number Of Sheds - 47, Approximate
Weight - 23 lbs, Section Length - 86 Inches, Shed Diameter - 5 Inches,
Shed Spacing - 1.5 Inches, Dry Arc Distance - 77 Inches, Leakage
Distance - 271 Inches, 60 Hz Dry Flash Over - 750 kV, 60 Hz Wet Flash
Over - 645 kV, Impulse Positive Flash Over - 1236 kV, Impulse Negative
Flash Over - 1301 kV, Specified Mechanical Load - 25,000 lbs., Routine
Test Load - 12,500 lbs. Brand name or equal to Reliable Power Products
P/N S198086BA00 ITEM 002 - (30 Each) Dead-End, 86'' Long, Polymer,
w/corona ring, Tower End Fitting - Eye, Line End Fitting - Ball (ANSI
52-11), Corona Ring (tower end) - None, Corona Ring (line end) - 8
inches, Number of Sheds - 46, Approximate Weight - 31 lbs., Section
Length - 86 Inches, Shed Diameter - 5.5 Inches, Shed Spacing - 1.5
Inches, Dry Arc Distance - 75 Inches, Leakage Distance - 263 Inches, 60
Hz Dry Flash Over - 724 kV, 60 Hz Wet Flash Over - 625 kV, Impulse
Positive Flash Over - 1194 kV, Impulse Negative Flash Over - 1258 kV,
Specified Mechanical Load - 50,000 lbs., Routine Test Load - 25,000
lbs. Brand name or equal to Reliable Power Products P/N S29808BA00 It
is intended that this acquisition will be conducted IAW FAR Part 12,
therefore, customary industry practices relating to modifying or
customizing items, warranty, financing, discounts or other contractual
terms under which commercial sales of the products are made are also
requested. Please send product information and information related to
standard commercial practices to: DOE- WAPA, Sierra-Nevada Region, 114
Parkshore Drive, Folsom, CA 95630, ATTN: Sharon Bates. This is a
combined synopsis/solicitation for commercial items prepared IAW the
format in FAR Subpart 12.6, as supplemented with additional information
included in this notice. This announcement constitutes the only
solicitation; proposals are being requested and a written solicitation
will not be issued. All responses should be submitted no later than
4:00 p.m. (PST), 02/20/96. Information hours 8:00 - 4:30pm (PST),
Monday thru Friday. (0036) Loren Data Corp. http://www.ld.com (SYN# 0271 19960206\59-0027.SOL)