Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 8,1996 PSA#1527

U. S. Department of Commerce, NOAA, Central Administratrive Support Center, 601 East 12th St., CC33:JAS, Rm. 1756, Kansas City, Missouri 64106

41 -- AIR-CONDITIONING EQUIPMENT SOL NAAW6600600107JAS DUE 031996 POC Jackie Shewmaker (816) 426-7129 extension 221 The National Weather Service, Tucson, Arizona has a need for packaged indoor computer room type air conditioning units and outdoor air cooled condenser systems (PAC units) for installation by others. GENERAL: PAC units shall include: A) downflow indoor air conditioning unit with fans, motor, direct expansion cooling coils, dual semi-hermetic compressors, dual refrigeration circuits with 4 stage control, infrared humidifier, staged electric reheat, control system and instrumentation, filters, non-locking disconnect switch on front of unit, firestat, and structural base (floorstand) with turning vanes. B) one auto-changeover control cabinet and one thermostat complete with controls for mounting on the wall between the indoor PAC units that automatically sequences two units. C) air-cooled condenser and disconnect switch for outdoor mounting. Only written requests to receive a copy of RFQ number NAAW6600600107JAS will be accepted and shall include a point of contact, phone number, fax number, and mailing address. Facsimile requests to 816-426-7530 will be accepted; however receipt by the government is the responsibility of the sender. All responsible sources may submit a response which shall be considered by the agency. (0037)

Loren Data Corp. http://www.ld.com (SYN# 0276 19960207\41-0001.SOL)


41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page