|
COMMERCE BUSINESS DAILY ISSUE OF MARCH 11,1996 PSA#1548Bureau of Reclamation, Acquisition Operations Branch, Code D-7810,
Denver Federal Center, PO Box 25007, Denver CO 80225 C -- REMOVE AND SHIP FOUR INTACT, FULL THICKNESS PRESTRESSED CONCRETE
PIPE WALL SAMPLES SOL 1425-96-RQ-81-00057 DUE 042596 POC Evelyn M.
Tate, Contracting Officer, 303/236-8040 extension 228 Concerns having
the ability to remove and ship four intact, full-thickness,
Hayden-RhodesAqueduct prestressed concrete pipe wall samples (about
3-feet circumferential by 1-foot longitudinal by 2-feet thick) from at
least four pipes exposed on two previously excavated sites located on
the New River Arizona Project, near Phoenix, AZ are requested to give
written notification, including a telephone number for a POC to the
acquisition office listed in this notice within 30 calendar days from
the date of synopsis. The Bureau of Reclamation, requires a Contractor
for removal of at least four intact, full-thickness, Hayden-Rhodes
Aqueduct (HRA) prestressed concrete pipe wall samples. Full-thickness
samples must be externally acquired through thick pipe walls
sequentially consisting of mortar (about 3/4-inch thick), steel wire
(about 1/4-inch in diameter, spaced every 1/4-inch), concrete (about
2-feet thick) and possibly a steel cylinder (about 1/16-inch thick).
Excavation of the 252-inch diameter pipes will be performed by
Reclamation prior to sampling; internal access through the siphons will
not be permitted unless permission is granted on an emergency basis by
Reclamation in accordance with Reclamation construction safety
standards. At each excavation site, excavations will be performed to
the joint of the two pipe units to be exposed. Thereafter, about
one-third of each pipe (each 22-feet long) will be exposed from the
joint in the longitudinal direction. Additionally, about two feet right
of the crown and four feet left of the crown will be exposed
circumferentially. Full-thickness samples must be acquired which
preserve the in situ environment about each wire's periphery inclusive
of the bond to the mortar and concrete core; thus the cut wire must be
externally and mechanically restrained from moving off of the concrete
pipe core. Thereafter, the exposed surfaces of the sampled areas must
each be covered and secured with a plate that is of sufficient
thickness and strength to resist at least 25 feet of earth overburden.
The plates must be fastened in place. If the plates and fasteners are
comprised of ferrous components they must be completely coated with a
Reclamation-approved corrosion-resistant material. The acquired
samples must be shipped by the contractor, using a contractor -supplied
method that will preserve intact sample integrity, to the Engineering
and Research Laboratory, Building 56, in Denver, Colorado where they
will be subsequently prepared by Reclamation for microscopic analysis.
Samples must be acquired and delivered by May 3, 1996. Previous
Reclamation experiments have indicated that if a prestressing wire is
cut externally through the mortar coating, full wire stress will be
established at a circumferential distance of about 18 to 24 inches from
the initial cut via expansion and anchoring of the wire into the mortar
coating as well as frictional restraint. Thus, circumferential sample
lengths of about 3-feet minimum are required to obtain a preserved wire
environment representative of in situ conditions at sample center with
no external restraints. When external mechanical restraints are
applied, they serve to further compress the wire against the concrete
core thereby preventing less of it from becoming totally stress
-relieved and preserving more of an intact, representative sample over
the 3-foot circumferentiallength. Contractor-supplied mechanical
restraints covering an external surface area of 3-feet circumferential
by 1-foot longitudinal minimum, are therefore required (1) during
sample removal to hold the wires in place thereby providing a large
preserved area representative of in situ conditions towards the sample
center and (2) after sample removal to provide a means of gradual
stress-relief of the prestressing wire towards the sample center as
mechanical restraints are subsequently and systematically removed from
the ends by Reclamation to facilitate additional sample modifications.
On thinner-walled pipes, the mortar-wire-concrete interface has been
successfully preserved by use of metal banding straps that were
inserted through circumferential cuts and tightened around the sample
prior to cutting of the prestressing wire and complete sample removal.
The procedure allowed for gradual stress-relief of the wire and an
intact, preserved specimen toward the center as banding straps were
subsequently removed from the ends. After additional Reclamation
cutting and applications of epoxy, a thin section representative of the
in situ wire environment, about the size of a microscope slide, was and
will be ultimately produced for the purposes of petrographic analysis.
The removal of samples from large diameter pipe necessitates the use
of contractor-supplied specialized equipment, namely a wire saw, which
provides the only known practical means of acquiring specimens from
thick-walled structures. Associated equipment, materials and services
likely to be required: (1) to initially core through the pipe walls to
allow for positioning of a specialized wire saw into the pipe interior
from the pipe exterior. (2) to provide for at least 3-feet
circumferential by 1-foot longitudinal mechanical restraint over the
external pipe surface to prevent the prestressing wire to be cut from
lifting off of the concrete pipe core (i.e. perhaps by use of
mechanical restraints such as bolts, angle irons, steel plates or a
combination thereof). (3) to saw through the reinforcing wire (i.e
probably by circular saws) as well as chip concrete and mortar (i.e.
likely with pneumatic hammers) to provide a path or guide for the wire
saw. (4) to support the heavy (about 900 pound), full-thickness sample
during cutting and removal. (5) to support and transport the removed
specimens in intact and preserved form to the Reclamation laboratory in
Denver, Colorado (i.e. likely by pallets, steel bands via truck). (6)
to cover and secure all exposed surfaces of the sampled areas with
plates that are of sufficient thickness and strength to resist at least
25 feet of earth overburden. The plates must be fastened in place (i.e.
likely with bolts). If the plates and fasteners are comprised of
ferrous components they must be completely coated with a
Reclamation-approved dielectric material (i.e. epoxy or moisture cured
urethane). (therefore, 7) to provide a safe working environment in
compliance with Reclamation construction safety standards. Electricity,
compressed air and water will not be available at the excavation sites;
thus self-contained, contractor-provided equipment (i.e. generators,
compressors, water storage containers) will be required for the
operation of contractor-supplied equipment (i.e. saws, pneumatic
hammers). Water is available to the contractor a few miles from the
sampling sites; however, it must be pumped out of canals, stored and
transported to the excavation sites by the contractor for
accessibility. Reclamation believes that only DeAndrea Coring and
Sawing Inc., possesses the unique knowledge, equipment (along with the
associated skills/capabilities necessary to operate this equipment)
and capabilities that are required for obtaining prestressed concrete
pipe samples in an intact and preserved form such that they may be
further modified and studied in sufficient microscopic detail by
Reclamation. The removal of samples from 252-inch diameterpipe, the
largest circular prestressed structures ever built, necessitates the
use of a wire saw, which provides the only known practical means of
acquiring specimens from thick-walled structures. Samples must be
acquired by the beginning of May 1996. This is not a formal
solicitation. Firms that respond shall provide detailed data concerning
their capabilities to meet this requirement. Firms may request to
receive a copy of the solicitation when and if it becomes available.
This notice may represent the only official notice of such a
solicitation. All sources responding to this synopsis shall submit
information relating to business status, including identification as to
whether they are small, large, minority-owned, and/or woman-owned. The
small business size standard for this acquisition is $2.5 Million
average annual receipts over the past three years. See Note 22. (0067) Loren Data Corp. http://www.ld.com (SYN# 0036 19960308\C-0003.SOL)
C - Architect and Engineering Services - Construction Index Page
|
|