COMMERCE BUSINESS DAILY ISSUE OF MARCH 21,1996 PSA#1556U.S. Army Engineer District, Savannah, P.O. Box 889, Savannah, Georgia
31402-0889 59 -- CIRCUIT BREAKERS - RETROFIT SULFUR HEXAFLUORIDE (SF6) GAS
GENERATOR CIRCUIT BREAKERS SOL DACW21-96-B-0051 DUE 050796 POC Kathleen
Achord, Contract Specialist, (912) 652-5169 or Judy Hackney,
Contracting Officer. Proposed procurement of four (4) retrofit
station-type generator circuit breakers, spare parts, and the services
of one or two Erecting Engineers. The breakers will replace existing
Westinghouse Type 150-CA-1500, three-pole, air blast breakers. The
circuit breakers shall be three-pole, single-throw, fully automatic,
single pressure interrupter units with pneumatic, hydraulic, or spring
operating mechanism. The breakers shall use sulfur hexafluoride (SF6)
gas as a dielectric and as an arc extinguishing medium. The retrofit
circuit breakers will be designed to utilize the existing Westinghouse
switchgear cubicles, current transformers, disconnect switches, door
interlocks and connect to the existing isolated phase bus. Application
of the circuit breakers will be in a hydroelectric powerhouse at an
altitude below 3,300 feet, within ambient temperature extremes of 0
degree C to +40 degrees C. It is estimated that the solicitation will
be issued on 4 April 1996. This is a Civil Works Program procurement
and is not funded by the Department of Defense. Only written requests
for the plans and specifications will be accepted. Required bid package
can be obtained from the Savannah District. (0079) Loren Data Corp. http://www.ld.com (SYN# 0248 19960320\59-0004.SOL)
59 - Electrical and Electronic Equipment Components Index Page
|
|