COMMERCE BUSINESS DAILY ISSUE OF MARCH 22,1996 PSA#1557Raytheon Engineers & Constructors, P O Box 5888, Denver, CO 80217 36 -- INDUCED DRAFT FANS AND DRIVE SYSTEMS SOL ANG5CQ04-a DUE 042496.
Contact Mr. Stephen D. Hoskins, 303/843-2359. The following equipment
will be purchased as part of the Chemical Stockpile Disposal Program
for the Department of the Army: Equipment required includes induced
draft fans, controls, drive systems (including transformers), lube oil
systems (if required for fan), interconnecting ducting and expansion
joints for four furnace systems. Electrical power will be supplied at
4160V/60Hz. All equipment may be purchased in one package or by two
separate packages as follows: 1.) fans, controls, lube oil systems (if
required for fan), interconnecting ducting and expansion joints, and
required for fan), interconnecting ducting and expansion joints, and
2.) drives (including transformers). Procurement may include options
for six (6) additional sites within the continental U.S. The fan/drive
assemblies for each furnace system may include one (1) or two (2)
units mounted on separate baseplates with interconnecting ducting to
provide the required volume and pressure. The number of units (stages)
per furnace system will be determined by the fan manufacturer based on
the operating conditions. The approximate fan operating conditions are
as follows: FAN 101 (INITIAL CONDITIONS): Inlet (ACFM) - 10,800 (max),
2300 (min); density (lb/cu. ft.) - 0.0382 (normal), 0.0364 to 0.0394
(range); inlet temperature (degrees F) - 350 (normal); differential
pressure (IN W.C.) - 23.1 (max), 10.9 (min). FAN 101 (FUTURE
CONDITIONS): Inlet (ACFM) - 5,750 (max), 1040 (min); density (lb/cu.
ft.) - 0.0548 (normal), 0.0391 to 0.0626 (range); inlet temperature
(degrees F) - 135 (normal), 350 (max); differential pressure (IN W.C.)
- 66.4 (max), 5.4 (min). FAN 102 (INITIAL CONDITIONS): Inlet (ACFM) -
17,100 (max), 2900 (min); density (lb/cu. ft.) - 0.0377 (normal),
0.0380 to 0.0448 (range); inlet temperature (degrees F) - 178 (normal);
differential pressure (IN W.C.) - 80.2 (max), 18.6 (min). FAN 102
(FUTURE CONDITIONS): Inlet (ACFM) - 9,000 (max), 1500 (min); density
(lb/cu. ft.) - 0.0463 (normal), 0.0442 to 0.0598 (range); inlet
temperature (degrees F) - 135 (normal), 170 (max); differential
pressure (IN W.C.) - 121.2 (max), 14.5 (min). FAN 103 (INITIAL
CONDITIONS): Inlet (ACFM) - 39,500 (max), 3300 (min); density (lb/cu.
ft.) - 0.0396 (normal), 0.0396 to 0.0470 (range); inlet temperature
(degrees F) - 169 (normal); differential pressure (IN W.C.) - 82.4
(max), 7.4 (min). FAN 103 (FUTURE CONDITIONS): Inlet (ACFM) - 23,300
(max), 1600 (min); density (lb/cu. ft.) - 0.0462 (normal), 0.0445 to
0.0609 (range); inlet temperature (degrees F) - 135 (normal), 164
(max); differential pressure (IN W.C.) - 113.4 (max), 6.2 (min). FAN
104 (INITIAL CONDITIONS): Inlet (ACFM) - 15,700 (max), 3000 (min);
density (lb/cu. ft.) - 0.0362 (normal), 0.0362 to 0.0375 (range); inlet
temperature (degrees F) - 171 (normal); differential pressure (IN W.C.)
- 82.1 (max), 16 (min). FAN 104 (FUTURE CONDITIONS): Inlet (ACFM) -
8,000 (max), 1500 (min); density (lb/cu. ft.) - 0.0435 (normal), 0.0420
to 0.600 (range); inlet temperature (degrees F) - 135 (normal), 170
(max); differential pressure (IN W.C.) - 109.6 (max), 16 (min). Drives
are expected to range from 100 to 600 HP. Companies interested in
receiving a Request For Proposal Package for either one package or both
(please specify) should contact Stephen D. Hoskins at (303) 843-2359 or
notify via fax at (303) 843-2150 by April 24, 1996. (080) Loren Data Corp. http://www.ld.com (SYN# 0257 19960321\36-0001.SOL)
36 - Special Industry Machinery Index Page
|
|