|
COMMERCE BUSINESS DAILY ISSUE OF APRIL 19,1996 PSA#1577Navy Public Works Center, 901 M Street, S.E., Bldg. 175, Washington, DC
20374-5095 Z -- REPLACE FIRE PROTECTION SYSTEM, BUILDINGS 1 THROUGH 10, NATIONAL
NAVAL MECIDAL CENTER, BETHESDA, MARYLAND SOL N68925-93-R-A335 DUE
071196 POC Rhonda Chaney, Contract Specialist, FAX (202)685-8236. The
design/build solicitation is for technical and cost submissions for a
complete new addressable fire alarm system and installation as a
replacement for the existing Fire Life Safety System (FLSS) serving
Buildings 1 through 10 at the National Naval Medical Center in
Bethesda, MD. All operational parameters of the new FLSS shall be
consistent with the existing FLSS except those changes which are
warranted by the current NFPA or other code requirements and
requirements specified herein. The design and installation of this
system is expected to be completed within 12 months from the date of
contract award. The new system will be a stand alone system independent
of the building's security and management system. The specific
requirements and descriptions of each item required are given in
Section 16725 of Appendix D, Paragraph 1.4.1 and 2.2. The Scope of Work
shall include the following: (a) Replace all existing alarm signal
initiating appliance with ''state- of the art'' addressable devices.
(b) Replace local zone controls with microprocessor based transponders.
(c) Replace the annunciation panel in the Emergency Command Center.
Upgrade all other panels to comply with NFPA-72. (d) Replace all
existing fire alarm control panels (FACP's) with ''state-of the art''
microprocessor based fire alarm control panels. Interlink all FACPs
within Buildings 1 through 10 in a supervised network. (e) Provide a
system of microprocessor based field programmable FACPs, which signal
the pre-alarm, normal, trouble, fire alarm status and address of all
initiating devices, audible and visible indicating devices, control
existing fire fighters' telephones and zone speaker systems. Visible
indicating devices and fire fighter telephones need not be replaced,
however, they shall be supervised through the new FLSS addressable
system. Provide an interface for the FLSS network for communications
between buildings and remote display/control terminal units. Provide a
supervised local area network for the system complete with display
terminals and interface electronics (See Paragraph 2.2.13 of Section
16725 Appendix D for CRT display requirments. (f) Replace the existing
fire alarm system's operational relay network with a supervised relay
network system. This system shall replace the controls for elevator
capture, HVAC controls, Halon and fire extinguishing systems and fire
pump controls. (g) Provide a system which shall supervise the building
networks' existing firefighter's telephone systems, the building's
existing indicating and notification appliances, the existing
annunciator panels, all systems' wiring and control network wiring. (h)
Remove all unused, accessible and existing conduits and cables which
are not to be reused by the replacement FLSS system. Abandon in place
all inaccessible conduits (such as those within slabs on masonry walls)
and cap their exposed ends. (i) Provide a complete system fully
operational system with no ground faults and (with remote graphic
terminal stations as indicated in Section 3.9.1). (j) Replace the
existing page-all call system with a supervised zone speaker system
compatible with the new FLSS which provides existing page-all call
functions. (k) All damaged surfaces and areas must be restored and
refinished to match existing finishes. All fire wall penetrations must
be filled with materials which shall match the fire wall rating and
flame spread rating. (l) Provide a full 2 year warranty, which covers
parts, materials and labor for the system. The contractor shall warrant
the system to be free from defects in materials, parts and overall
operation. This shll include any re-used conduits, cables and wiring.
(m) Provide a complete set of drawings showing all devise locations and
wiring, wiring riser diagrams; provide a complete set of operation and
program manuals. (n) The contractor shall have a fully qualified
quality (CQC) control representative on the job site at all times
during construction. He shall be fully familiar with the project to be
installed and his creditials shll be acceptable to the government.
This work includes designing and providing a replacement, addressable
fire alarm system as described herein for each building segment shown
in sheets b1-b140 of Appendix B for the Buildings 1 through 10 of the
National Naval Medical Center in Bethesda, MD. The system shall include
all necessary wiring, conduits, raceways, pull boxes, terminal
cabinets, outlet and mounting boxes, addressable alarm, and supervisory
signal initiating devices, interfaces with existing alarm notification
appliances, and all other accessories and miscellaneous items required
for a complete operating system, even though each item is not
specifically mentions or described herein. The offeror shall provide
separate techinical, cost and business management proposals for
''design, hardware procurement and installation of an independent
complete Fire Life Safety System (FLSS) in Buildings 1 through 10 at
the National Naval Medical Center in Bethesda, Maryland. Cost is equal
in importance to the Technical/Business Managment factors. Demonstrate
your understanding of the FLSS configuration required to replace the
current Fire Life Safety System. Fully Describe the alternative
trade-offs that you have made in arriving at your proposed design
approach. The offeror shall demonstrate his understanding of the
existing fire alarm initiating devices, controls and alarm appliances
and operational controls required for various alarm conditions. The
offeror should also address the inherent problems associated with
''down time'' expected during replacement of the existing system within
the hospital complex and how he would provide required equivalent fire
alarm protection during any such ''down time''. The offeror shall
discuss the proposed design approaches which meet the needs, overcome
technical difficulties and satisfy the objectives of this procurement.
The offeror shall as a minimum, describe his understanding and
potential solution. Describe fully how the system is to be maintained,
how the operational staffing requirements are to be met, the extent to
which the system is self diagnostic and its ability to locate and
correct problems without manual intervention. Explain the full extent
and limits of your FLSS warranty. Describe how the offeror intends to
replace the existing system's annunciations, controls and any ancillary
displays. A proposal shall detail the sequence of construction, the
time required for each phase of the construction and the sequence for
transfer from the existing fire life safety to the new fire life safety
system, with no expected down time. Describe the organization and the
management methods that will be used for technical management of this
proposed contract project. The offeror shall describe his ability to
provide an on-going off-site and on-site support for this FLSS
replacement project. Indicate how you plan to react to unforeseen peak
work leak periods, technical problems and loss of key personnel.
Provide a synopsis of your company's past technical experience on
similar sized projects, which would especially qualify your company for
meeting all of the requirments for this proposal, Limitations on the
size of the Technical Proposal, Summary of Deviations/ Exceptions to
the Techincal Proposal, Cost Proposal. The Estimated Cost Range is
between $1 million and $5 million. The Standard Industrial Code is
1731. The Small Business Size Standard is $7.0 million. The Bid Opening
Date is 11 July 1996. The project Site Visit is scheduled for 10:00am,
1 July 1996. Submit requests for receving plans and specifications
when the become available on or about 10 June 1996 by fax to
(202)685-8288, Attn: Bob Roth. There is no charge for plans and specs.
One set per firm. Fax all bid inquiries to (202)685-8236. Telephone
inquiries and requests will not be honored. (0108) Loren Data Corp. http://www.ld.com (SYN# 0122 19960418\Z-0001.SOL)
Z - Maintenance, Repair or Alteration of Real Property Index Page
|
|