COMMERCE BUSINESS DAILY ISSUE OF MAY 15,1996 PSA#1595U.S. Army Engineer District, Savannah, 100 W. Oglethorpe Avenue,
Savannah, GA 31402 59 -- CIRCUIT BREAKERS - RETROFIT SULFUR HEXAFLUORIDE (SF) GAS
GENERATOR CIRCUIT BREAKERS SOL DACW21-96-B-0065 DUE 082196 POC Contact
Point, Julie Talley (912) 652-5898, or Judy I. Hackney, Contracting
Officer. The U.S. Army Corps of Engineers has a requirement for one (1)
sulfur hexafluoride (SF6) gas generator circuit breaker rated 15.5 kV,
3,000 amperes, 63 kA symmetrical interrupting capability, six (6)
retrofit sulfur hexafluoride (SF6) gas generator circuit breakers rated
15.5 kV, 3,000 amperes, 63 kA symmetrical interrupting capability, and
seven (7) generator neutral grounding cubicles. Six breakers are to
retrofit existing Westinghouse 150-CA-1000, 3,000 ampere airblast
circuit breakers. Spare parts and the services of an Erecting Engineer
are also required. The circuit breakers shall be three-pole, single
throw, fully automatic, single pressure interrupter units with
pneumatic, hydraulic, or spring operating mechanism. The breakers shall
use sulfur hexafluoride (SF6) gas as a dielectric and as an arc
extinguishing medium. The retrofit circuit breakers will be designed to
utilize the existing Westinghouse switchgear cubicles, current
transformers, disconnect switches, door interlocks and connect to the
existing isolated phase bus. Application of the circuit breakers will
be in a hydroelectric powerhouse at an altitude below 3,300 feet,
within ambient temperature extremes of 0 degrees C to +40 degrees C. It
is estimated that the solicitation will be issued on July 12, 1996.
This is a Civil Works Program procurement and is not funded by the
Department of Defense. Only written requests for the plans and
specifications will be accepted. (0134) Loren Data Corp. http://www.ld.com (SYN# 0263 19960514\59-0001.SOL)
59 - Electrical and Electronic Equipment Components Index Page
|
|