COMMERCE BUSINESS DAILY ISSUE OF MAY 17,1996 PSA#1597Department of the Army, New England Division, Corps of Engineers, 424
Trapelo Road, Waltham, Massachusetts 02254-9149 41 -- REFRIGERATION COMPRESSOR UNIT SOL DACA33-96-R-0011 DUE 070996
POC Julie Mackley, 617-647-8413 Request for proposal to Furnish,
Deliver, and Install, F.O.B. Destination, U.S. Army Cold Regions
Research and Engineering Laboratory (CRREL), Hanover, New Hampshire,
One 115 (+/-5)-Ton High-Stage Ammonia Refrigeration Compressor (RC3)
similar or equal to Freezing Equipment Sales (FES) Model 16S. The
compressor must be rated at 115 Ton using an equivalent suction of 10
degrees F SST and a condensing temperature of 95 degrees F SDT. The
compressor will be factory assembled on a steel frame and include a 200
HP, Premiumefficiency 460/3/60 Electric Motor, Direct-Coupled to the
Compressor, Oil-Separator Motor, Wye-Delta Close Transition Starter, 3
HP Oil Pump with starter, and Micro-Processor with control language
compatible with FES Micro II control language. Contract is to include
Furnishing and Installation of a water-Cooled Shell-And-Tube Heat
Exchanger which is required to keep the Glycol below 98 Degrees F. The
contractor will supply the heat exchanger, motorized valves for the
glycol and water supply, and the necessary structural support and
mechanical components to install the heat exchanger. The contractor
will restore the insulation where it was removed, as well as insulate
the new piping. The proposed contract listed here is a 100% small
business set-aside. The number of employees of the concern and its
affiliates must not exceed 750 persons. Specifications available on or
about 060796 at no charge. All responsible sources may submit a bid
which will be considered by the New England Division. (0136) Loren Data Corp. http://www.ld.com (SYN# 0233 19960516\41-0001.SOL)